Cosel-JAC-06-223-D

Part #Cosel-JAC-06-223-D
Download 
Cosel-JAC-06-223-D
Ordering information  
Three phase input type(1-stage filter)  
JAC -30 -683 –
O  
JAC series(6-30A)  
1
2
3
4
1
Model Name  
2
Rated Current  
3
Line to ground capacitor code:See table 1.1.  
R
table1.1 Line
 
to ground capacitor code  
Leakage Current  
Line to ground  
Code (Input
 
250/500V 60Hz)
 
capacitor  
(Only “224” is 250/400V 60Hz)
 
(nominal value)  
103  
223  
683  
224  
0.5mA / 1.0mA max  
1.0mA / 2.0mA max  
2.5mA / 5.0mA max  
15mA / 24mA max  
10,000pF  
22,000pF  
68,000pF  
220,000pF  
When the line to ground capacitor code is  
different, the attenuation characteristic is  
different.  
*
4
Option  
D:DIN rail installation type  
The dimensions change when the option is set.  
Refer to External view.  
*
The terminal cover is retracted inside the unit  
DIN rail installation type is option  
H:Ultra high-attenuation type  
“103”,“223”,“683” is applied.  
U:Improve differential mode attenuation  
(Rated voltage 250V)  
Features of JAC series  
Compact and low profile, common mode EMI/EMC filters in 150kHz to 1MHz (1-stage filter)  
–
Three Phase 500 VAC
 
–
Push down type terminal block  
–
Selectable leakage current value, Ultra high-attenuation type “224” for EU (Y type with neutral earth system)  
Specifications  
No.  
1
Items  
JAC-06-683  
AC Three Phase 500 (voltage range:528 max)
 
50/60Hz
*
1
*
2  
10 20  
JAC-10-683  
JAC-20-683  
JAC-30-683  
Rated Voltage[V]  
2
Rated Current[A]  
6
30  
3
Test Voltage (Terminal-Mounting Plate)  
2,500 VAC (Cutoff Current = 100mA), 1minute at room temperature and humidity
 
*
3  
4
Isolation Resistance (Terminal-Mounting Plate)
 
500 VDC 100M
W
min at room temperature and humidity
 
*
4  
5
6
Leakage current 250/500V 60Hz  
DC resistance  
2.5mA/5.0mA max  
100m
W
max  
45m
W
max  
15m
W
max  
8m
W
max  
7
8
9
Safety agency approval temperatures  
Operating temperature  
Operating humidity  
-25 to +85
C
(Refer to Derating Curve)  
-40 to +85
C
(Refer to Derating Curve)  
20 to 95%RH (Non condensing)  
10  
11  
12  
13  
Storage temperature/humidity  
Vibration  
Impact  
-40 to +85
C
/20 to 95%RH (Non condensing)  
2
10 to 55Hz, 19.6m/s (2G), 3min. Period, 1hour each X, Y and Z axis  
2
196.1m/s (20G), 11ms Once each X, Y and Z axis  
Safety agency approvals  
UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565
T
e
il3-1, ENEC  
63
X
44
X
132 mm (W
X
H
X
D) (Option: -D refer to external view)  
[2.48
X
1.73
X
5.20 inches] (W
X
H
X
D)  
14  
Case size (without projection)  
15  
Weight  
440g max  
*
1
Capacitor code “224”
 
: Three Phase
D
-connection 400 (440 max),
Y
–
connection 500 (528 max).  
*
2
“JAC-
OO
–
OOO
-U” :
 
Three Phase 250 (275 max).  
*
3
Capacitor code “224”
 
: 2,800VDC (Cutoff Current = 10mA), 1 minute at room temperature and humidit
y
.  
*
4
Capacitor code “224”
 
: Isolation resistance specification is deleted.  
Circuit Diagram  
Derating Curve  
(1) Line to ground capacitor code : 103, 223, 683  
(2) Line to ground capacitor code : 224  
100  
Case  
Case  
LINE  
LINE  
LOAD  
LOAD  
80  
70  
60  
1
2
4
5
1
2
4
5
3
6
3
6
40  
CX  
CX  
CX  
CX  
CX  
CX  
CY  
CX  
CX  
CX  
CX CX CX  
20  
10  
0
CY  
CY  
-40  
-30 -20  
40  
50  
60  
70  
80  
90  
CX :
Line to line capacitor  
CY :
Line to ground capacitor  
: Mounting Plate  
CX :
Line to line capacitor  
CY :
Line to ground capacitor  
: Mounting Plate  
Ambient Temperature [
 
]  
(3) Line to ground capacitor code : 103, 223, 683  
Option : U  
(4) Line to ground capacitor code : 224  
Option : U  
Case  
Case  
LINE  
LOAD  
LINE  
LOAD  
1
2
4
5
1
2
4
5
3
6
3
6
CX  
CX  
CX  
CY  
CX  
CX  
CX  
CX CX CX  
CX  
CX  
CX  
CY  
CY  
CX :
Line to line capacitor  
CY :
Line to ground capacitor  
: Mounting Plate  
CX :
Line to line capacitor  
CY :
Line to ground capacitor  
: Mounting Plate  
September 16, 2021  
JAC-1  

JAC series(6-30A)  
External view  
This product is shipped in the following condition, because it is equipped with push-down terminals.  
1
The terminal cover is retracted inside the unit.  
2
The screws for connecting the terminals are held in the up right position.  
Standard Type  
132  
[5.20]  
T
e
rminal Cover  
(
T
e
rminal Block screw pitch)  
119  
[4.69]  
2-
f
5.5
[0.22]  
Mounting Hole  
2.5  
32  
[1.26]  
[0.10]  
3-M4  
Output  
T
e
rminal  
Name Plate  
3-M4  
Input  
T
e
rminal  
Mounting Plate  
M4  
Protection Earth  
(Mounting Hole pitch)  
118  
[4.61]  
T
e
rminal cover  
Close the terminal cover  
T
o
lerance :
 
1[ 0.04]  
Weight : 440g max  
Mounting Plate : Iron(surface finishing : nickel plating) t=1.0[0.04]  
Case : PBT  
Dimensions in mm, [
 
]=inches  
T
e
rminal block screw tighting torque M4 : 1.6N
–
m(16.9kgf
–
cm)max  
4.5  
4.5  
[0.18]  
[0.18]  
DIN rail installation Type  
9
[0.35]  
2
132  
[5.20]  
T
e
rminal Cover  
(
T
e
rminal Block screw pitch)  
[4.69]  
119  
2.5  
[0.10]  
32  
[1.26]  
3-M4  
3-M4  
Output  
Input  
T
e
rminal  
Name Plate  
T
e
rminal  
Mounting Plate  
M4  
Protection Earth  
T
e
rminal cover  
Close the terminal cover  
T
o
lerance :
 
1[ 0.04]  
Weight : 440g max  
Mounting Plate : Iron(surface finishing : nickel plating) t=1.0[0.04]  
Case : PBT  
Dimensions in mm, [
 
]=inches  
T
e
rminal block screw tighting torque M4 : 1.6N
–
m(16.9kgf
–
cm)max  
4.5  
DIN rail  
4.5  
[0.18]  
[0.18]  
Note when installing the EMI/  
EMC Filter on a DIN rail.  
¡
DIN rail  
When the EMI/EMC Filter is grounded through  
the DIN rail, the proper noise attenuation may not  
be achieved.  
Name Plate  
Be sure to connect the protection earth (PE) of  
the EMI/EMC Filter body to the earth.  
September 16, 2021  
JAC-2