Littelfuse-ALT-100-3-SW
Protection Relays  
Pump Controls and Liquid Level Controls  
ALT-XXX-1-SW / ALT-XXX-3-SW SERIES  
Alternating Relay  
Description  
The AL
T
–
xxx-1-SW/AL
T
–
xxx-3-SW Series are used to alternate  
between two loads and are commonly used in duplex  
pump-up and pump-down applications to balance the runtime  
of both pumps.  
The ALT relays have a built-in debounce time delay that prevents  
the relay from changing state if the float momentarily bounces,  
and they have a built-in switch to manually force a specific load  
(pump) to operate each time the input float closes. This is helpful  
when performing periodic maintenance or pump repair.  
Must use the OT08PC socket for the 8-pin models, and the OT11PC socket for the  
11-pin models, for UL Rating!  
*Note: Manufacturer’s recommended screw terminal torque for the OT Series  
Octal Sockets is 12 in.-lbs.  
Features & Benefits  
Wiring Diagram  
FEATURES  
BENEFITS  
TYPICAL WIRING DIAGRAM FOR A
L
T
–
XXX-1-SW  
Prevents rapid cycling caused by waves or splashing  
in the tank  
Debounce time delay  
Visual indication of load operation in  
duplex application  
LED indicators  
Built-in manual switch  
to force load operation  
Helpful to control load operation when performing  
periodic maintenance or pump repair  
A
L
T
–
xxx-3-SW  
offers duplexing  
Allows lag pump to energize if lead pump can’t  
handle current demand  
Accessories  
OT08PC 8-pin
 
Octal Socket  
Octal Socket for plug-in units. 8-pin surface &  
DIN rail mountable. Rated for 10A @ 600VAC.  
OT11PC 11-pin
 
Magnal Socket  
11
–
pin surface & DIN rail mountable. Rated for  
10A @ 300VAC  
TYPICAL WIRING DIAGRAM  
FOR A
L
T
–
XXX-3-SW  
Ordering Information  
LINE  
VOTAGE  
MODEL  
MOUNTING DESCRIPTION  
Single float input, two isolated  
Form C relays (DPDT), 2 LEDs  
for load indication  
11-pin  
magnal  
ALT-100-1-SW 95-120VAC  
Three float inputs (lead, lag,  
stop floats), actuating latching  
relays on lead/lag floats,  
2 LEDs for load indication  
ALT-100-3-SW 95-120VAC
 
8-pin octal  
ALT-200-3-SW 190-240VAC 8-pin
 
octal  
Three float inputs (lead, lag,  
stop floats), actuating latching  
relays on lead/lag floats,  
2 LEDs for load indication  
© 2016 Littelfuse Protection Relays & Controls  
Rev: 1-A-062716  

Protection Relays  
Pump Controls and Liquid Level Controls  
ALT-XXX-1-SW / ALT-XXX-3-SW SERIES  
Standards Passed  
Electrostatic Discharge (ESD)
 
IEC 61000-4-2, Level 3, 6kV contact, 8kV air  
Specifications  
Input Characteristics  
Supply Voltage  
Radio Frequency, Radiated  
Fast Transient Burst  
150MHz, 10V/m  
IEC 61000-4-4, Level 3, 3.5kV  
input power and controls  
ALT-100-1-SW,  
ALT-100-3-SW  
ALT-200-3-SW  
Frequency  
Functional Characteristics  
Debounce Time Delay  
ALT-100-1-SW,  
ALT-100-3-SW,  
ALT-200-3-SW  
Output Characteristics  
Output Relay (DPDT)  
Pilot Duty  
General Purpose  
General Characteristics  
Temperature Range  
Maximum Input Power  
95-120VAC  
190-240VAC  
50/60Hz  
Safety Marks  
UL (OT08PC or OT11PC  
octal socket required)  
CE  
UL508 (File #E68520)  
IEC 60947-6-2  
Dimensions  
H
44.45 mm (1.75”);
W
60.33 mm (2.375”);  
D
104.78 mm (4.125”) (with socket)  
0.65 lb. (10.4 oz., 294.84 g)  
DIN rail or surface mount (plug into OT08PC  
or OT11PC socket)  
1 second  
Weight  
Mounting Method  
5 seconds  
Sockets Available  
Model OT08PC  
Model OT11PC  
480VA @ 240VAC  
10A @ 240VAC  
UL Rating 600V  
UL Rating 300V  
-40° to 70°C (-40° to 158°F)  
5 W  