Mueller-Electric-ARA-24-ACA

Part #Mueller-Electric-ARA-24-ACA
Download 
Mueller-Electric-ARA-24-ACA
The
Triplexor and Quadraplexor Alternating Relays
are designed for  
use in
MULTIPLE LOAD
installations that are required to alternate in  
sequence while assuring equal run time on all loadsꢄ They also allow for  
additional loads to run in the event of excess load requirementsꢄ  
The
Triplexor and Quadraplexor
have the option of automatic  
alterations or external clocking alterationsꢄ When the factory installed  
jumper is in place the alternating action is initiated by a control switch,  
which is common with one side of the control voltageꢄ When the jumper  
is removed the alternating action is initiated by an isolated normally  
open switchꢄ  
ARA-XXX-AFE ALTERNATING ACTION  
TRIPLEXOR:
For automatic alterations a factory-installed jumper is in  
place between terminals 3 and 4ꢄ The alternating action is accomplished  
when the control switch between terminals 2 and 4 opensꢄ  
INDꢄ CON
T
ꢄ
E
Qꢄ  
49/Y  
Triplexor  
For external clocking alterations, remove the factory-installed jumper  
between terminals 3 and 4 and place an isolated normally open switch  
between terminals 2 and 3ꢄ The alternating action will occur each time  
this isolated switch is closed and then re-openedꢄ  
SPECIFICATIONS  
CONTROL  
VOLTAGE  
24, 120 VAC
 
10ꢀ, ꢁ0ꢂ/0 ꢃH  
ARA-XXX-AGE  
CONTROL SWITCH
 
2 mA  
CURRENT  
QUADRAPLEXOR:
For automatic alterations, a factory installed jumper  
is in place between terminals 11 and 12ꢄ The alternating action is  
accomplished when the control switch between terminals 2 and 3 opensꢄ  
POWER  
3 VA (Approximately)  
REQUIRED  
For external clocking alterations, remove the factory-installed jumper  
between terminals 11 and 12 and place an isolated normally open  
switch between terminals 2 and 12ꢄ The alternating action will occur  
each time this isolated switch is closed and then re-openedꢄ  
DUTY CYCLE  
Continuous  
Triplexor  
OUTPUT RATING  
24V ꢁA Resistive,
 
2ꢁ VA @ 24VAC  
-120V (3) ꢁ Amp Resistive, 1ꢂ/ hp,  
211 VA @ 120 VAC, Inductive Externally  
Switched to Terminal #2  
In the event of a power failure the Alternating Relays will return to their  
quiescent state and continue sequencing loads on one-at-a-timeꢄ  
Quadraplexo
r
(
4) ꢁ Amp Resistive, 1ꢂ/ hp, 211 VA  
@ 120 VAC, Inductive Externally  
DIMENSIONS
(INCHES)  
Switched to terminal #2  
LIFE EXPECTANCY
 
Mechanical 10,000,000
 
Operations (Minimum)  
Electrical 100,000
 
Operations @ Rated Load  
INDICATORS  
LED’s Show Condition of Outputs  
TEMPERATURES  
RATING  
Operate  
Storage  
-4° to 131°F (-20° to +ꢁꢁ°C)  
-40° to 18ꢁ°F (-40° to +8ꢁ°C)  
ENCLOSURE  
TERMINATIONS  
WEIGHT  
Style “E” Lexan® Surface Mounted  
(12) #8-32 Screw Terminals  
12 to 14 oHꢄ  
NOTE: For Analog signal inputs, ATC offers a duplexing pump control  
the ATC-Digitec 3800 Panel Mete
r
ꢄ  
WIRING  

MODEL

M

N
U

O

M

D

B

E

E
R

L NUMBE
R

ARA  

A
E
CONTROL VOLTAGE  
24 V Triplexor  
24  
120 V Triplexor  
120 V Quadraplexor  
120  
120  
Triplexor  
Quadraplexor (120 V only)  
F
G
The ARA Series Triplexor and Quadraplexor are UL Listed under  
UL File Number Eꢁꢁ82/ꢄ  
192  
Diversified Electronics  
800.727.5646 atcdiversified.com  

The
Expandable Alternating Relays
are designed for use in multiple  
load installations that are required to alternate in sequence and have the  
ability to accept an additional load installation in the futureꢄ  
ARA-120-AME
: The ARA-120-AME is a
Duplexor/Triplexor Alternating  
Relay
ꢄ With the selector switch in position A, this alternating relay will  
duplex the loads on terminals 7 and 9ꢄ With the switch in position B, the  
Alternating Relay will triplex the three loads on terminals 7, 9 and 11ꢄ  
For automatic alterations, a factory-installed jumper is in place between  
terminals 3 and 4ꢄ The alternating action is accomplished when the  
control switch between terminals 2 and 4 opensꢄ  
For external clocking alterations, remove the factory installed jumper  
between terminals 3 and 4 and place an isolated normally open switch  
between terminals 2 and 3ꢄ The alternating action will occur each time  
this isolated switch is closed and then re-openedꢄ  
Expandable Alternating Relays  
ARA-120-ANE
: The ARA-120-ANE is a
Triplexor/Quadraplexor  
Alternating Relay
ꢄ With the selector switch in position A, the Alternating  
Relay will triplex between the loads on terminals 7, 8 and 9ꢄ With the  
switch in position B, the Alternating relay will quadraplex the loads on  
terminals 7, 8, 9 and 10ꢄ  
ORDERING INFORMATION  
MODEL NUMBER  
DESCRIPTION  
For automatic alterations, a factory installed jumper is in place between  
terminals 11 and 12ꢄ The alternating action is accomplished when the  
control switch between terminals 2 and 3 opensꢄ For external clocking  
alterations, remove the factory installed jumper between terminals 11  
and 12 and place an isolated normally open switch between terminals 2  
and 12ꢄ The alternating action will occur each time this isolated switch is  
closed and then re-openedꢄ  
ARA-120-AME  
ARA-120-ANE  
DuplexorꢂTriplexor  
TriplexorꢂQuadraplexor  
DIMENSIONS
(INCHES)  
In the event of a power failure the Alternating Relays will return to their  
quiescent state and continue sequencing loads on one-at-a-timeꢄ  
SPECIFICATIONS  
CONTROL VOLTAGE
 
120 VAC
 
10ꢀ, ꢁ0ꢂ/0 ꢃH  
CONTROL SWITCH
 
2 mA  
CURRENT  
POWER REQUIRED
 
3 VA (Approximately)  
DUTY CYCLE  
Continuous  
Triplexor  
OUTPUT RATING  
(3) ꢁ Amp Resistive, 1ꢂ/ hp, 211 VA  
@ 120 VAC, Inductive Externally  
Switched to terminal #2  
WIRING  
Quadraplexo
r
(
4) ꢁ Amp Resistive, 1ꢂ/ hp, 211 VA  
@ 120 VAC, Inductive Externally  
Switched to terminal #2  
LIFE EXPECTANCY
 
Mechanical 10,000,000
 
Operations (Minimum)  
Electrical 100,000
 
Operations @ Rated Load  
INDICATORS  
LED’s Show Condition of Outputs  
TEMPERATURES  
RATING  
Operate  
Storage  
-4° to 131°F (-20° to +ꢁꢁ°C)  
-40° to 18ꢁ°F (-40° to +8ꢁ°C)  
ENCLOSURE  
TERMINATIONS  
WEIGHT  
Style “E” Lexan® Surface Mounted  
(12) #8-32 Screw Terminals  
12ꢄꢁ to 14 oHꢄ  
193  
Diversified Electronics  
800.727.5646 atcdiversified.com  

OPERATION  
The
ARA-120-AHE
is a special function
TRIPLEXOR
designed for three  
load installationsꢄ This model has a field selection switch that is used to  
omit one of the three loads for general or emergency maintenance while  
duplexing the remaining two loadsꢄ The ARA-120-AꢃE has the option of  
alternating on each load cycle or by external clockingꢄ This alternating  
relay also allows for additional loads to run in the event of excess load  
requirementsꢄ  
INCLUDES  
“LOAD OMIT”  
SWITCꢃ  
The alternating action is initiated by the control switch between  
terminals 2 and 4 when the factory installed jumper is in place between  
terminals 3 and 4ꢄ  
The alternating action may be initiated externally by removing the  
factory installed jumper between terminals 3 and 4 and placing an  
isolated normally open switch between terminals 2 and 3ꢄ An alternating  
action will occur each time this isolated switch is closed and then re-  
openedꢄ  
Special Function Alternating Relay  
The selection switch has the following positions:  
Normal
— Normal operation as Triplexor  
ORDERING INFORMATION  
MODEL NUMBER  
DESCRIPTION  
Omit 1
— Omit load #1 Duplex loads 2 and 3  
Omit 2
— Omit load #2 Duplex loads 1 and 3  
Omit 3
— Omit load #3 Duplex loads 1 and 2  
ARA-120-AꢃE  
Special Function Alternating Relay  
In the event of a power failure, the Alternating Relay will return to its  
quiescent state and continue sequencing loads on one-at-a-timeꢄ  
NOTE: When the “omit load” option is selected, full potential will appear  
on the output terminal of the omitted load when the lag switch between  
terminals 2 and ꢁ closesꢄ It is recommended that the ꢃ-O-A switch be  
placed in the “off” position for the omitted loadꢄ  
DIMENSIONS
(INCHES)  
SPECIFICATIONS  
CONTROL VOLTAGE
 
120 VAC
 
10ꢀ, ꢁ0ꢂ/0 ꢃH  
CONTROL SWITCH
 
2 mA  
CURRENT  
POWER REQUIRED
 
3 VA (Approximately)  
DUTY CYCLE  
Continuous  
Triplexor  
OUTPUT RATING  
(3) ꢁ Amp Resistive, 1ꢂ/ hp, 211 VA  
@ 120 VAC, Inductive Externally  
Switched to terminal #2  
WIRING  
LIFE EXPECTANCY
 
Mechanical 10,000,000
 
Operations (Minimum)  
Electrical 100,000
 
Operations @ Rated Load  
INDICATORS  
LED’s Show Condition of Outputs  
TEMPERATURES  
RATING  
Operate  
Storage  
-4° to 131°F (-20° to +ꢁꢁ°C)  
-40° to 18ꢁ°F (-40° to +8ꢁ°C)  
ENCLOSURE  
TERMINATIONS  
WEIGHT  
Style “E” Lexan® Surface Mounted  
(12) #8-32 Screw Terminals  
1/ oHꢄ  
194  
Diversified Electronics  
800.727.5646 atcdiversified.com  

OPERATION  
The
ARA-120-AJE
is a special function
TRIPLEXOR
designed for three  
load installationsꢄ This model has a field selection switch that is used  
to lock the Alternating Relay into a desired sequenceꢄ The ARA-120-AJE  
has the option of automatically alternating on each load cycle or by  
external clockingꢄ This Alternating Relay also allows for additional loads  
to run in the event of excess load requirementsꢄ  
INCLUDES  
SEQUENCE LOCKING  
SWITCꢃ  
The alternating action is initiated by the control switch between  
terminals 2 and 4 when the factory installed jumper is in place between  
terminals 3 and 4ꢄ The alternating action may be initiated externally by  
removing the factory installed jumper between terminals 3 and 4 and  
placing an isolated normally open switch between terminals 2 and 3ꢄ  
The alternating action will occur each time this isolated switch is closed  
and then re-openedꢄ  
A four position
ROTARY SWITCH
has been incorporated to permit field  
selection of the sequence that is to be maintainedꢄ The selection switch  
has the following positions:  
Triplexor Alternating Relay  
Normal
— Normal operation as a Triplexor  
ORDERING INFORMATION  
Lock 1
— Locks in sequence 1-2-3; No alternation will occur  
while in this positionꢄ  
MODEL NUMBER  
DESCRIPTION  
Lock 2
— Locks in sequence 2-3-1; No alternation will occur  
ARA-120-AJE  
Alternating Relay  
while in this positionꢄ  
Lock 3
— Locks in sequence 3-1-2; No alternation will occur  
while in this positionꢄ  
In the event of a power failure, the alternating relay will return to its  
quiescent state and continue sequencing loads on one-at-a-timeꢄ  
DIMENSIONS
(INCHES)  
SPECIFICATIONS  
CONTROL VOLTAGE
 
120 VAC
 
10ꢀ, ꢁ0ꢂ/0 ꢃH  
CONTROL SWITCH
 
2 mA  
CURRENT  
POWER REQUIRED
 
3 VA (Approximately)  
DUTY CYCLE  
Continuous  
Triplexor  
OUTPUT RATING  
(3) ꢁ Amp Resistive, 1ꢂ/ hp, 211 VA  
@ 120 VAC, Inductive Externally  
Switched to terminal #2  
LIFE EXPECTANCY
 
Mechanical 10,000,000
 
Operations (Minimum)  
Electrical 100,000
 
Operations @ Rated Load  
INDICATORS  
LED’s Show Condition of Outputs  
TEMPERATURES  
RATING  
Operate  
Storage  
-4° to 131°F (-20° to +ꢁꢁ°C)  
-40° to 18ꢁ°F (-40° to +8ꢁ°C)  
WIRING  
ENCLOSURE  
TERMINATIONS  
WEIGHT  
Style “E” Lexan

®

Surface Mounted  
(12) #8-32 Screw Terminals  
17 oHꢄ  
195  
Diversified Electronics  
800.727.5646 atcdiversified.com