Mueller-Electric-ARA-24-ACA
| Part # | Mueller-Electric-ARA-24-ACA |
| Download | Mueller-Electric-ARA-24-ACA |
The
Triplexor and Quadraplexor Alternating Relays
are designed for
use in
MULTIPLE LOAD
installations that are required to alternate in
sequence while assuring equal run time on all loadsꢄ They also allow for
additional loads to run in the event of excess load requirementsꢄ
The
Triplexor and Quadraplexor
have the option of automatic
alterations or external clocking alterationsꢄ When the factory installed
jumper is in place the alternating action is initiated by a control switch,
which is common with one side of the control voltageꢄ When the jumper
is removed the alternating action is initiated by an isolated normally
open switchꢄ
ARA-XXX-AFE ALTERNATING ACTION
TRIPLEXOR:
For automatic alterations a factory-installed jumper is in
place between terminals 3 and 4ꢄ The alternating action is accomplished
when the control switch between terminals 2 and 4 opensꢄ
INDꢄ CON
T
ꢄ
E
Qꢄ
49/Y
Triplexor
For external clocking alterations, remove the factory-installed jumper
between terminals 3 and 4 and place an isolated normally open switch
between terminals 2 and 3ꢄ The alternating action will occur each time
this isolated switch is closed and then re-openedꢄ
SPECIFICATIONS
CONTROL
VOLTAGE
24, 120 VAC
10ꢀ, ꢁ0ꢂ/0 ꢃH
ARA-XXX-AGE
CONTROL SWITCH
2 mA
CURRENT
QUADRAPLEXOR:
For automatic alterations, a factory installed jumper
is in place between terminals 11 and 12ꢄ The alternating action is
accomplished when the control switch between terminals 2 and 3 opensꢄ
POWER
3 VA (Approximately)
REQUIRED
For external clocking alterations, remove the factory-installed jumper
between terminals 11 and 12 and place an isolated normally open
switch between terminals 2 and 12ꢄ The alternating action will occur
each time this isolated switch is closed and then re-openedꢄ
DUTY CYCLE
Continuous
Triplexor
OUTPUT RATING
24V ꢁA Resistive,
2ꢁ VA @ 24VAC
-120V (3) ꢁ Amp Resistive, 1ꢂ/ hp,
211 VA @ 120 VAC, Inductive Externally
Switched to Terminal #2
In the event of a power failure the Alternating Relays will return to their
quiescent state and continue sequencing loads on one-at-a-timeꢄ
Quadraplexo
r
(
4) ꢁ Amp Resistive, 1ꢂ/ hp, 211 VA
@ 120 VAC, Inductive Externally
DIMENSIONS
(INCHES)
Switched to terminal #2
LIFE EXPECTANCY
Mechanical 10,000,000
Operations (Minimum)
Electrical 100,000
Operations @ Rated Load
INDICATORS
LED’s Show Condition of Outputs
TEMPERATURES
RATING
Operate
Storage
-4° to 131°F (-20° to +ꢁꢁ°C)
-40° to 18ꢁ°F (-40° to +8ꢁ°C)
ENCLOSURE
TERMINATIONS
WEIGHT
Style “E” Lexan® Surface Mounted
(12) #8-32 Screw Terminals
12 to 14 oHꢄ
NOTE: For Analog signal inputs, ATC offers a duplexing pump control
the ATC-Digitec 3800 Panel Mete
r
ꢄ
WIRING
MODEL
M
N
U
O
M
D
B
E
E
R
L NUMBE
R
ARA
A
E
CONTROL VOLTAGE
24 V Triplexor
24
120 V Triplexor
120 V Quadraplexor
120
120
Triplexor
Quadraplexor (120 V only)
F
G
The ARA Series Triplexor and Quadraplexor are UL Listed under
UL File Number Eꢁꢁ82/ꢄ
192
Diversified Electronics
800.727.5646 atcdiversified.com
The
Expandable Alternating Relays
are designed for use in multiple
load installations that are required to alternate in sequence and have the
ability to accept an additional load installation in the futureꢄ
ARA-120-AME
: The ARA-120-AME is a
Duplexor/Triplexor Alternating
Relay
ꢄ With the selector switch in position A, this alternating relay will
duplex the loads on terminals 7 and 9ꢄ With the switch in position B, the
Alternating Relay will triplex the three loads on terminals 7, 9 and 11ꢄ
For automatic alterations, a factory-installed jumper is in place between
terminals 3 and 4ꢄ The alternating action is accomplished when the
control switch between terminals 2 and 4 opensꢄ
For external clocking alterations, remove the factory installed jumper
between terminals 3 and 4 and place an isolated normally open switch
between terminals 2 and 3ꢄ The alternating action will occur each time
this isolated switch is closed and then re-openedꢄ
Expandable Alternating Relays
ARA-120-ANE
: The ARA-120-ANE is a
Triplexor/Quadraplexor
Alternating Relay
ꢄ With the selector switch in position A, the Alternating
Relay will triplex between the loads on terminals 7, 8 and 9ꢄ With the
switch in position B, the Alternating relay will quadraplex the loads on
terminals 7, 8, 9 and 10ꢄ
ORDERING INFORMATION
MODEL NUMBER
DESCRIPTION
For automatic alterations, a factory installed jumper is in place between
terminals 11 and 12ꢄ The alternating action is accomplished when the
control switch between terminals 2 and 3 opensꢄ For external clocking
alterations, remove the factory installed jumper between terminals 11
and 12 and place an isolated normally open switch between terminals 2
and 12ꢄ The alternating action will occur each time this isolated switch is
closed and then re-openedꢄ
ARA-120-AME
ARA-120-ANE
DuplexorꢂTriplexor
TriplexorꢂQuadraplexor
DIMENSIONS
(INCHES)
In the event of a power failure the Alternating Relays will return to their
quiescent state and continue sequencing loads on one-at-a-timeꢄ
SPECIFICATIONS
CONTROL VOLTAGE
120 VAC
10ꢀ, ꢁ0ꢂ/0 ꢃH
CONTROL SWITCH
2 mA
CURRENT
POWER REQUIRED
3 VA (Approximately)
DUTY CYCLE
Continuous
Triplexor
OUTPUT RATING
(3) ꢁ Amp Resistive, 1ꢂ/ hp, 211 VA
@ 120 VAC, Inductive Externally
Switched to terminal #2
WIRING
Quadraplexo
r
(
4) ꢁ Amp Resistive, 1ꢂ/ hp, 211 VA
@ 120 VAC, Inductive Externally
Switched to terminal #2
LIFE EXPECTANCY
Mechanical 10,000,000
Operations (Minimum)
Electrical 100,000
Operations @ Rated Load
INDICATORS
LED’s Show Condition of Outputs
TEMPERATURES
RATING
Operate
Storage
-4° to 131°F (-20° to +ꢁꢁ°C)
-40° to 18ꢁ°F (-40° to +8ꢁ°C)
ENCLOSURE
TERMINATIONS
WEIGHT
Style “E” Lexan® Surface Mounted
(12) #8-32 Screw Terminals
12ꢄꢁ to 14 oHꢄ
193
Diversified Electronics
800.727.5646 atcdiversified.com
OPERATION
The
ARA-120-AHE
is a special function
TRIPLEXOR
designed for three
load installationsꢄ This model has a field selection switch that is used to
omit one of the three loads for general or emergency maintenance while
duplexing the remaining two loadsꢄ The ARA-120-AꢃE has the option of
alternating on each load cycle or by external clockingꢄ This alternating
relay also allows for additional loads to run in the event of excess load
requirementsꢄ
INCLUDES
“LOAD OMIT”
SWITCꢃ
The alternating action is initiated by the control switch between
terminals 2 and 4 when the factory installed jumper is in place between
terminals 3 and 4ꢄ
The alternating action may be initiated externally by removing the
factory installed jumper between terminals 3 and 4 and placing an
isolated normally open switch between terminals 2 and 3ꢄ An alternating
action will occur each time this isolated switch is closed and then re-
openedꢄ
Special Function Alternating Relay
The selection switch has the following positions:
Normal
— Normal operation as Triplexor
ORDERING INFORMATION
MODEL NUMBER
DESCRIPTION
Omit 1
— Omit load #1 Duplex loads 2 and 3
Omit 2
— Omit load #2 Duplex loads 1 and 3
Omit 3
— Omit load #3 Duplex loads 1 and 2
ARA-120-AꢃE
Special Function Alternating Relay
In the event of a power failure, the Alternating Relay will return to its
quiescent state and continue sequencing loads on one-at-a-timeꢄ
NOTE: When the “omit load” option is selected, full potential will appear
on the output terminal of the omitted load when the lag switch between
terminals 2 and ꢁ closesꢄ It is recommended that the ꢃ-O-A switch be
placed in the “off” position for the omitted loadꢄ
DIMENSIONS
(INCHES)
SPECIFICATIONS
CONTROL VOLTAGE
120 VAC
10ꢀ, ꢁ0ꢂ/0 ꢃH
CONTROL SWITCH
2 mA
CURRENT
POWER REQUIRED
3 VA (Approximately)
DUTY CYCLE
Continuous
Triplexor
OUTPUT RATING
(3) ꢁ Amp Resistive, 1ꢂ/ hp, 211 VA
@ 120 VAC, Inductive Externally
Switched to terminal #2
WIRING
LIFE EXPECTANCY
Mechanical 10,000,000
Operations (Minimum)
Electrical 100,000
Operations @ Rated Load
INDICATORS
LED’s Show Condition of Outputs
TEMPERATURES
RATING
Operate
Storage
-4° to 131°F (-20° to +ꢁꢁ°C)
-40° to 18ꢁ°F (-40° to +8ꢁ°C)
ENCLOSURE
TERMINATIONS
WEIGHT
Style “E” Lexan® Surface Mounted
(12) #8-32 Screw Terminals
1/ oHꢄ
194
Diversified Electronics
800.727.5646 atcdiversified.com
OPERATION
The
ARA-120-AJE
is a special function
TRIPLEXOR
designed for three
load installationsꢄ This model has a field selection switch that is used
to lock the Alternating Relay into a desired sequenceꢄ The ARA-120-AJE
has the option of automatically alternating on each load cycle or by
external clockingꢄ This Alternating Relay also allows for additional loads
to run in the event of excess load requirementsꢄ
INCLUDES
SEQUENCE LOCKING
SWITCꢃ
The alternating action is initiated by the control switch between
terminals 2 and 4 when the factory installed jumper is in place between
terminals 3 and 4ꢄ The alternating action may be initiated externally by
removing the factory installed jumper between terminals 3 and 4 and
placing an isolated normally open switch between terminals 2 and 3ꢄ
The alternating action will occur each time this isolated switch is closed
and then re-openedꢄ
A four position
ROTARY SWITCH
has been incorporated to permit field
selection of the sequence that is to be maintainedꢄ The selection switch
has the following positions:
Triplexor Alternating Relay
Normal
— Normal operation as a Triplexor
ORDERING INFORMATION
Lock 1
— Locks in sequence 1-2-3; No alternation will occur
while in this positionꢄ
MODEL NUMBER
DESCRIPTION
Lock 2
— Locks in sequence 2-3-1; No alternation will occur
ARA-120-AJE
Alternating Relay
while in this positionꢄ
Lock 3
— Locks in sequence 3-1-2; No alternation will occur
while in this positionꢄ
In the event of a power failure, the alternating relay will return to its
quiescent state and continue sequencing loads on one-at-a-timeꢄ
DIMENSIONS
(INCHES)
SPECIFICATIONS
CONTROL VOLTAGE
120 VAC
10ꢀ, ꢁ0ꢂ/0 ꢃH
CONTROL SWITCH
2 mA
CURRENT
POWER REQUIRED
3 VA (Approximately)
DUTY CYCLE
Continuous
Triplexor
OUTPUT RATING
(3) ꢁ Amp Resistive, 1ꢂ/ hp, 211 VA
@ 120 VAC, Inductive Externally
Switched to terminal #2
LIFE EXPECTANCY
Mechanical 10,000,000
Operations (Minimum)
Electrical 100,000
Operations @ Rated Load
INDICATORS
LED’s Show Condition of Outputs
TEMPERATURES
RATING
Operate
Storage
-4° to 131°F (-20° to +ꢁꢁ°C)
-40° to 18ꢁ°F (-40° to +8ꢁ°C)
WIRING
ENCLOSURE
TERMINATIONS
WEIGHT
Style “E” Lexan
®
Surface Mounted
(12) #8-32 Screw Terminals
17 oHꢄ
195
Diversified Electronics
800.727.5646 atcdiversified.com