Mueller-Electric-ARM-120-AFEP
| Part # | Mueller-Electric-ARM-120-AFEP |
| Download | Mueller-Electric-ARM-120-AFEP |
The
ARM Series
Alternating Relay is a
microprocessor-based
controller
designed for use in dual load installations to assure
equal run time on each loadꢃ LED indicators show the status of
the unit’s five intrinsically safe control switch inputs% one alarm%
and two load outputsꢃ H-O-A switches% a lead select switch% and a
testꢂclear button are provided for manual controlꢃ The ARM Series
reduces the number of components required for this application
by combining many functions into one unitꢃ
Process
Control
Equipment for
Hazardous
Locations
7M26
UL913
INCLUDES
INTRINSICALLY
SAFE INPUTS
TWO PUMP SEQUENCING:
Evenly distributes run time by
automatically alternating lead and lag load designations when the off
control switch input opensꢃ
UL913 INTRINSICALLY SAFE:
Control switch inputs are low voltageꢂ
low current and are electronically isolated from the control voltage
and load alarm contactsꢃ
Integrated Duplex Controller
SOSO Operation
(Sequence-on, Simultaneous-off)
H-O-A Switches: Hand-Off-Automatic switches allow for manual
operationꢃ
LEAD SELECT SWITCH:
Disables the automatic sequencing function
and allows loads to be locked into the 2-1 or 1-2 sequenceꢃ
CONTROL SWITCH FAULT DETECTION:
Unit detects open and
shorted control switch failuresꢃ
SPECIFICATIONS
CONTROL VOLTAGE
24 or 120 VAC
10ꢀ% ꢁ0ꢂ60 Hz
TEST/CLEAR SWITCH:
Verifies function and resets the control
CONTROL SWITCH
Open Circuit
ꢁ VDC
switch fault detection algorithmꢃ
Voltage
Short Circuit
0ꢃ1mA
Voltage
ALARM OUTPUT:
Alarm contacts close when a control switch
fails or the system’s capacity is exceededꢃ
INRUSH CURRENT DELAY:
Reduces line sags by preventing
both loads from energizing simultaneousl
y
ꢃ
POWER REQUIRED
4 VA Maximum
DUTY CYCLE
RESPONSE
Continuous
VERSATILE MOUNTING:
Two (2) mounting configurations are
availableꢃ The standard surface mount has top access to controls
and indicators and is intended for back panel mountingꢃ The panel
mount option is intended for front panel or door cutout access to
controls and indicatorsꢃ
Power Up
Inrush Current
ꢁ SECꢃ
ꢁꢀ
3 SECꢃ
ꢁꢀ
CONTACT
RATING
(3) SPST-NꢃOꢃ 10 Amp Resistive% 1ꢂ4 hp% 278 VA
Inductive @ 120 VAC
SPECIAL CONTROLS: ARM-2003
and
ARM-2010
–Standard
operation without the H-O-A switches
ARM-2011
–Standard
operation without the Control Switch Failure featureꢃ
LED INDICATORS
Designation
LevelꢂAlarm
Lag
Lead
Off
Color
Red
Green
Green
Green
Green
State
ON
ON
ON
ON
Condition
csꢁ Closed
cs4 Closed
cs3 Closed
cs2 Closed
cs1 Auxꢃꢂcs2
Closed
Load ON
Load ON
Failure
OpenꢂClosed
ORDERING INFORMATION
Auxꢃ Off
ON
MODEL
NUMBER
CONTROL
VOLTAGE
Load 1
Load 2
Ctrlꢃ Switch
Green
Green
Red
ON
ON
ON
MOUNTING
COMMENTS
ARM-XXX-AFE*
ARM-XXX-AFEP* 24
or 120 VAC
24 or 120 VAC
Surface
Panel
Standard
Standard
ARM-2003
ARM-2010
ARM-2011
120 VAC
120 VAC
120 VAC
Surface
Special: wꢂo
H-O-A switches
Special: wꢂo
H-O-A switches
Special: wꢂo
Control switch
failure feature
LIFE EXPECTANCY
Mechanical
20 Million Operations
7ꢁ%000 @ Rated Load
Electrical
Panel
TEMPERATURE
RATING
Operate
Storage
-4° to 131°F (-20° to +ꢁꢁ°C)
-40° to 18ꢁ°F (-40° to +8ꢁ°C)
Surface
TERMINATIONS
(12) #8-32 Screw Terminals
WEIGHT
16 ozꢃ
*Replace XXX with desire control voltage (24% 120)
The ARM Series is UL Listed under UL File Number E1ꢁ1ꢁ78ꢃ
196
Diversified Electronics
800.727.5646 atcdiversified.com
DIMENSIONS
(INCHES)
OPERATION
FOUR CONTROL SWITCHING:
Do not remove factory-installed
jumper between terminals 2 and 3ꢃ The control switches connected
to terminals 3 through 6 are labeled OFF (CS2)% LEAD (CS3)% LAG
(CS4) and ALARM (CSꢁ)ꢃ Under normal operation the lead load
energizes when the off and lead control switches close in orde
r
ꢃ
T
he
lag load energizes when the lag closes and the alarm load energizes
when the alarm switch closesꢃ When all four switches reopen in the
proper order all outputs are de-energized and the leadꢂlag output
designations reverseꢃ
FIVE CONTROL SWITCHING:
Remove factory installed jumper
between terminals 2 and 3ꢃ After the jumper has been removed% the
additional control switch is connected to terminal 2ꢃ The extra switch
functions as an AUXILIARY OFF (CS1) switchꢃ It is used to prevent
loads from running continuously if the primary OFF (CS2) switch
fails to open properl
y
ꢃ
*Panel Mount Cutout
FAULT DETECTION ALGORITHM:
If any of the control switches
open or close out of order% the alarm output energizes and a fault
detection algorithm is used to identify the faulty switchꢃ The faulty
switch is then ignored and the OF
F
%
L
EAD% and LAG control switch
designations are altered to maintain safe operationꢃ
*Greenlee punch #60071 or equivalent
WIRING
CONTROL DRAWING 190
1ꢃ To
maintain intrinsic safet
y
%
c
onnect the Controller’s Earth Ground Terminal 8 to the earth ground of the AC Power Supply feede
r
ꢃ
The resistance between the Controller’s Earth Ground Terminal and Earth Ground shall be less than 1 ohmꢃ
2ꢃ Maximum
distance between Controller and switch contact is 1000 feetꢃ
3ꢃ All
intrinsically safe wiring shall be separated from non-intrinsically safe wiringꢃ Refer to article ꢁ04 of the National Electrical Code
ANSIꢂNFPA 70 on procedures for intrinsically safe wiringꢃ
4ꢃ Switch
contact shall be any non-energy storing or generating mechanical switch type device containing no capacitance or inductanceꢃ
ꢁꢃ Connections
to terminals ꢁ% 6% 9% 10% 11% and 12 are optionalꢃ If the Auxꢃ Off switch is omitted% terminals 2 & 3 must be jumperedꢃ