Mueller-Electric-ARM-120-AFEP

Part #Mueller-Electric-ARM-120-AFEP
Download 
Mueller-Electric-ARM-120-AFEP
The
ARM Series
Alternating Relay is a
microprocessor-based  
controller
designed for use in dual load installations to assure  
equal run time on each loadꢃ LED indicators show the status of  
the unit’s five intrinsically safe control switch inputs% one alarm%  
and two load outputsꢃ H-O-A switches% a lead select switch% and a  
testꢂclear button are provided for manual controlꢃ The ARM Series  
reduces the number of components required for this application  
by combining many functions into one unitꢃ  
Process  
Control  
Equipment for  
Hazardous  
Locations  
7M26  
UL913  
INCLUDES  
INTRINSICALLY  
SAFE INPUTS  
TWO PUMP SEQUENCING:
Evenly distributes run time by  
automatically alternating lead and lag load designations when the off  
control switch input opensꢃ  
UL913 INTRINSICALLY SAFE:
Control switch inputs are low voltageꢂ  
low current and are electronically isolated from the control voltage  
and load alarm contactsꢃ  
Integrated Duplex Controller  
SOSO Operation  
(Sequence-on, Simultaneous-off)  
H-O-A Switches: Hand-Off-Automatic switches allow for manual  
operationꢃ  
LEAD SELECT SWITCH:
Disables the automatic sequencing function  
and allows loads to be locked into the 2-1 or 1-2 sequenceꢃ  
CONTROL SWITCH FAULT DETECTION:
Unit detects open and  
shorted control switch failuresꢃ  
SPECIFICATIONS  
CONTROL VOLTAGE
 
24 or 120 VAC
 
10ꢀ% ꢁ0ꢂ60 Hz  
TEST/CLEAR SWITCH:
Verifies function and resets the control  
CONTROL SWITCH
 
Open Circuit
 
ꢁ VDC  
switch fault detection algorithmꢃ  
Voltage  
Short Circuit
 
0ꢃ1mA  
Voltage  
ALARM OUTPUT:
Alarm contacts close when a control switch  
fails or the system’s capacity is exceededꢃ  
INRUSH CURRENT DELAY:
Reduces line sags by preventing  
both loads from energizing simultaneousl
y
ꢃ  
POWER REQUIRED
 
4 VA Maximum  
DUTY CYCLE  
RESPONSE  
Continuous  
VERSATILE MOUNTING:
Two (2) mounting configurations are  
availableꢃ The standard surface mount has top access to controls  
and indicators and is intended for back panel mountingꢃ The panel  
mount option is intended for front panel or door cutout access to  
controls and indicatorsꢃ  
Power Up  
Inrush Current
 
ꢁ SECꢃ
 
ꢁꢀ  
3 SECꢃ
 
ꢁꢀ  
CONTACT  
RATING  
(3) SPST-NꢃOꢃ 10 Amp Resistive% 1ꢂ4 hp% 278 VA  
Inductive @ 120 VAC  
SPECIAL CONTROLS: ARM-2003
and
ARM-2010
–Standard  
operation without the H-O-A switches
ARM-2011
–Standard  
operation without the Control Switch Failure featureꢃ  
LED INDICATORS  
Designation  
LevelꢂAlarm  
Lag  
Lead  
Off  
Color  
Red  
Green  
Green  
Green  
Green  
State  
ON  
ON  
ON  
ON  
Condition  
csꢁ Closed  
cs4 Closed  
cs3 Closed  
cs2 Closed  
cs1 Auxꢃꢂcs2  
Closed  
Load ON  
Load ON  
Failure  
OpenꢂClosed  
ORDERING INFORMATION  
Auxꢃ Off  
ON  
MODEL  
NUMBER  
CONTROL  
VOLTAGE  
Load 1  
Load 2  
Ctrlꢃ Switch  
Green  
Green  
Red  
ON  
ON  
ON  
MOUNTING  
COMMENTS  
ARM-XXX-AFE*  
ARM-XXX-AFEP* 24
 
or 120 VAC  
24 or 120 VAC  
Surface  
Panel  
Standard  
Standard  
ARM-2003  
ARM-2010  
ARM-2011  
120 VAC  
120 VAC  
120 VAC  
Surface  
Special: wꢂo  
H-O-A switches  
Special: wꢂo  
H-O-A switches  
Special: wꢂo  
Control switch  
failure feature  
LIFE EXPECTANCY
 
Mechanical  
20 Million Operations  
7ꢁ%000 @ Rated Load  
Electrical  
Panel  
TEMPERATURE  
RATING  
Operate  
Storage  
-4° to 131°F (-20° to +ꢁꢁ°C)  
-40° to 18ꢁ°F (-40° to +8ꢁ°C)  
Surface  
TERMINATIONS  
(12) #8-32 Screw Terminals  
WEIGHT
16 ozꢃ  
*Replace XXX with desire control voltage (24% 120)  
The ARM Series is UL Listed under UL File Number E1ꢁ1ꢁ78ꢃ  
196  
Diversified Electronics  
800.727.5646 atcdiversified.com  

DIMENSIONS
(INCHES)  
OPERATION  
FOUR CONTROL SWITCHING:
Do not remove factory-installed  
jumper between terminals 2 and 3ꢃ The control switches connected  
to terminals 3 through 6 are labeled OFF (CS2)% LEAD (CS3)% LAG  
(CS4) and ALARM (CSꢁ)ꢃ Under normal operation the lead load  
energizes when the off and lead control switches close in orde
r
ꢃ
T
he  
lag load energizes when the lag closes and the alarm load energizes  
when the alarm switch closesꢃ When all four switches reopen in the  
proper order all outputs are de-energized and the leadꢂlag output  
designations reverseꢃ  
FIVE CONTROL SWITCHING:
Remove factory installed jumper  
between terminals 2 and 3ꢃ After the jumper has been removed% the  
additional control switch is connected to terminal 2ꢃ The extra switch  
functions as an AUXILIARY OFF (CS1) switchꢃ It is used to prevent  
loads from running continuously if the primary OFF (CS2) switch  
fails to open properl
y
ꢃ  
*Panel Mount Cutout  
FAULT DETECTION ALGORITHM:
If any of the control switches  
open or close out of order% the alarm output energizes and a fault  
detection algorithm is used to identify the faulty switchꢃ The faulty  
switch is then ignored and the OF
F
%
L
EAD% and LAG control switch  
designations are altered to maintain safe operationꢃ  
*Greenlee punch #60071 or equivalent  
WIRING  
CONTROL DRAWING 190  
1ꢃ To
 
maintain intrinsic safet
y
%
c
onnect the Controller’s Earth Ground Terminal 8 to the earth ground of the AC Power Supply feede
r
ꢃ  
The resistance between the Controller’s Earth Ground Terminal and Earth Ground shall be less than 1 ohmꢃ  
2ꢃ Maximum
 
distance between Controller and switch contact is 1000 feetꢃ  
3ꢃ All
 
intrinsically safe wiring shall be separated from non-intrinsically safe wiringꢃ Refer to article ꢁ04 of the National Electrical Code  
ANSIꢂNFPA 70 on procedures for intrinsically safe wiringꢃ  
4ꢃ Switch
 
contact shall be any non-energy storing or generating mechanical switch type device containing no capacitance or inductanceꢃ  
ꢁꢃ Connections
 
to terminals ꢁ% 6% 9% 10% 11% and 12 are optionalꢃ If the Auxꢃ Off switch is omitted% terminals 2 & 3 must be jumperedꢃ  
197  