Omron-Electronics-G9EJ-1-E-UVDDC12
| Part # | Omron-Electronics-G9EJ-1-E-UVDDC12 |
| Download | Omron-Electronics-G9EJ-1-E-UVDDC12 |
New Product News
DC Power Relays
G9EJ-1-E
Compact DC Power Relays Capable of
Switching 400 V 15 A DC loads
• Actualize a high capacity interruption through the function of
extinction of magnetic arc by adopting high-efficiency magnetic circuit.
• Actualize improvement of inrush-withstand performance and a
long-life by adopting Omron’s own contact driving system.
• Actualize the power saving.
• Small and lightweight type.
Size: H31 mm × W27 mm × L44 mm, Weight: approx. 45 g
RoHS Compliant
Refer to the
Precautions
on page 5.
Model Number Structure
1. Number of Poles
4. Classification
G9EJ-@-@-@
–
@
–
@
— — — — —
1: 1 pole
E: High capacity
1
2 3 4 5
2. Contact Form
5. Approved standards
Blank: SPST-NO
UVD: UL, CSA, VDE approved standard type
3. Terminal Form
Blank: Tab terminals (#25ꢀ terminals)
P: PCB terminals
Ordering Information
T
e
rminals
Minimum packing unit
(quantity)
Models
Contact form
Contact terminals
Rated coil voltage
Model
Coil terminals
12 VDC
24 VDC
12 VDC
24 VDC
T
a
b terminals
#25ꢀ
T
a
b terminals
#25ꢀ
G9EJ-1-E-UVD
G9EJ-1-P-E-UVD
Switching/current
conduction models
SPS
T
–
NO
1ꢀ
PCB terminals
PCB terminals
Ratings
●
Coil
Rated voltage
Rated current
Coil resistance
Must-operate voltage
Must-release voltage
50 min. of rated voltage
Maximum voltage (See note 3)
Power consumption
12 VDC
24 VDC
1ꢀꢀ mA
5ꢀ mA
12ꢀ
Ω
48ꢀ
Ω
6ꢀ0 max. of rated
voltage
13ꢀ0 of rated voltage
Approx. 1.2 W
(at 23°C within 1ꢀ minutes)
Note: 1.
The figures for the rated current and coil resistance are for a coil temperature of 23°C and have a tolerance of
1ꢀ0.
Note: 2.
The figures for the operating characteristics are for a coil temperature of 23°C .
Note: 3.
The figure for the maximum voltage is the maximum voltage that can be applied to the relay coil.
●
Contacts
Item
Resistive load
15 A at 4ꢀꢀ VDC
15 A
Rated load
Rated carry current
Maximum switching voltage
Maximum switching current
4ꢀꢀ V
15 A
1
G9EJ-1-E
DC Power Relays
Characteristics
Item
G9EJ-1(-P)-E-UVD
Contact resistance *1
Contact voltage drop
Operate time *2
1ꢀꢀ m
Ω
max.
ꢀ.2 V max. (for a carry current of 15 A)
5ꢀ ms max.
Release time *2
3ꢀ ms max.
Between coil and contacts
1,ꢀꢀꢀ M
Ω
min.
Insulation resistance *3
Dielectric strength
Between contacts of the same polarity
1,ꢀꢀꢀ M
Ω
min.
Between coil and contacts
2,5ꢀꢀ VAC 1 min
Between contacts of the same polarity
2,5ꢀꢀ VAC 1 min
Impulse withstand voltage *4
4,5ꢀꢀ V
1ꢀ to 55 to 1ꢀHz, ꢀ.75 mm single amplitude
(Acceleration: 2.94 to 88.9 m/s
2
)
Destruction
Vibration resistance
Shock resistance
1ꢀ to 55 to 1ꢀHz, ꢀ.75 mm single amplitude
Malfunction
Destruction
Malfunction
(Acceleration: 2.94 to 88.9 m/s
2
)
49ꢀ m/s
2
49ꢀ m/s
2
98 m/s
2
Energized
Deenergized
Mechanical endurance *5
Electrical endurance *6
Electrical endurance (condenser load) *6
Short-time carry current
Overload switching
Maximum interruption current
Reverse polarity interruption
Ambient operating temperature
Ambient operating humidity
Weight
2ꢀꢀ,ꢀꢀꢀ ops. min.
4ꢀꢀ VDC, 15 A, 1ꢀ,ꢀꢀꢀ ops. min.
4ꢀꢀ VDC, 25 A, 1ꢀꢀ,ꢀꢀꢀ ops. min.
3ꢀ A (2ꢀ sec.)
4ꢀꢀ VDC, 3ꢀA, 1ꢀꢀ ops. min.
5ꢀ A at 4ꢀꢀ VDC (5 times)
–15 A at 4ꢀꢀ VDC (1,ꢀꢀꢀ times min.)
–4ꢀ to 7ꢀ°C (with no icing or condensation)
50 to 850
Approx. 45 g
Note: The above values are initial values at an ambient temperature of 23°C unless otherwise specified.
*1. The
contact resistance was measured with 1 A at 5 VDC using the voltage drop method.
*2. Measurement
conditions: With rated operating voltage applied (without diode), not including contact bounce.
*3. The
insulation resistance was measured with a 5ꢀꢀ VDC megohmmeter.
*4. The
impulse withstand voltage was measured with a JEC-212 (1981) standard impulse voltage waveform (1.2 × 5ꢀ µs).
*5. The
mechanical endurance was measured at a switching frequency of 3,6ꢀꢀ operations/hr.
*6. The
electrical endurance was measured at a switching frequency of 6ꢀ operations/hr.
Engineering Data
●
Maximum Switching Capacity
●
Electrical Endurance
(Switching Performance)
●
Electrical Endurance
(Interruption Performance)
1ꢀ,ꢀꢀꢀ
5,ꢀꢀꢀ
3,ꢀꢀꢀ
1ꢀ,ꢀꢀꢀ
5,ꢀꢀꢀ
3,ꢀꢀꢀ
1,ꢀꢀꢀ
5ꢀꢀ
3ꢀꢀ
1,ꢀꢀꢀ
1,ꢀꢀꢀ
5ꢀꢀ
3ꢀꢀ
5ꢀꢀ
3ꢀꢀ
1ꢀꢀ
DC resistive load
5ꢀ
3ꢀ
Switching 4ꢀꢀ-VDC resistive
1ꢀꢀ
1ꢀꢀ
load (positive direction)
5ꢀ
5ꢀ
3ꢀ
3ꢀ
1ꢀ
Interrupting 4ꢀꢀ-VDC resistive
1ꢀ
1ꢀ
5
3
load (positive direction)
5
5
3
3
1
1
1
1ꢀ
3ꢀ
5ꢀ
1ꢀꢀ
3ꢀꢀ 5ꢀꢀ
1,ꢀꢀꢀ
Switching voltage (V)
1
3
5
1ꢀ
3ꢀ
5ꢀ
1ꢀꢀ
1ꢀ
3ꢀ
5ꢀ
1ꢀꢀ
Switching current (A)
Switching current (A)
●
Carry Current vs. Energizing Time
●
Must-operate
V
o
ltage and Must-
release
V
o
ltage Distributions
(Number of Relays × Percentage of
Rated Voltage)
●
Time Characteristic Distributions
(Number of Contacts × Time (ms))
35
35
1ꢀꢀ,ꢀꢀꢀ
Must-operate voltage
Operate time
Must-release voltage
3ꢀ
Release time
3ꢀ
1ꢀ,ꢀꢀꢀ
1,ꢀꢀꢀ
1ꢀꢀ
Number: 64
25
25
Number: 64
2ꢀ
15
1ꢀ
5
2ꢀ
15
1ꢀ
5
1ꢀ
1
ꢀ
ꢀ
2ꢀ
4ꢀ
6ꢀ
8ꢀ
1ꢀꢀ
5
1ꢀ
15
2ꢀ
25
15
1
3
5
1ꢀ
3ꢀ
5ꢀ
1ꢀꢀ
Percentage of rated voltage (0)
Time (ms)
Switching current (A)
2
G9EJ-1-E
DC Power Relays
●
Vibration Malfunction
●
Vibration Resistance
●
Shock Resistance
1
1ꢀ.ꢀ
1ꢀ.ꢀ
Must-operate voltage
Must-release voltage
Must-operate voltage
Must-release voltage
Number: 5
ꢀ.9
8.ꢀ
6.ꢀ
8.ꢀ
Unconfirmed area
ꢀ.8
ꢀ.7
ꢀ.6
ꢀ.5
ꢀ.4
ꢀ.3
ꢀ.2
6.ꢀ
4.ꢀ
4.ꢀ
2.ꢀ
2.ꢀ
ꢀ.ꢀ
ꢀ.ꢀ
−2.ꢀ
−4.ꢀ
−6.ꢀ
−2.ꢀ
−4.ꢀ
−6.ꢀ
Confirmed area
Number: 5
Number: 5
ꢀ.1
ꢀ
−8.ꢀ
−8.ꢀ
−1ꢀ.ꢀ
−1ꢀ.ꢀ
1
3
5
1ꢀ
3ꢀ
5ꢀ 1ꢀꢀ
Start
After test
Start
After test
Frequency (Hz)
Characteristics were measured after applying vibration
at a frequency of 1ꢀ to 55 Hz (single amplitude of ꢀ.75
mm) to the test piece (not energized)
for 2 hours each
in 3 directions. The percentage rate of change is the
average value for all of the samples
Characteristics were measured after applying a shock
of 49ꢀ m/s
2
to the test piece 3 times each in 6 directions
along 3 axes.
The percentage rate of change is the average value for
all of the samples.
●
Shock Malfunction
Z
Z
Z
´
Y
Y
5ꢀꢀ
5ꢀꢀ
Z
´
X´
X
´
Y
´
4ꢀꢀ
Y
´
4ꢀꢀ
X
Y
X
Y
3ꢀꢀ
3ꢀꢀ
X
Z
X
Z
2ꢀꢀ
2ꢀꢀ
1ꢀꢀ
ꢀ
1ꢀꢀ
Deenergized
Deenergized
ꢀ
Z
´
X
´
Z
´
X
´
Unit: m/s
2
Sample: G9EJ-1-E-UVD
Number: 5
Unit: m/s
2
Sample: G9EJ-1-P-E-UVD
Number: 5
Energized
Energized
Y
´
Y
´
The value at which malfunction occurred was
measured after applying shock to the test piece
3 times each in 6 directions along 3 axes.
The value at which malfunction occurred was
measured after applying shock to the test piece
3 times each in 6 directions along 3 axes.
3
G9EJ-1-E
DC Power Relays
Dimensions
(Unit: mm)
Mounting Hole Dimensions
(TOP VIEW)
G9EJ-1-E-UVD
4
3
44
38
31
2ꢀ.9
8.5
ꢀ.8
15.5
ꢀ.8
2 (−)
(+)1
27 15.4
8 3.5
Note: Be
sure to connect terminals
with the correct polarity.
Coils do not have polarity.
Mounting Hole Dimensions
6.3
ꢀ.8
6.3
Connecting terminals
(#25ꢀ tab)
Two, M3 or 3.5-dia. holes
11
Dimension (mm)
T
o
lerance (mm)
1ꢀ or lower
1ꢀ to 5ꢀ
ꢀ.3
ꢀ.5
3ꢀ
1
ꢀ.1
4ꢀ
2
Mounting Hole Dimensions
(TOP VIEW)
G9EJ-1-P-E-UVD
27
31
4
3
3ꢀ
32.2
2 (−)
(+)1
Note: Be
sure to connect terminals
with the correct polarity.
1.2
4
ꢀ.8
1.2
Coils do not have polarity.
1.2
6.3
Mounting Hole Dimensions
Relay Mounted on PCB (Reference Information)
Six,
1.7
+ꢀ.1
dia.
ꢀ
(3.25)
5.1
ꢀ.1
ꢀ.8
15.5
ꢀ.8
Dimension (mm)
T
o
lerance (mm)
1ꢀ or lower
1ꢀ to 5ꢀ
ꢀ.3
ꢀ.5
15.4
15.4
ꢀ.1
16.3
ꢀ.1
(32.5)
(5.35)
8.5
(3.1)
2ꢀ.9
ꢀ.1
(7)
2ꢀ.9
Approved standards
UL Recognized:
File No.E41515
CSA Certified:
File No.LR31928
VDE Certified:
File No.40037110
Model
Coil ratings
Contact ratings
Pollution level
2
Model
Coil ratings
Contact ratings
Pollution level
2
G9EJ-1(-P)-E-UVD
12 V, 24 V
15 A, 5ꢀꢀ VDC (Resistive)
G9EJ-1(-P)-E-UVD
12 V, 24 V
15 A, 5ꢀꢀ VDC (Resistive)
4
G9EJ-1-E
DC Power Relays
Precautions
WARNING
T
a
ke measures to prevent contact with charged parts
when using the Relay for high voltages.
Precautions for Correct Use
Refer to the relevant catalog for common precautions.
1. The
G9EJ Relays’ contacts have polarit
y
.
11
.
D
o not use the Relay in locations where water, solvents,
chemicals, or oil may come in contact with the case or termi-
nals. Doing so may result in deterioration of the case resin or
abnormal heating due to corrosion or contamination of the
terminals. Also, if electrolyte adheres to the output terminals,
electrolysis may occur between the output terminals, result-
ing in corrosion of the terminals or wiring disconnections.
12
.
B
e sure to turn OFF the power and confirm that there is no
residual voltage before replacing the Relay or performing wir-
ing.
13
.
T
he distance between crimp terminals or other conductive
parts will be reduced and insulation properties will be lowered
if wires are laid in the same direction from the contact termi-
nals. Use insulating coverings, do not wire in the same direc-
tion, and take other measures as required to maintain
insulation properties.
Be sure to perform connections with the correct polarit
y
.
If the contacts are connected with the reverse polarit
y
,
t
he
switching characteristics specified in this document cannot be
assured.
2. Do not drop or disassemble this Rela
y
.
N
ot only may the
Relay fail to meet the performance specifications, it may also
result in damage, electric shock, or burning.
3. Do
not use these Relays in strong magnetic fields of 8ꢀꢀ A/m
or higher (e.g., near transformers or magnets). The arc dis-
charge that occurs during switching may be bent by the mag-
netic field, resulting in flashover or insulation faults.
4. This
Relay is a device for switching high DC voltages. If it is
used for voltages exceeding the specified range, it may not
be possible to interrupt the load and burning may result. In
order to prevent fire spreading, use a configuration in which
the current load can be interrupted in the event of emergen-
cies.
14
.
U
se either a varistor, or a diode plus Zener diode as a protec-
tive circuit against reverse surge in the relay coil. Using a
diode alone will reduce the switching characteristics.
15
.
U
se two M3 screws to mount a Relay with tab terminals. (The
tightening torque is ꢀ.98 N·m.)
In order to ensure safety of the system, replace the Relay on
a regular basis.
5. If
the Relay is used for no-load and/or minute load switching,
the contact resistance may increase and so confirm correct
operation under the actual operating conditions.
16
.
M
anually mount Relays with PCB
T
e
rminals. Do not use auto-
matic soldering for them.
Do not bend the terminals to secure the Relay to the PCB.
17
.
A
R
elay with PCB
T
e
rminals weighs approximately 45 g.
Be sure that the PCB is strong enough to support it.
18
.
F
or the PCBs, we recommend dual-side through-hole PCBs
to reduce solder cracking from heat stress.
19
.
T
he coil terminals (A in the figure) and contact terminals (B in
the figure) on Relays with PCB terminals have charged metal
parts. Also, the shaded part in the following diagram may also
be charged. When you use the Rela
y
,
m
ake sure that there is
no metal pattern on the corresponding part of the PCB.
6. With
this Rela
y
,
i
f the rated voltage (or current) is continu-
ously applied to the coil and contacts, and then turned OFF
and immediately ON again, the coil temperature, and conse-
quently the coil resistance, will be higher than usual. This
means that the must operate voltage will also be higher than
usual, exceeding the rated value (“hot start”). In this case,
take the appropriate countermeasures, such as reducing the
load current or restricting the energizing time or ambient
operating temperature.
7. The
ripple percentage for DC relays can cause fluctuations in
the must-operate voltage or humming. For this reason,
reduce the ripple percentage in full-wave rectified power sup-
ply circuits by adding a smoothing capacitor. Ensure that the
ripple percentage is less than 50.
8. Ensure
that a voltage exceeding the specified maximum volt-
age is not continuously applied to the coil. Abnormal heating
in the coil may shorten the lifetime of the insulation coating.
9. Do
not use the Relay at a switching voltage or current greater
than the specified maximum values. Doing so may result in
arc discharge interruption failure or burning due to abnormal
heating in the contacts.
Detail of Area A
Detail of Area B
(1)
(1)
1.2
6.3
6.3
A
B
6
1ꢀ
.
T
he contact ratings are for resistive loads. The electrical
endurance with inductive loads is inferior to that of resistive
loads. Confirm correct operation under the actual operating
conditions.
3
Charged metal part
9
5
•
Application examples provided in this document are for reference only. In actual applications, confirm equipment functions and safety before using the product.
•
Consult your OMRON representative before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad
systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems or equipment that may have a serious
influence on lives and property if used improperly. Make sure that the ratings and performance characteristics of the product provide a margin of safety for the system or
equipment, and be sure to provide the system or equipment with double safety mechanisms.
Note: Do not use this document to operate the Unit.
OMRON Corporation
Electronic and Mechanical Components Company
Cat. No. J195-E1-05
1215 (ꢀ114) (O)