New Product News  
DC Power Relays  
G9EJ-1-E  
Compact DC Power Relays Capable of  
Switching 400 V 15 A DC loads  
• Actualize a high capacity interruption through the function of  
extinction of magnetic arc by adopting high-efficiency magnetic circuit.  
• Actualize improvement of inrush-withstand performance and a  
long-life by adopting Omron’s own contact driving system.  
• Actualize the power saving.  
• Small and lightweight type.  
Size: H31 mm × W27 mm × L44 mm, Weight: approx. 45 g  
RoHS Compliant  
Refer to the
Precautions
on page 5.  
Model Number Structure  
1. Number of Poles  
4. Classification  
G9EJ-@-@-@
–
@
–
@  
— — — — —  
1: 1 pole  
E: High capacity  
1
2 3 4 5  
2. Contact Form  
5. Approved standards  
Blank: SPST-NO  
UVD: UL, CSA, VDE approved standard type  
3. Terminal Form  
Blank: Tab terminals (#25ꢀ terminals)  
P: PCB terminals  
Ordering Information  
T
e
rminals  
Minimum packing unit  
(quantity)  
Models  
Contact form  
Contact terminals  
Rated coil voltage  
Model  
Coil terminals  
12 VDC  
24 VDC  
12 VDC  
24 VDC  
T
a
b terminals  
#25ꢀ  
T
a
b terminals  
#25ꢀ  
G9EJ-1-E-UVD  
G9EJ-1-P-E-UVD  
Switching/current  
conduction models  
SPS
T
–
NO  
1ꢀ  
PCB terminals  
PCB terminals  
Ratings  
●
Coil  
Rated voltage  
Rated current  
Coil resistance  
Must-operate voltage  
Must-release voltage  
50 min. of rated voltage  
Maximum voltage (See note 3)
 
Power consumption  
12 VDC  
24 VDC  
1ꢀꢀ mA  
5ꢀ mA  
12ꢀ
Ω
 
48ꢀ
Ω  
6ꢀ0 max. of rated  
voltage  
13ꢀ0 of rated voltage  
Approx. 1.2 W  
(at 23°C within 1ꢀ minutes)  
Note: 1.
 
The figures for the rated current and coil resistance are for a coil temperature of 23°C and have a tolerance of
 
1ꢀ0.  
Note: 2.
 
The figures for the operating characteristics are for a coil temperature of 23°C .  
Note: 3.
 
The figure for the maximum voltage is the maximum voltage that can be applied to the relay coil.  
●
Contacts  
Item  
Resistive load  
15 A at 4ꢀꢀ VDC  
15 A  
Rated load  
Rated carry current  
Maximum switching voltage  
Maximum switching current  
4ꢀꢀ V  
15 A  
1

G9EJ-1-E  
DC Power Relays  
Characteristics  
Item  
G9EJ-1(-P)-E-UVD  
Contact resistance *1  
Contact voltage drop  
Operate time *2  
1ꢀꢀ m
Ω
max.  
ꢀ.2 V max. (for a carry current of 15 A)  
5ꢀ ms max.  
Release time *2  
3ꢀ ms max.  
Between coil and contacts  
1,ꢀꢀꢀ M
Ω
min.  
Insulation resistance *3  
Dielectric strength  
Between contacts of the same polarity
 
1,ꢀꢀꢀ M
Ω
min.  
Between coil and contacts
 
2,5ꢀꢀ VAC 1 min  
Between contacts of the same polarity
 
2,5ꢀꢀ VAC 1 min  
Impulse withstand voltage *4  
4,5ꢀꢀ V  
1ꢀ to 55 to 1ꢀHz, ꢀ.75 mm single amplitude  
(Acceleration: 2.94 to 88.9 m/s

2

)  
Destruction  
Vibration resistance  
Shock resistance  
1ꢀ to 55 to 1ꢀHz, ꢀ.75 mm single amplitude  
Malfunction  
Destruction  
Malfunction  
(Acceleration: 2.94 to 88.9 m/s

2

)  
49ꢀ m/s

2  

49ꢀ m/s

2  

98 m/s

2  

Energized  
Deenergized  
Mechanical endurance *5  
Electrical endurance *6  
Electrical endurance (condenser load) *6  
Short-time carry current  
Overload switching  
Maximum interruption current  
Reverse polarity interruption  
Ambient operating temperature  
Ambient operating humidity  
Weight  
2ꢀꢀ,ꢀꢀꢀ ops. min.  
4ꢀꢀ VDC, 15 A, 1ꢀ,ꢀꢀꢀ ops. min.  
4ꢀꢀ VDC, 25 A, 1ꢀꢀ,ꢀꢀꢀ ops. min.  
3ꢀ A (2ꢀ sec.)  
4ꢀꢀ VDC, 3ꢀA, 1ꢀꢀ ops. min.  
5ꢀ A at 4ꢀꢀ VDC (5 times)  
–15 A at 4ꢀꢀ VDC (1,ꢀꢀꢀ times min.)  
–4ꢀ to 7ꢀ°C (with no icing or condensation)  
50 to 850  
Approx. 45 g  
Note: The above values are initial values at an ambient temperature of 23°C unless otherwise specified.  
*1. The
 
contact resistance was measured with 1 A at 5 VDC using the voltage drop method.  
*2. Measurement
 
conditions: With rated operating voltage applied (without diode), not including contact bounce.  
*3. The
 
insulation resistance was measured with a 5ꢀꢀ VDC megohmmeter.  
*4. The
 
impulse withstand voltage was measured with a JEC-212 (1981) standard impulse voltage waveform (1.2 × 5ꢀ µs).  
*5. The
 
mechanical endurance was measured at a switching frequency of 3,6ꢀꢀ operations/hr.  
*6. The
 
electrical endurance was measured at a switching frequency of 6ꢀ operations/hr.  
Engineering Data  
●
Maximum Switching Capacity  
●
Electrical Endurance  
(Switching Performance)  
●
Electrical Endurance  
(Interruption Performance)  
1ꢀ,ꢀꢀꢀ  
5,ꢀꢀꢀ  
3,ꢀꢀꢀ  
1ꢀ,ꢀꢀꢀ  
5,ꢀꢀꢀ  
3,ꢀꢀꢀ  
1,ꢀꢀꢀ  
5ꢀꢀ  
3ꢀꢀ  
1,ꢀꢀꢀ  
1,ꢀꢀꢀ  
5ꢀꢀ  
3ꢀꢀ  
5ꢀꢀ  
3ꢀꢀ  
1ꢀꢀ  
DC resistive load  
5ꢀ  
3ꢀ  
Switching 4ꢀꢀ-VDC resistive  
1ꢀꢀ  
1ꢀꢀ  
load (positive direction)  
5ꢀ  
5ꢀ  
3ꢀ  
3ꢀ  
1ꢀ  
Interrupting 4ꢀꢀ-VDC resistive  
1ꢀ  
1ꢀ  
5
3
load (positive direction)  
5
5
3
3
1
1
1
1ꢀ  
3ꢀ  
5ꢀ  
1ꢀꢀ  
3ꢀꢀ 5ꢀꢀ
 
1,ꢀꢀꢀ  
Switching voltage (V)  
1
3
5
1ꢀ  
3ꢀ  
5ꢀ  
1ꢀꢀ  
1ꢀ  
3ꢀ  
5ꢀ  
1ꢀꢀ  
Switching current (A)  
Switching current (A)  
●
Carry Current vs. Energizing Time  
●
Must-operate
V
o
ltage and Must-  
release
V
o
ltage Distributions  
(Number of Relays × Percentage of  
Rated Voltage)  
●
Time Characteristic Distributions  
(Number of Contacts × Time (ms))  
35  
35  
1ꢀꢀ,ꢀꢀꢀ  
Must-operate voltage  
Operate time  
Must-release voltage  
3ꢀ  
Release time  
3ꢀ  
1ꢀ,ꢀꢀꢀ  
1,ꢀꢀꢀ  
1ꢀꢀ  
Number: 64  
25  
25  
Number: 64  
2ꢀ  
15  
1ꢀ  
5
2ꢀ  
15  
1ꢀ  
5
1ꢀ  
1
ꢀ
ꢀ
2ꢀ  
4ꢀ  
6ꢀ  
8ꢀ  
1ꢀꢀ  
5
1ꢀ  
15  
2ꢀ  
25  
15  
1
3
5
1ꢀ  
3ꢀ  
5ꢀ  
1ꢀꢀ  
Percentage of rated voltage (0)  
Time (ms)  
Switching current (A)  
2

G9EJ-1-E  
DC Power Relays  
●
Vibration Malfunction  
●
Vibration Resistance  
●
Shock Resistance  
1
1ꢀ.ꢀ  
1ꢀ.ꢀ  
Must-operate voltage  
Must-release voltage  
Must-operate voltage  
Must-release voltage  
Number: 5  
ꢀ.9  
8.ꢀ  
6.ꢀ  
8.ꢀ  
Unconfirmed area  
ꢀ.8  
ꢀ.7  
ꢀ.6  
ꢀ.5  
ꢀ.4  
ꢀ.3  
ꢀ.2  
6.ꢀ  
4.ꢀ  
4.ꢀ  
2.ꢀ  
2.ꢀ  
ꢀ.ꢀ  
ꢀ.ꢀ  
−2.ꢀ  
−4.ꢀ  
−6.ꢀ  
−2.ꢀ  
−4.ꢀ  
−6.ꢀ  
Confirmed area  
Number: 5  
Number: 5  
ꢀ.1  
ꢀ
−8.ꢀ  
−8.ꢀ  
−1ꢀ.ꢀ  
−1ꢀ.ꢀ  
1
3
5
1ꢀ  
3ꢀ  
5ꢀ 1ꢀꢀ  
Start  
After test  
Start  
After test  
Frequency (Hz)  
Characteristics were measured after applying vibration  
at a frequency of 1ꢀ to 55 Hz (single amplitude of ꢀ.75  
mm) to the test piece (not energized)
 
for 2 hours each  
in 3 directions. The percentage rate of change is the  
average value for all of the samples  
Characteristics were measured after applying a shock  
of 49ꢀ m/s

2

to the test piece 3 times each in 6 directions  
along 3 axes.  
The percentage rate of change is the average value for  
all of the samples.  
●
Shock Malfunction  
Z
Z
Z
´  
Y
Y
5ꢀꢀ  
5ꢀꢀ  
Z
´  
X´  
X
´  
Y
´  
4ꢀꢀ  
Y
´  
4ꢀꢀ  
X
Y
X
Y
3ꢀꢀ  
3ꢀꢀ  
X
Z
X
Z
2ꢀꢀ  
2ꢀꢀ  
1ꢀꢀ  
ꢀ
1ꢀꢀ  
Deenergized  
Deenergized  
ꢀ
Z
´  
X
´  
Z
´  
X
´  
Unit: m/s

2  

Sample: G9EJ-1-E-UVD  
Number: 5  
Unit: m/s

2  

Sample: G9EJ-1-P-E-UVD  
Number: 5  
Energized  
Energized  
Y
´  
Y
´  
The value at which malfunction occurred was  
measured after applying shock to the test piece  
3 times each in 6 directions along 3 axes.  
The value at which malfunction occurred was  
measured after applying shock to the test piece  
3 times each in 6 directions along 3 axes.  
3

G9EJ-1-E  
DC Power Relays  
Dimensions
(Unit: mm)  
Mounting Hole Dimensions  
(TOP VIEW)  
G9EJ-1-E-UVD  
4
3
44  
38  
31  
2ꢀ.9  
8.5  
ꢀ.8  
15.5  
ꢀ.8  
2 (−)  
(+)1  
27 15.4  
8 3.5  
Note: Be
 
sure to connect terminals  
with the correct polarity.  
Coils do not have polarity.  
Mounting Hole Dimensions  
6.3  
ꢀ.8  
6.3  
Connecting terminals  
(#25ꢀ tab)  
Two, M3 or 3.5-dia. holes  
11  
Dimension (mm)
 
T
o
lerance (mm)  
1ꢀ or lower  
1ꢀ to 5ꢀ  
ꢀ.3  
ꢀ.5  
3ꢀ  
1
ꢀ.1  
4ꢀ  
2
Mounting Hole Dimensions  
(TOP VIEW)  
G9EJ-1-P-E-UVD  
27  
31  
4
3
3ꢀ  
32.2  
2 (−)  
(+)1  
Note: Be
 
sure to connect terminals  
with the correct polarity.  
1.2  
4
ꢀ.8  
1.2  
Coils do not have polarity.  
1.2  
6.3  
Mounting Hole Dimensions  
Relay Mounted on PCB (Reference Information)  
Six,
1.7

+ꢀ.1  

dia.  
ꢀ
(3.25)  
5.1
ꢀ.1  
ꢀ.8  
15.5  
ꢀ.8  
Dimension (mm)
 
T
o
lerance (mm)  
1ꢀ or lower  
1ꢀ to 5ꢀ  
ꢀ.3  
ꢀ.5  
15.4  
15.4

ꢀ.1  

16.3
ꢀ.1  
(32.5)  
(5.35)  
8.5  
(3.1)  
2ꢀ.9
ꢀ.1  
(7)  
2ꢀ.9  
Approved standards  
UL Recognized:  
File No.E41515  
CSA Certified:  
File No.LR31928  
VDE Certified:  
File No.40037110  
Model  
Coil ratings  
Contact ratings  
Pollution level  
2
Model  
Coil ratings  
Contact ratings  
Pollution level  
2
G9EJ-1(-P)-E-UVD
12 V, 24 V
 
15 A, 5ꢀꢀ VDC (Resistive)  
G9EJ-1(-P)-E-UVD
12 V, 24 V
 
15 A, 5ꢀꢀ VDC (Resistive)  
4

G9EJ-1-E  
DC Power Relays  
Precautions  
WARNING  
T
a
ke measures to prevent contact with charged parts  
when using the Relay for high voltages.  
Precautions for Correct Use  
Refer to the relevant catalog for common precautions.  
1. The
 
G9EJ Relays’ contacts have polarit
y
.  
11
.
D
o not use the Relay in locations where water, solvents,  
chemicals, or oil may come in contact with the case or termi-  
nals. Doing so may result in deterioration of the case resin or  
abnormal heating due to corrosion or contamination of the  
terminals. Also, if electrolyte adheres to the output terminals,  
electrolysis may occur between the output terminals, result-  
ing in corrosion of the terminals or wiring disconnections.  
12
.
B
e sure to turn OFF the power and confirm that there is no  
residual voltage before replacing the Relay or performing wir-  
ing.  
13
.
T
he distance between crimp terminals or other conductive  
parts will be reduced and insulation properties will be lowered  
if wires are laid in the same direction from the contact termi-  
nals. Use insulating coverings, do not wire in the same direc-  
tion, and take other measures as required to maintain  
insulation properties.  
Be sure to perform connections with the correct polarit
y
.  
If the contacts are connected with the reverse polarit
y
,
t
he  
switching characteristics specified in this document cannot be  
assured.  
2. Do not drop or disassemble this Rela
y
.
N
ot only may the  
Relay fail to meet the performance specifications, it may also  
result in damage, electric shock, or burning.  
3. Do
 
not use these Relays in strong magnetic fields of 8ꢀꢀ A/m  
or higher (e.g., near transformers or magnets). The arc dis-  
charge that occurs during switching may be bent by the mag-  
netic field, resulting in flashover or insulation faults.  
4. This
 
Relay is a device for switching high DC voltages. If it is  
used for voltages exceeding the specified range, it may not  
be possible to interrupt the load and burning may result. In  
order to prevent fire spreading, use a configuration in which  
the current load can be interrupted in the event of emergen-  
cies.  
14
.
U
se either a varistor, or a diode plus Zener diode as a protec-  
tive circuit against reverse surge in the relay coil. Using a  
diode alone will reduce the switching characteristics.  
15
.
U
se two M3 screws to mount a Relay with tab terminals. (The  
tightening torque is ꢀ.98 N·m.)  
In order to ensure safety of the system, replace the Relay on  
a regular basis.  
5. If
 
the Relay is used for no-load and/or minute load switching,  
the contact resistance may increase and so confirm correct  
operation under the actual operating conditions.  
16
.
M
anually mount Relays with PCB
T
e
rminals. Do not use auto-  
matic soldering for them.  
Do not bend the terminals to secure the Relay to the PCB.  
17
.
A
R
elay with PCB
T
e
rminals weighs approximately 45 g.  
Be sure that the PCB is strong enough to support it.  
18
.
F
or the PCBs, we recommend dual-side through-hole PCBs  
to reduce solder cracking from heat stress.  
19
.
T
he coil terminals (A in the figure) and contact terminals (B in  
the figure) on Relays with PCB terminals have charged metal  
parts. Also, the shaded part in the following diagram may also  
be charged. When you use the Rela
y
,
m
ake sure that there is  
no metal pattern on the corresponding part of the PCB.  
6. With
 
this Rela
y
,
i
f the rated voltage (or current) is continu-  
ously applied to the coil and contacts, and then turned OFF  
and immediately ON again, the coil temperature, and conse-  
quently the coil resistance, will be higher than usual. This  
means that the must operate voltage will also be higher than  
usual, exceeding the rated value (“hot start”). In this case,  
take the appropriate countermeasures, such as reducing the  
load current or restricting the energizing time or ambient  
operating temperature.  
7. The
 
ripple percentage for DC relays can cause fluctuations in  
the must-operate voltage or humming. For this reason,  
reduce the ripple percentage in full-wave rectified power sup-  
ply circuits by adding a smoothing capacitor. Ensure that the  
ripple percentage is less than 50.  
8. Ensure
 
that a voltage exceeding the specified maximum volt-  
age is not continuously applied to the coil. Abnormal heating  
in the coil may shorten the lifetime of the insulation coating.  
9. Do
 
not use the Relay at a switching voltage or current greater  
than the specified maximum values. Doing so may result in  
arc discharge interruption failure or burning due to abnormal  
heating in the contacts.  
Detail of Area A  
Detail of Area B  
(1)  
(1)  
1.2  
6.3  
6.3  
A
B
6
1ꢀ
.
T
he contact ratings are for resistive loads. The electrical  
endurance with inductive loads is inferior to that of resistive  
loads. Confirm correct operation under the actual operating  
conditions.  
3
Charged metal part  
9
5

•
Application examples provided in this document are for reference only. In actual applications, confirm equipment functions and safety before using the product.  
•
Consult your OMRON representative before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad  
systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems or equipment that may have a serious  
influence on lives and property if used improperly. Make sure that the ratings and performance characteristics of the product provide a margin of safety for the system or  
equipment, and be sure to provide the system or equipment with double safety mechanisms.  
Note: Do not use this document to operate the Unit.  
OMRON Corporation  
Electronic and Mechanical Components Company  