Omron-Electronics-MKS1XT-10-AC240

Part #Omron-Electronics-MKS1XT-10-AC240
Download 
Omron-Electronics-MKS1XT-10-AC240
New Product  
Power Relays  
MK-S(X)  
MK-S-series Relays with DC-switching  
Models That Can Switch 220 VDC, 10 A  
(Resistive Load).  
• Switch a DC load of 220 VDC, 10 A (resistive load).  
• Models for AC Loads can switch 250 VAC, 15 A (resistive load).  
• Lineup includes models with SPST-NO and SPST-NO/SPST-  
NC contact forms.  
• Using a SPST-NO/SPST-NC contact form enables detecting  
contact welding. (When the NO contacts become welded, the  
NC contacts will maintain a minimum distance of 0.5 mm.)  
• Models available with operation indicators and built-in test  
buttons.  
For the most recent information on models that have been certified for  
safety standards, refer to your OMRON website.  
• RoHS compliant.  
• Standards: UL, IEC (TÜV certification)  
Ordering Information  
When your order, specify the rated voltage.  
General-purpose Relays  
Models for DC Loads  
Contact form  
SPST-NO  
Rated voltage (V)  
SPST-NO/SPST-NC  
Type  
Model  
Model  
Rated voltage (V)  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
Standard Models  
MKS1XT-10  
MKS2XT-11  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
Models with Built-in  
Operation Indicators  
MKS1XTN-10  
MKS1XTI-10  
MKS1XTIN-10  
MKS2XTN-11  
MKS2XTI-11  
MKS2XTIN-11  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
Models with Test Button  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
Models with Test Button and  
Built-in Operation Indicators  
Models for AC Loads  
Contact form  
SPST-NO  
SPST-NO/SPST-NC  
Type  
Model  
Rated voltage (V)  
Model  
Rated voltage (V)  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
Standard Models  
MKS1T-10  
MKS2T-11  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
Models with Built-in  
Operation Indicators  
MKS1TN-10  
MKS1TI-10  
MKS1TIN-10  
MKS2TN-11  
MKS2TI-11  
MKS2TIN-11  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
Models with Test Button  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
AC: 24, 100, 110, 120, 200, 220, 230, 240  
DC: 12, 24, 48, 110, 220  
Models with Test Button and  
Built-in Operation Indicators  
Accessory (Order Separately)  
Connecting Socket  
Classifications  
Built-in diode  
Model  
Back-connecting Socket  
PCB Terminals  
No  
No  
P7M-06P  
P7MF-06  
Mounts to DIN Track or via  
screws  
Front-connecting Socket  
Yes  
P7MF-06-D  
1

MK-S(X)  
Specifications  
Ratings  
Operating Coil  
Must  
operate  
voltage (V)  
Must  
release  
voltage (V)
 
allowable (V)  
Maximum  
voltage  
Coil  
resistance  
(
Ω
)  
Power  
consumption  
(VA, W)  
Item  
Rated current (mA)  
Rated voltage (V)  
50 Hz  
110  
60 Hz  
96.3  
23.1  
21.0  
19.3  
11.6  
10.5  
10.0  
9.6  
Percentage of rated voltage  
24  
100  
110  
48.4  
760  
26.6  
24.2  
22.2  
13.3  
12.1  
11.5  
11.0  
932  
30% min. at  
60 Hz  
25% min. at  
50 Hz  
Approx. 2.3 VA  
at 60 Hz  
Approx. 2.7 VA  
at 50 Hz  
120  
1,130  
3,160  
3,550  
4,250  
4,480  
95  
AC  
200  
220  
230  
240  
12  
80% max.  
110%  
126  
63.2  
24  
380  
DC  
48  
110  
220  
32.0  
13.6  
6.8  
1,500  
8,060  
32,200  
15% min.  
Approx. 1.5 W  
Note: 1.
 
The rated current and coil resistance are measured at a coil temperature of 23
°
C with tolerances of +15%/
−
20% for AC rated current and  
15% for DC coil resistance.  
2.
Performance characteristic data are measured at a coil temperature of 23
°
C.  
3.
The maximum allowable voltage is the maximum value of the allowable voltage range for the operating power supply for the relay coil.  
There is no continuous allowance.  
4.
The rated current is approximately 5 mA higher for Models with Built-in Operation Indicators (DC operating coils).  
2

MK-S(X)  
Contact Ratings for Models for DC Loads  
Contact form  
Model  
SPST-NO  
MKS1XT(I)(N)-10  
Inductive load  
SPST-NO/SPST-NC  
MKS2XT(I)(N)-11  
Load  
Inductive load  
Resistive load  
Resistive load  
Item  
L/R = 7 ms  
DC13 class  
L/R = 7 ms  
Double-break  
Single-break  
AgSnIn  
DC13 class  
NO  
Double-break  
Contact configuration  
Contact material  
Rated load  
NC  
—  
AgSnIn  
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
10 A, 220 VDC  
5 A, 220 VDC  
0.4 A, 220 VDC  
5 A, 220 VDC  
2 A, 220 VDC  
3 A, 220 VDC  
0.3 A, 220 VDC  
5 A  
0.2 A, 220 VDC  
0.1 A, 220 VDC  
—  
10 A  
—  
Rated carry current  
2 A  
220 VDC  
—  
Max. switching voltage  
Max. switching current  
220 VDC  
10 A  
5 A  
0.4 A  
—  
5 A  
2 A  
3 A  
0.3 A  
—  
0.2 A  
0.1 A  
—  
—  
2,200 W  
—  
1,100 W  
440 W  
Max. switching capacity  
(reference value)  
—  
—  
—  
Note:
If the L/R of an inductive load exceeds 7 ms with a Model for a DC Load, the arc interruption time must be less than approximately 50 ms  
to use the Relay. Design the circuit so that the arc interruption time is 50 ms or less.  
*
These values apply to a switching frequency of 30 times per minute.  
Contact Ratings for Models for AC Loads  
Contact form  
Model  
SPST-NO  
SPST-NO/SPST-NC  
MKS2T(I)(N)-11  
MKS1T(I)(N)-10  
Load  
Resistive load  
Resistive load  
Item  
NO  
Double-break  
Double-break  
Single-break  
AgSnIn  
Contact configuration  
Contact material  
Rated load  
NC  
—  
AgSnIn  
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
15 A, 250 VAC  
15 A, 250 VAC  
5 A, 250 VAC  
15 A  
—  
15 A  
—  
Rated carry current  
5 A  
250 VAC  
—  
Max. switching voltage  
Max. switching current  
250 VAC  
15 A  
—  
15 A  
5 A  
3,750 VA  
—  
3,750 VA  
1,250 VA  
Max. switching capacity  
(reference value)  
*
These values apply to a switching frequency of 20 times per minute.  
3

MK-S(X)  
Characteristics  
Contact resistance
*
1  
Operate time
*
2  
100 m
Ω
max.  
AC: 20 ms max.  
DC: 30 ms max.  
Release time
*
2  
20 ms max.  
Mechanical  
18,000 operations/h  
Max. operating  
frequency  
Models for DC loads: 1,800 times/hour  
Models for AC loads: 1,200 times/hour  
Rated load  
Insulation resistance
*
3  
Between coil and contacts  
100 M
Ω
min.  
2,500 VAC 50/60 Hz for 1 min between  
Dielectric  
strength  
Between contacts of different polarity
 
2,500 VAC 50/60 Hz for 1 min between  
Between contacts of same polarity  
Destruction  
1,000 VAC 50/60 Hz for 1 min  
10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)  
Vibration  
resistance  
Malfunction  
10 to 55 to 10 Hz, 0.50-mm single amplitude (1.0-mm double amplitude)  
Back-connecting Socket (P7M-06P) mounting: 1,000 m/s

2  

Front-connecting Socket (P7MF-06(-D)) mounting:500m/s

2  

100 m/s

2  

Destruction  
Shock  
resistance  
Malfunction  
Mechanical  
Electrical
*
4  
1,000,000 operations min. (at 18,000 operations/hr)  
100,000 operations min. (at rated load and maximum switching frequency)  
10 mA at 24 VDC  
Endurance  
Failure rate P level (reference value)  
−
40
°
C to 60
°
C (with no icing or condensation)  
Note:
The range is
−
25
°
C to 60
°
C for models with built-in operation indicators.  
Ambient operating temperature  
Ambient operating humidity  
Weight  
5% to 85%  
SPST-NO: Approx. 73 g, SPST-NO/SPST-NC: Approx. 82 g  
Note:
The values given above are initial values.  
*1.
The contact resistance was measured for 1 A at 5 VDC using the voltage drop method.  
*2.
The operate time was measured with the rated voltage imposed and any contact bounce ignored at an ambient temperature of 23
°
C.  
*3.
The insulation resistance was measured with a 500-VDC insulation resistance tester at the same places as those used for checking the  
dielectric strength.  
*4.
The electrical endurance was measured at an ambient temperature of 23
°
C.  
Approved Standards  
UL508 (File No. E41515)  
*
Model  
Coil ratings  
Contact ratings  
Operations  
10 A, 220 VDC (Resistive)  
NO contacts
 
5 A, 220 VDC L/R (T

0.632

) = 7 ms  
0.4 A, 220 VDC L/R (T

0.95

) = 300 ms  
MKS1XT
@
–
@  
5 A, 220 VDC (Resistive)  
NO contacts
 
3 A, 220 VDC L/R (T

0.632

) = 7 ms  
0.2 A, 220 VDC L/R (T

0.95

) = 300 ms  
12 to 220 VDC  
24 to 240 VAC  
MKS2XT
@
–
@  
6,000  
2 A, 220 VDC (Resistive)  
NC contacts  
0.3 A, 220 VDC L/R (T

0.632

) = 7 ms  
0.1 A, 220 VDC L/R (T

0.95

) = 300 ms  
MKS1T
@
–
@  
MKS2T
@
–
@  
NO contacts
 
15 A, 250 VAC (Resistive)  
NO contacts
 
15 A, 250 VAC (Resistive)  
5 A, 250 VAC (Resistive)  
NC contacts  
CSA Standard: CSA Certification by  
: CSA C22.2 No.14  
IEC Standard/TÜV Certification: IEC61810-1 (Certification No. R50104853)  
Model  
Coil ratings  
Contact ratings  
Operations  
DC-1: 10 A, 220 VDC  
NO contacts
 
5 A, 220 VDC L/R (T

0.632

) = 7 ms  
DC-13: 0.4 A, 220 VDC  
MKS1XT
@
–
@  
DC-1: 5 A, 220 VDC  
NO contacts
 
3 A, 220 VDC L/R (T

0.632

) = 7 ms  
DC-13: 0.2 A, 220 VDC  
12, 24, 48, 110,  
220 VDC  
24, 100, 110, 120,  
200, 220, 230,  
240 VAC  
MKS2XT
@
–
@  
100,000  
DC-1: 2 A, 220 VDC  
0.3 A, 220 VDC L/R (T

0.632

) = 7 ms  
DC-13: 0.1 A, 220 VDC  
NC contacts  
MKS1T
@
–
@  
MKS2T
@
–
@  
NO contacts
 
AC-1: 15 A, 250 VAC 50/60 Hz  
NO contacts
 
AC-1: 15 A, 250 VAC 50/60 Hz  
AC-1: 5 A, 250 VAC 50/60 Hz  
NC contacts  
4

MK-S(X)  
Engineering Data  
Maximum Switching Power  
MKS1XT-10, MKS1XTN-10  
MKS1XTI-10, MKS1XTIN-10  
MKS2XT-11, MKS2XTN-11  
MKS2XTI-11, MKS2XTIN-11  
100  
100  
DC resistive load  
DC inductive load  
L/R = 7 ms  
NO  
DC resistive load  
NO  
10  
10  
5
5
3
DC inductive load  
L/R = 7 ms  
2
DC inductive load  
L/R = 7 ms  
NC  
1
1
DC resistive load  
NC  
0.4  
0.3  
0.2  
0.1  
0.1  
DC inductive load  
DC inductive load  
DC13 class  
NO  
DC13 class  
DC inductive load  
DC13 class  
NC  
0.01  
0.01  
1
10  
100  
1.000  
1
10  
100  
1.000  
Switching voltage (V)  
Switching voltage (V)  
MKS1T-10, MKS1TN-10  
MKS1TI-10, MKS1TIN-10  
100  
MKS2T-11, MKS2TN-11  
MKS2TI-11, MKS2TIN-11  
100  
AC resistive
 
load  
NO  
15  
10  
15  
10  
5
AC resistive load  
AC resistive
 
load  
1
1
NC  
0.1  
0.1  
0.01  
0.01  
1
10  
100  
1.000  
1
10  
100  
1.000  
Switching voltage (V)  
Switching voltage (V)  
Ambient Temperature vs. Must Operate Voltage and Must Release Voltage  
MKS2XT-11  
AC Specification (60 Hz)  
MKS2XT-11  
DC Specification  
100  
100  
Must operate  
voltage  
Number of Relays: 5  
Must operate  
voltage  
Number of Relays: 5  
Must release  
voltage  
Must release  
voltage  
80  
80  
60  
40  
20  
60  
40  
20  
-40  
23  
60  
-40  
23  
60  
Ambient temperature (
°
C)  
Ambient temperature (
°
C)  
Inductive Load Switching Power (Models for DC Loads)  
MKS1XT-10, MKS1XTN-10  
MKS1XTI-10, MKS1XTIN-10  
MKS2XT-11, MKS2XTN-11  
MKS2XTI-11, MKS2XTIN-11  
100  
10  
220 VDC  
220 VDC  
NO  
10  
1
1
0.1  
NC  
0.1  
0.01  
0
7 10  
50  
100  
0
7 10  
50  
100  
Load time constant (ms)  
Load time constant (ms)  
5

MK-S(X)  
Test Button  
The circuit can be checked using either of two modes.  
Test Button  
Mode 1  
(momentary)  
Mode 2  
(locked)  
DC specification: Blue  
AC specification: Red  
Normal  
Press the button  
for operation.  
(No tool is required.)  
Lock the contacts by  
pressing down on the  
button and turning it.  
Test Button Applications  
Example: Checking operation of Relays and sequence circuits.  
6

MK-S(X)  
Dimensions  
(Unit: mm)  
General-purpose Relays  
Models for DC Loads  
Standard Models  
34.5 max.  
MKS1XT-10  
Models with Built-in Operation Indicators  
MKS1XTN-10 MKS2XTN-11  
MKS2XT-11  
34.5 max.  
Models for AC Loads  
Standard Models  
0.8  
MKS1T-10  
MKS2T-11  
Models with Built-in Operation Indicators  
44 max.  
MKS1TN-10  
MKS2TN-11  
7.3  
3.5  
Models for DC Loads  
Models with Test Button  
MKS1XTI-10  
Models with Test Button and Built-in  
Operation Indicators  
MKS2XTI-11  
34.5 max.  
MKS1XTIN-10  
MKS2XTIN-11  
34.5 max.  
Models for AC Loads  
0.8  
0.5  
Models with Test Button  
MKS1TI-10  
MKS2TI-11  
Models with Test Button and Built-in  
Operation Indicators  
44 max.  
29.7  
MKS1TIN-10  
MKS2TIN-11  
7.3  
Terminal Arrangement/Internal Connection
(Bottom View)  
MKS1XT-10  
MKS1XTI-10  
MKS1XTN-10  
MKS1XTIN-10  
MKS2XT-11  
MKS2XTI-11  
MKS2XTN-11  
MKS2XTIN-11  
DC specification  
AC specification  
DC specification  
AC specification  
2
2
2
4
6 (
+)  
B
4
6 (+)  
4
6 (+)  
4
6 (+)  
B
4
6 (+)  
4
6 (+)  
B
8
8
8 (+)  
8 (+)  
8 (+)  
8
A
A (+)  
B (
−
)  
A
B
A
A (+)  
B (
−
)  
A
MKS1T-10  
MKS1TI-10  
MKS1TN-10  
MKS1TIN-10  
MKS2T-11  
MKS2TI-11  
MKS2TN-11  
MKS2TIN-11  
DC specification  
AC specification  
DC specification  
AC specification  
2
2
2
8
4
6
4
6
4
6
4
6
4
6
4
6
8
8
8
8
8
A (+)  
B (
−
)  
A (+)  
B (
−
)  
A
B
A
B
A
B
A
B
Note: 1.
 
Wire properly using the correct coil polarity.  
2.
The contact terminals on Models for DC Loads have polarity. Wire properly using the correct polarity.  
7

MK-S(X)  
Connecting Socket  
Back-connecting Socket  
P7M-06P  
Terminal Arrangement/Internal Connections
 
PCB Mounting Holes  
Dimensions  
(Bottom View)  
(Bottom View)  
39 max.  
2
5.5  
4
6
43 max.  
39 max.  
8.3  
7.7  
0.9  
8
A
B
Six 1.8-dia. hole  
21.9  
1.55  
4.35  
22.1  
0.5  
0.9  
7.7  
8.3  
5.5  
Front-connecting Socket  
P7MF-06  
P7MF-06-D  
Terminal Arrangement/Internal Connections  
(TOP View)  
Mounting Holes  
(TOP View)  
Dimensions  
7
P7MF-±6  
P7MF-±6-D  
34 max.  
T
w
o, M4 or  
two 3.5-dia. hole  
66±±.3  
78 max.  
35.5  
Note: 1. The internal connections diagram is for the MKS2(X)T
@@
-11.  
2. The P7MF-±6-D has polarit
y
.
B
e careful to wire with the  
correct polarit
y
.  
4
6
39 max.  
31±±.2  
24.3  
Six, M3 x 8  
8

MK-S(X)  
Accessory (Order Separately)  
Connecting Socket  
Socket  
Back-connecting Socket  
PCB terminals  
Front-connecting Socket  
Number of poles  
Mounts to DIN Track or via screws  
P7M-06P  
P7MF-06  
P7MF-06-D  
2
Note: 1.
 
The P7M-06P, P7MF-06, and P7MF-06-D can be used with models for DC loads with an SPST-NO or SPST-NO/SPST-NC contact form  
or with models for AC loads with an SPST-NO or SPST-NO/SPST-NC contact form.  
2.
The P7MF-06-D has a built-in diode and can thus be used only with Relays with DC operating coils. Do not use it with a Relay with an  
AC operating coil.  
3.
Refer to
Gang Mounting
on page 10 for the conditions required for gang mounting.  
Relay Hold-down Clips  
Use the Clips to securely mount the Relay and prevent it from falling due to vibration or shock.  
PYC-A2  
One Set (Two Clips)  
Applicable Relay models  
MKS1XT-10  
MKS1XTI-10  
MKS1XTIN-10  
MKS1XTN-10  
MKS1T-10  
MKS2XT-11  
MKS2XTI-11  
MKS2XTIN-11  
MKS2XTN-11  
MKS2T-11  
5 max.  
Socket  
MKS1TI-10  
MKS2TI-11  
MKS1TIN-10  
MKS1TN-10  
MKS2TIN-11  
MKS2TN-11  
42.8  
4.5  
Back-connecting Socket  
Front-connecting Socket  
PCB terminals  
P7M-06P  
P7MF-06  
Mounts to DIN  
Track or via  
screws  
PYC-A2  
P7MF-06-D  
4.5  
1.2  
Note:
The minimum order for the  
PYC-A2 is ten clips.  
Socket Mounting Height  
P7M-06P  
64  
61  
MK-S(X)  
P7MF-06  
P7MF-06-D  
MK-S(X)  
70  
75  
79  
74  
9

MK-S(X)  
Safety Precautions  
Refer also to
Precautions for All Relays
.  
Precautions for Correct Use  
Installation  
•
Models for DC loads (i.e., models with “X” in the model number)  
have permanent magnets built into the insulating block. If a  
permanent magnet or other magnetic body comes near the Relay,  
magnetic interference will occur with the built-in permanent magnet  
and the contact switching capacity will be decreased.  
•
Models for AC loads do not contain a permanent magnet.  
•
When mounting a P7MF-06(-D) Front-mounting Socket to a DIN  
Track, attach PFP-M End Plates on both sides of the Socket to  
prevent it from moving.  
Test Button  
•
Turn OFF the power supply before operating the test button.  
Always return the test button to the original position after you use it.  
•
Do not use the test button as a switch.  
•
The durability of the test button is 100 operations minimum.  
Operating Environment  
Do not use the Relay in environments with combustible gas. Doing so  
may result in explosion due to arcing.  
Storage  
Gang Mounting  
Models for DC Loads (i.e., models with “X” in the model number) are  
magnetized because they have a built-in magnet to deflect and  
extinguish the arc. Do not install the Relay near IC cards or other  
items that may be adversely affected by magnetism.  
Conditions for Gang Mounting Relays  
Socket  
Rate
d
c
urrent  
of Relay  
Back-Connecting  
Socket  
Front-Connecting  
Socket  
Relay  
Usage  
Model
s
f
or  
DC Loads  
10A  
15A  
❍
❍
❍
Use the Relay mounted in the P7M-06P or P7MF-06(-D) Socket.  
Model
s
f
or  
AC Loads  
*
*
Gang mounting of the Front-Mounting Sockets is not possible if the  
contact carry current exceeds 10A.Provide space on both the right  
and left sides of the Sockets.  
The mounting pitch is given in the following diagram.  
20  
15  
10  
5
0
0
10  
20  
30  
40  
50  
Mounting interval (mm)  
Mounting interval  
Wiring  
•
The contact terminals on Models for DC Loads (i.e., models with  
“X” in the model number) have polarity. Wiring with incorrect  
polarity may result in inability to turn OFF the Relay or loss of  
functionality.  
•
Wire models with built-in operation indicators with the correct coil  
polarity (DC operating coil).  
10  

MK-S(X)  
Warranty and Application Considerations  
Read and Understand this Catalog  
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you  
have any questions or comments.  
Warranty and Limitations of Liability  
WARRANTY  
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or  
other period if specified) from date of sale by OMRON.  
OMRON MAKES NO WARRANTY OR REPRESEN
T
A
T
ION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMEN
T
,  
MERCHAN
T
A
BILIT
Y
,
O
R FITNESS FOR
P
A
RTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER  
ACKNOWLEDGES TH
A
T
T
HE BUYER OR USER ALONE HAS DETERMINED TH
A
T
T
HE PRODUCTS WILL SUI
T
A
B
L
Y
M
EET  
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR  
IMPLIED.  
LIMITATIONS OF LIABILITY  
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIREC
T
,
O
R CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,  
OR COMMERCIAL LOSS IN ANY W
A
Y
C
ONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON  
CONTRAC
T
, WARRANT
Y
,
N
EGLIGENCE, OR STRICT LIABILIT
Y
.  
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.  
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANT
Y
,
R
E
P
A
IR, OR OTHER CLAIMS REGARDING THE  
PRODUCTS UNLESS OMRON’S ANA
L
Y
SIS CONFIRMS TH
A
T
T
HE PRODUCTS WERE PROPER
L
Y
H
ANDLED, STORED,  
INS
T
A
LLED, AND MAIN
T
A
INED AND NOT SUBJECT TO CON
T
A
MIN
A
T
ION, ABUSE, MISUSE, OR INAPPROPRI
A
T
E  
MODIFIC
A
T
ION OR RE
P
A
IR.  
Application Considerations  
SUITABILITY FOR USE  
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of  
products in the customer’s application or use of the products.  
T
a
ke all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will  
be used.  
Know and observe all prohibitions of use applicable to this product.  
NEVER USE THE PRODUCTS FOR AN APPLIC
A
T
ION INVO
L
V
ING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT  
ENSURING TH
A
T
T
HE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND TH
A
T
T
HE OMRON  
PRODUCTS ARE PROPER
L
Y
R
A
T
ED AND INS
T
A
LLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR  
SYSTEM.  
Disclaimers  
PERFORMANCE DATA  
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a  
warrant
y
.
I
t may represent the result of OMRON’s test conditions, and the users must correlate it to actual application  
requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liabilit
y
.  
CHANGE IN SPECIFIC
A
T
IONS  
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with  
your OMRON representative at any time to confirm actual specifications of purchased product.  
DIMENSIONS AND WEIGHTS  
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.  
11  

OMRON ELECTRONICS LLC  
One Commerce Drive Schaumburg,  
IL 60173-5302 U.S.A.  
OMRON Corporation  
Authorized Distributor:  
Industrial Automation Company  
T
e
l: (1) 847-843-7900/Fax: (1) 847-843-7787  
Control Devices Division H.Q.  
Strategy Planning Division  
Shiokoji Horikawa, Shimogyo-ku,  
Kyoto, 600-8530 Japan  
T
e
l: (81) 75-344-7109/Fax: (81) 75-344-7149  
OMRON ASIA
P
ACIFIC PTE. LTD.  
No. 438A Alexandra Road # 05-05/08 (Lobby 2),  
Alexandra
T
e
chnopark, Singapore 119967  
T
e
l: (65) 6835-3011/Fax: (65) 6835-2711  
Regional Headquarters  
OMRON EUROPE B.
V
.  
Wegalaan 67-69-2132 JD Hoofddorp  
The Netherlands  
T
e
l: (31)2356-81-300/Fax: (31)2356-81-388  
OMRON (CHINA) CO., LTD.  
Room 2211, Bank of China
T
o
wer,  
200 Yin Cheng Zhong Road,  
PuDong New Area, Shanghai, 200120, China  
T
e
l: (86) 21-5037-2222/Fax: (86) 21-5037-2200  
© OMRON Corporation 2008-2020
 
All Rights Reserved.  
In the interest of product improvement,  
specifications are subject to change without notice.  
CSM_5_3  
Cat. No. J175-E1-03  
Printed in Japan  
0520(0809)  
OMRON Industrial Automation Global: