Omron-Electronics-MKS1XTIN-10-AC110
| Part # | Omron-Electronics-MKS1XTIN-10-AC110 |
| Download | Omron-Electronics-MKS1XTIN-10-AC110 |
New Product
Power Relays
MK-S(X)
MK-S-series Relays with DC-switching
Models That Can Switch 220 VDC, 10 A
(Resistive Load).
• Switch a DC load of 220 VDC, 10 A (resistive load).
• Models for AC Loads can switch 250 VAC, 15 A (resistive load).
• Lineup includes models with SPST-NO and SPST-NO/SPST-
NC contact forms.
• Using a SPST-NO/SPST-NC contact form enables detecting
contact welding. (When the NO contacts become welded, the
NC contacts will maintain a minimum distance of 0.5 mm.)
• Models available with operation indicators and built-in test
buttons.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
• RoHS compliant.
• Standards: UL, IEC (TÜV certification)
Ordering Information
When your order, specify the rated voltage.
General-purpose Relays
Models for DC Loads
Contact form
SPST-NO
Rated voltage (V)
SPST-NO/SPST-NC
Type
Model
Model
Rated voltage (V)
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
Standard Models
MKS1XT-10
MKS2XT-11
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
Models with Built-in
Operation Indicators
MKS1XTN-10
MKS1XTI-10
MKS1XTIN-10
MKS2XTN-11
MKS2XTI-11
MKS2XTIN-11
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
Models with Test Button
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
Models with Test Button and
Built-in Operation Indicators
Models for AC Loads
Contact form
SPST-NO
SPST-NO/SPST-NC
Type
Model
Rated voltage (V)
Model
Rated voltage (V)
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
Standard Models
MKS1T-10
MKS2T-11
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
Models with Built-in
Operation Indicators
MKS1TN-10
MKS1TI-10
MKS1TIN-10
MKS2TN-11
MKS2TI-11
MKS2TIN-11
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
Models with Test Button
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
Models with Test Button and
Built-in Operation Indicators
Accessory (Order Separately)
Connecting Socket
Classifications
Built-in diode
Model
Back-connecting Socket
PCB Terminals
No
No
P7M-06P
P7MF-06
Mounts to DIN Track or via
screws
Front-connecting Socket
Yes
P7MF-06-D
1
MK-S(X)
Specifications
Ratings
Operating Coil
Must
operate
voltage (V)
Must
release
voltage (V)
allowable (V)
Maximum
voltage
Coil
resistance
(
Ω
)
Power
consumption
(VA, W)
Item
Rated current (mA)
Rated voltage (V)
50 Hz
110
60 Hz
96.3
23.1
21.0
19.3
11.6
10.5
10.0
9.6
Percentage of rated voltage
24
100
110
48.4
760
26.6
24.2
22.2
13.3
12.1
11.5
11.0
932
30% min. at
60 Hz
25% min. at
50 Hz
Approx. 2.3 VA
at 60 Hz
Approx. 2.7 VA
at 50 Hz
120
1,130
3,160
3,550
4,250
4,480
95
AC
200
220
230
240
12
80% max.
110%
126
63.2
24
380
DC
48
110
220
32.0
13.6
6.8
1,500
8,060
32,200
15% min.
Approx. 1.5 W
Note: 1.
The rated current and coil resistance are measured at a coil temperature of 23
°
C with tolerances of +15%/
−
20% for AC rated current and
15% for DC coil resistance.
2.
Performance characteristic data are measured at a coil temperature of 23
°
C.
3.
The maximum allowable voltage is the maximum value of the allowable voltage range for the operating power supply for the relay coil.
There is no continuous allowance.
4.
The rated current is approximately 5 mA higher for Models with Built-in Operation Indicators (DC operating coils).
2
MK-S(X)
Contact Ratings for Models for DC Loads
Contact form
Model
SPST-NO
MKS1XT(I)(N)-10
Inductive load
SPST-NO/SPST-NC
MKS2XT(I)(N)-11
Load
Inductive load
Resistive load
Resistive load
Item
L/R = 7 ms
DC13 class
L/R = 7 ms
Double-break
Single-break
AgSnIn
DC13 class
NO
Double-break
Contact configuration
Contact material
Rated load
NC
—
AgSnIn
NO
NC
NO
NC
NO
NC
NO
NC
NO
NC
10 A, 220 VDC
5 A, 220 VDC
0.4 A, 220 VDC
5 A, 220 VDC
2 A, 220 VDC
3 A, 220 VDC
0.3 A, 220 VDC
5 A
0.2 A, 220 VDC
0.1 A, 220 VDC
—
10 A
—
Rated carry current
2 A
220 VDC
—
Max. switching voltage
Max. switching current
220 VDC
10 A
5 A
0.4 A
—
5 A
2 A
3 A
0.3 A
—
0.2 A
0.1 A
—
—
2,200 W
—
1,100 W
440 W
Max. switching capacity
(reference value)
—
—
—
Note:
If the L/R of an inductive load exceeds 7 ms with a Model for a DC Load, the arc interruption time must be less than approximately 50 ms
to use the Relay. Design the circuit so that the arc interruption time is 50 ms or less.
*
These values apply to a switching frequency of 30 times per minute.
Contact Ratings for Models for AC Loads
Contact form
Model
SPST-NO
SPST-NO/SPST-NC
MKS2T(I)(N)-11
MKS1T(I)(N)-10
Load
Resistive load
Resistive load
Item
NO
Double-break
Double-break
Single-break
AgSnIn
Contact configuration
Contact material
Rated load
NC
—
AgSnIn
NO
NC
NO
NC
NO
NC
NO
NC
NO
NC
15 A, 250 VAC
15 A, 250 VAC
5 A, 250 VAC
15 A
—
15 A
—
Rated carry current
5 A
250 VAC
—
Max. switching voltage
Max. switching current
250 VAC
15 A
—
15 A
5 A
3,750 VA
—
3,750 VA
1,250 VA
Max. switching capacity
(reference value)
*
These values apply to a switching frequency of 20 times per minute.
3
MK-S(X)
Characteristics
Contact resistance
*
1
Operate time
*
2
100 m
Ω
max.
AC: 20 ms max.
DC: 30 ms max.
Release time
*
2
20 ms max.
Mechanical
18,000 operations/h
Max. operating
frequency
Models for DC loads: 1,800 times/hour
Models for AC loads: 1,200 times/hour
Rated load
Insulation resistance
*
3
Between coil and contacts
100 M
Ω
min.
2,500 VAC 50/60 Hz for 1 min between
Dielectric
strength
Between contacts of different polarity
2,500 VAC 50/60 Hz for 1 min between
Between contacts of same polarity
Destruction
1,000 VAC 50/60 Hz for 1 min
10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Vibration
resistance
Malfunction
10 to 55 to 10 Hz, 0.50-mm single amplitude (1.0-mm double amplitude)
Back-connecting Socket (P7M-06P) mounting: 1,000 m/s
2
Front-connecting Socket (P7MF-06(-D)) mounting:500m/s
2
100 m/s
2
Destruction
Shock
resistance
Malfunction
Mechanical
Electrical
*
4
1,000,000 operations min. (at 18,000 operations/hr)
100,000 operations min. (at rated load and maximum switching frequency)
10 mA at 24 VDC
Endurance
Failure rate P level (reference value)
−
40
°
C to 60
°
C (with no icing or condensation)
Note:
The range is
−
25
°
C to 60
°
C for models with built-in operation indicators.
Ambient operating temperature
Ambient operating humidity
Weight
5% to 85%
SPST-NO: Approx. 73 g, SPST-NO/SPST-NC: Approx. 82 g
Note:
The values given above are initial values.
*1.
The contact resistance was measured for 1 A at 5 VDC using the voltage drop method.
*2.
The operate time was measured with the rated voltage imposed and any contact bounce ignored at an ambient temperature of 23
°
C.
*3.
The insulation resistance was measured with a 500-VDC insulation resistance tester at the same places as those used for checking the
dielectric strength.
*4.
The electrical endurance was measured at an ambient temperature of 23
°
C.
Approved Standards
UL508 (File No. E41515)
*
Model
Coil ratings
Contact ratings
Operations
10 A, 220 VDC (Resistive)
NO contacts
5 A, 220 VDC L/R (T
0.632
) = 7 ms
0.4 A, 220 VDC L/R (T
0.95
) = 300 ms
MKS1XT
@
–
@
5 A, 220 VDC (Resistive)
NO contacts
3 A, 220 VDC L/R (T
0.632
) = 7 ms
0.2 A, 220 VDC L/R (T
0.95
) = 300 ms
12 to 220 VDC
24 to 240 VAC
MKS2XT
@
–
@
6,000
2 A, 220 VDC (Resistive)
NC contacts
0.3 A, 220 VDC L/R (T
0.632
) = 7 ms
0.1 A, 220 VDC L/R (T
0.95
) = 300 ms
MKS1T
@
–
@
MKS2T
@
–
@
NO contacts
15 A, 250 VAC (Resistive)
NO contacts
15 A, 250 VAC (Resistive)
5 A, 250 VAC (Resistive)
NC contacts
CSA Standard: CSA Certification by
: CSA C22.2 No.14
IEC Standard/TÜV Certification: IEC61810-1 (Certification No. R50104853)
Model
Coil ratings
Contact ratings
Operations
DC-1: 10 A, 220 VDC
NO contacts
5 A, 220 VDC L/R (T
0.632
) = 7 ms
DC-13: 0.4 A, 220 VDC
MKS1XT
@
–
@
DC-1: 5 A, 220 VDC
NO contacts
3 A, 220 VDC L/R (T
0.632
) = 7 ms
DC-13: 0.2 A, 220 VDC
12, 24, 48, 110,
220 VDC
24, 100, 110, 120,
200, 220, 230,
240 VAC
MKS2XT
@
–
@
100,000
DC-1: 2 A, 220 VDC
0.3 A, 220 VDC L/R (T
0.632
) = 7 ms
DC-13: 0.1 A, 220 VDC
NC contacts
MKS1T
@
–
@
MKS2T
@
–
@
NO contacts
AC-1: 15 A, 250 VAC 50/60 Hz
NO contacts
AC-1: 15 A, 250 VAC 50/60 Hz
AC-1: 5 A, 250 VAC 50/60 Hz
NC contacts
4
MK-S(X)
Engineering Data
Maximum Switching Power
MKS1XT-10, MKS1XTN-10
MKS1XTI-10, MKS1XTIN-10
MKS2XT-11, MKS2XTN-11
MKS2XTI-11, MKS2XTIN-11
100
100
DC resistive load
DC inductive load
L/R = 7 ms
NO
DC resistive load
NO
10
10
5
5
3
DC inductive load
L/R = 7 ms
2
DC inductive load
L/R = 7 ms
NC
1
1
DC resistive load
NC
0.4
0.3
0.2
0.1
0.1
DC inductive load
DC inductive load
DC13 class
NO
DC13 class
DC inductive load
DC13 class
NC
0.01
0.01
1
10
100
1.000
1
10
100
1.000
Switching voltage (V)
Switching voltage (V)
MKS1T-10, MKS1TN-10
MKS1TI-10, MKS1TIN-10
100
MKS2T-11, MKS2TN-11
MKS2TI-11, MKS2TIN-11
100
AC resistive
load
NO
15
10
15
10
5
AC resistive load
AC resistive
load
1
1
NC
0.1
0.1
0.01
0.01
1
10
100
1.000
1
10
100
1.000
Switching voltage (V)
Switching voltage (V)
Ambient Temperature vs. Must Operate Voltage and Must Release Voltage
MKS2XT-11
AC Specification (60 Hz)
MKS2XT-11
DC Specification
100
100
Must operate
voltage
Number of Relays: 5
Must operate
voltage
Number of Relays: 5
Must release
voltage
Must release
voltage
80
80
60
40
20
60
40
20
-40
23
60
-40
23
60
Ambient temperature (
°
C)
Ambient temperature (
°
C)
Inductive Load Switching Power (Models for DC Loads)
MKS1XT-10, MKS1XTN-10
MKS1XTI-10, MKS1XTIN-10
MKS2XT-11, MKS2XTN-11
MKS2XTI-11, MKS2XTIN-11
100
10
220 VDC
220 VDC
NO
10
1
1
0.1
NC
0.1
0.01
0
7 10
50
100
0
7 10
50
100
Load time constant (ms)
Load time constant (ms)
5
MK-S(X)
Test Button
The circuit can be checked using either of two modes.
Test Button
Mode 1
(momentary)
Mode 2
(locked)
DC specification: Blue
AC specification: Red
Normal
Press the button
for operation.
(No tool is required.)
Lock the contacts by
pressing down on the
button and turning it.
Test Button Applications
Example: Checking operation of Relays and sequence circuits.
6
MK-S(X)
Dimensions
(Unit: mm)
General-purpose Relays
Models for DC Loads
Standard Models
34.5 max.
MKS1XT-10
Models with Built-in Operation Indicators
MKS1XTN-10 MKS2XTN-11
MKS2XT-11
34.5 max.
Models for AC Loads
Standard Models
0.8
MKS1T-10
MKS2T-11
Models with Built-in Operation Indicators
44 max.
MKS1TN-10
MKS2TN-11
7.3
3.5
Models for DC Loads
Models with Test Button
MKS1XTI-10
Models with Test Button and Built-in
Operation Indicators
MKS2XTI-11
34.5 max.
MKS1XTIN-10
MKS2XTIN-11
34.5 max.
Models for AC Loads
0.8
0.5
Models with Test Button
MKS1TI-10
MKS2TI-11
Models with Test Button and Built-in
Operation Indicators
44 max.
29.7
MKS1TIN-10
MKS2TIN-11
7.3
Terminal Arrangement/Internal Connection
(Bottom View)
MKS1XT-10
MKS1XTI-10
MKS1XTN-10
MKS1XTIN-10
MKS2XT-11
MKS2XTI-11
MKS2XTN-11
MKS2XTIN-11
DC specification
AC specification
DC specification
AC specification
2
2
2
4
6 (
+)
B
4
6 (+)
4
6 (+)
4
6 (+)
B
4
6 (+)
4
6 (+)
B
8
8
8 (+)
8 (+)
8 (+)
8
A
A (+)
B (
−
)
A
B
A
A (+)
B (
−
)
A
MKS1T-10
MKS1TI-10
MKS1TN-10
MKS1TIN-10
MKS2T-11
MKS2TI-11
MKS2TN-11
MKS2TIN-11
DC specification
AC specification
DC specification
AC specification
2
2
2
8
4
6
4
6
4
6
4
6
4
6
4
6
8
8
8
8
8
A (+)
B (
−
)
A (+)
B (
−
)
A
B
A
B
A
B
A
B
Note: 1.
Wire properly using the correct coil polarity.
2.
The contact terminals on Models for DC Loads have polarity. Wire properly using the correct polarity.
7
MK-S(X)
Connecting Socket
Back-connecting Socket
P7M-06P
Terminal Arrangement/Internal Connections
PCB Mounting Holes
Dimensions
(Bottom View)
(Bottom View)
39 max.
2
5.5
4
6
43 max.
39 max.
8.3
7.7
0.9
8
A
B
Six 1.8-dia. hole
21.9
1.55
4.35
22.1
0.5
0.9
7.7
8.3
5.5
Front-connecting Socket
P7MF-06
P7MF-06-D
Terminal Arrangement/Internal Connections
(TOP View)
Mounting Holes
(TOP View)
Dimensions
7
P7MF-±6
P7MF-±6-D
34 max.
T
w
o, M4 or
two 3.5-dia. hole
66±±.3
78 max.
35.5
Note: 1. The internal connections diagram is for the MKS2(X)T
@@
-11.
2. The P7MF-±6-D has polarit
y
.
B
e careful to wire with the
correct polarit
y
.
4
6
39 max.
31±±.2
24.3
Six, M3 x 8
8
MK-S(X)
Accessory (Order Separately)
Connecting Socket
Socket
Back-connecting Socket
PCB terminals
Front-connecting Socket
Number of poles
Mounts to DIN Track or via screws
P7M-06P
P7MF-06
P7MF-06-D
2
Note: 1.
The P7M-06P, P7MF-06, and P7MF-06-D can be used with models for DC loads with an SPST-NO or SPST-NO/SPST-NC contact form
or with models for AC loads with an SPST-NO or SPST-NO/SPST-NC contact form.
2.
The P7MF-06-D has a built-in diode and can thus be used only with Relays with DC operating coils. Do not use it with a Relay with an
AC operating coil.
3.
Refer to
Gang Mounting
on page 10 for the conditions required for gang mounting.
Relay Hold-down Clips
Use the Clips to securely mount the Relay and prevent it from falling due to vibration or shock.
PYC-A2
One Set (Two Clips)
Applicable Relay models
MKS1XT-10
MKS1XTI-10
MKS1XTIN-10
MKS1XTN-10
MKS1T-10
MKS2XT-11
MKS2XTI-11
MKS2XTIN-11
MKS2XTN-11
MKS2T-11
5 max.
Socket
MKS1TI-10
MKS2TI-11
MKS1TIN-10
MKS1TN-10
MKS2TIN-11
MKS2TN-11
42.8
4.5
Back-connecting Socket
Front-connecting Socket
PCB terminals
P7M-06P
P7MF-06
Mounts to DIN
Track or via
screws
PYC-A2
P7MF-06-D
4.5
1.2
Note:
The minimum order for the
PYC-A2 is ten clips.
Socket Mounting Height
P7M-06P
64
61
MK-S(X)
P7MF-06
P7MF-06-D
MK-S(X)
70
75
79
74
9
MK-S(X)
Safety Precautions
Refer also to
Precautions for All Relays
.
Precautions for Correct Use
Installation
•
Models for DC loads (i.e., models with “X” in the model number)
have permanent magnets built into the insulating block. If a
permanent magnet or other magnetic body comes near the Relay,
magnetic interference will occur with the built-in permanent magnet
and the contact switching capacity will be decreased.
•
Models for AC loads do not contain a permanent magnet.
•
When mounting a P7MF-06(-D) Front-mounting Socket to a DIN
Track, attach PFP-M End Plates on both sides of the Socket to
prevent it from moving.
Test Button
•
Turn OFF the power supply before operating the test button.
Always return the test button to the original position after you use it.
•
Do not use the test button as a switch.
•
The durability of the test button is 100 operations minimum.
Operating Environment
Do not use the Relay in environments with combustible gas. Doing so
may result in explosion due to arcing.
Storage
Gang Mounting
Models for DC Loads (i.e., models with “X” in the model number) are
magnetized because they have a built-in magnet to deflect and
extinguish the arc. Do not install the Relay near IC cards or other
items that may be adversely affected by magnetism.
Conditions for Gang Mounting Relays
Socket
Rate
d
c
urrent
of Relay
Back-Connecting
Socket
Front-Connecting
Socket
Relay
Usage
Model
s
f
or
DC Loads
10A
15A
❍
❍
❍
Use the Relay mounted in the P7M-06P or P7MF-06(-D) Socket.
Model
s
f
or
AC Loads
*
*
Gang mounting of the Front-Mounting Sockets is not possible if the
contact carry current exceeds 10A.Provide space on both the right
and left sides of the Sockets.
The mounting pitch is given in the following diagram.
20
15
10
5
0
0
10
20
30
40
50
Mounting interval (mm)
Mounting interval
Wiring
•
The contact terminals on Models for DC Loads (i.e., models with
“X” in the model number) have polarity. Wiring with incorrect
polarity may result in inability to turn OFF the Relay or loss of
functionality.
•
Wire models with built-in operation indicators with the correct coil
polarity (DC operating coil).
10
MK-S(X)
Warranty and Application Considerations
Read and Understand this Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or
other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESEN
T
A
T
ION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMEN
T
,
MERCHAN
T
A
BILIT
Y
,
O
R FITNESS FOR
P
A
RTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES TH
A
T
T
HE BUYER OR USER ALONE HAS DETERMINED TH
A
T
T
HE PRODUCTS WILL SUI
T
A
B
L
Y
M
EET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIREC
T
,
O
R CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY W
A
Y
C
ONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRAC
T
, WARRANT
Y
,
N
EGLIGENCE, OR STRICT LIABILIT
Y
.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANT
Y
,
R
E
P
A
IR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON’S ANA
L
Y
SIS CONFIRMS TH
A
T
T
HE PRODUCTS WERE PROPER
L
Y
H
ANDLED, STORED,
INS
T
A
LLED, AND MAIN
T
A
INED AND NOT SUBJECT TO CON
T
A
MIN
A
T
ION, ABUSE, MISUSE, OR INAPPROPRI
A
T
E
MODIFIC
A
T
ION OR RE
P
A
IR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer’s application or use of the products.
T
a
ke all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLIC
A
T
ION INVO
L
V
ING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING TH
A
T
T
HE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND TH
A
T
T
HE OMRON
PRODUCTS ARE PROPER
L
Y
R
A
T
ED AND INS
T
A
LLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warrant
y
.
I
t may represent the result of OMRON’s test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liabilit
y
.
CHANGE IN SPECIFIC
A
T
IONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
11
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
OMRON Corporation
Authorized Distributor:
Industrial Automation Company
T
e
l: (1) 847-843-7900/Fax: (1) 847-843-7787
Control Devices Division H.Q.
Strategy Planning Division
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
T
e
l: (81) 75-344-7109/Fax: (81) 75-344-7149
OMRON ASIA
P
ACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra
T
e
chnopark, Singapore 119967
T
e
l: (65) 6835-3011/Fax: (65) 6835-2711
Regional Headquarters
OMRON EUROPE B.
V
.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
T
e
l: (31)2356-81-300/Fax: (31)2356-81-388
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China
T
o
wer,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
T
e
l: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2008-2020
All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
CSM_5_3
Cat. No. J175-E1-03
Printed in Japan
0520(0809)