Omron-Electronics-MM2XP-AC100

Part #Omron-Electronics-MM2XP-AC100
Download 
Omron-Electronics-MM2XP-AC100
Power Relay  
MM  
CSM_MM_DS_E_5_5  
Stable Contact Reliability and Long Life  
• Easy to mount, wire, and use.  
• A large selection of models including various contact forms,  
DC-switching models, and open models.  
• Mechanical life: 5,000,000 operations; electrical life  
(under rated load): 500,000 operations.  
• Models also available with built-in diodes and for use as  
auxiliary power relays.  
Refer to
Safety Precautions for All Relays
.  
Ordering Information  
Type  
Contact form  
Open structure  
Solder terminals
 
Screw terminals  
Cased  
Plug-in (octal pins)  
terminals  
Standard  
DPDT  
MM2  
MM3  
MM4  
MM2X  
MM3X  
MM4X  
—  
MM2B  
MM3B  
MM4B  
MM2XB  
MM3XB  
MM4XB  
—  
MM2P  
3PDT  
4PDT  
DPDT  
3PDT  
4PDT  
DPDT  
4PDT  
DPDT  
4PDT  
DPDT  
3PDT  
4PDT  
DPDT  
3PDT  
4PDT  
MM3P  
MM4P  
DC-switching  
With built-in diode  
MM2XP  
MM3XP  
MM4XP  
MM2P-D  
MM4P-D  
MM2XP-D  
MM4XP-D  
MM2PN  
MM3PN  
MM4PN  
MM2XPN  
MM3XPN  
MM4XPN  
MM4P-JD  
MM4XP-JD  
—  
—  
DC-switching with built-in diode  
With operation indicator  
—  
—  
—  
—  
—  
—  
—  
—  
—  
—  
DC-switching with operation indicator  
—  
—  
—  
—  
—  
—  
Conforming to auxiliary power relay speci-
 
4PDT  
fications  
—  
—  
—  
—  
■
Available Models  
When your order, specify the rated voltage.  
Open Coils (with Solder Terminals)  
Type  
Contact form  
Relay model  
Available rated voltage  
Standard  
DP  
3P  
4P  
DP  
3P  
4P  
MM2  
MM3  
MM4  
6, 12, 24, 50, 100/(110), 200/(220) VAC  
6, 12, 24, 48, 100/110, 200/220 VDC  
100/(110), 200/(220) VAC  
6, 12, 24, 48, 200/220 VDC  
24, 100/(110), 200/(220) VAC  
6, 12, 24, 48, 100/110, 200/220 VDC  
DC-switching  
MM2X  
MM3X  
MM4X  
100/(110), 200/(220) VAC  
6, 12, 24, 48, 100/110, 200/220 VDC  
100/(110), 200/(220) VAC  
12, 24, 100/110 VDC  
100/(110), 200/(220) VAC  
12, 24, 48, 100/110 VDC  
1

MM  
Open Coils (with Screw Terminals)  
Type  
Contact form  
Relay model  
MM2B  
Available rated voltage  
Standard  
DP  
3P  
4P  
DP  
3P  
4P  
6, 12, 24, 50, 100/(110), 200/(220) VAC  
12, 24, 48, 100/110, 125, 200/220 VDC  
MM3B  
6, 100/(110), 200/(220) VAC  
12, 24, 100/110 VDC  
MM4B  
6, 100/(110), 200/(220) VAC  
12, 24, 48, 100/110 VDC  
DC-switching  
MM2XB  
MM3XB  
MM4XB  
24, 100/(110), 200/(220) VAC  
12, 24, 48, 100/110, 125, 200/220 VDC  
100/(110), 200/(220) VAC  
12, 24, 48, 100/110, 125, 200/220 VDC  
12, 24, 100/(110), 200/(220) VAC  
6, 12, 24, 48, 100/110, 200/220 VDC  
Cased Coils (Plug-in Terminals)  
Type  
Contact form  
Relay model  
Available rated voltage  
Standard  
DP  
3P  
4P  
DP  
3P  
4P  
DP  
DP  
DP  
3P  
4P  
DP  
3P  
4P  
4P  
4P  
MM2P  
6, 12, 24, 50, 100/(110), 200/(220) VAC  
6, 12, 24, 48, 100/110, 125, 200/220 VDC  
MM3P  
6, 24, 100/(110), 200/(220) VAC  
6, 12, 24, 48, 100/110, 125, 200/220 VDC  
MM4P  
6, 24, 50, 100/(110), 200/(220) VAC  
12, 24, 48, 100/110, 125, 200/220 VDC  
DC-switching  
With built-in diode  
MM2XP  
MM3XP  
MM4XP  
6, 24, 100/(110), 125, 200/(220) VAC  
6, 12, 24, 48, 100/110, 125, 200/220 VDC  
24, 50, 100/(110), 200/(220) VAC  
12, 24, 48, 100/110, 125, 200/220 VDC  
12, 24, 50, 100/(110), 200/(220) VAC  
6, 12, 24, 48, 100/110, 125, 200/220 VDC  
MM2P-D  
MM4P-D  
12, 24, 48, 100/110, 200/220 VDC  
12, 24, 48, 100/110, 125, 200/220 VDC  
DC-switching with built-in diode  
With operation indicator  
MM2XP-D  
MM4XP-D  
12, 24, 48, 100/110, 125, 200/220 VDC  
12, 24, 48, 100/110, 125, 200/220 VDC  
MM2PN  
6, 24, 100/(110), 200/(220) VAC  
6, 12, 24, 48, 100/110, 125, 200/220 VDC  
MM3PN  
100/(110), 200/(220) VAC  
6, 12, 24, 48, 100/110, 200/220 VDC  
MM4PN  
24, 100/(110), 200/(220) VAC  
24, 48, 100/110, 125, 200/220 VDC  
DC-switching with operation indicator  
MM2XPN  
MM3XPN  
MM4XPN  
MM4P-JD  
MM4XP-JD  
100/(110), 200/(220) VAC  
12, 24, 48, 100/110, 125, 200/220 VDC  
100/(110), 200/(220) VAC  
24, 48, 100/110, 200/220 VDC  
100/(110), 200/(220) VAC  
12, 24, 48, 100/110, 125, 200/220 VDC  
Conforming to auxiliary power relay  
specifications  
100/(110), 110, 115, 200/(220), 220 VAC  
24, 100/110, 125, 200/220 VDC  
Conforming to auxiliary power relay  
specifications for DC-switching  
100/(110), 110, 115, 200/(220) VAC  
24, 48, 100/110, 125, 200/220 VDC  
Models Conforming to Auxiliary Power Relay Specifications  
The MM4P-JD and MM4XP-JD satisfy the ratings of auxiliary relays provided in JEC-2500 (1987) standards for power protective relays specified  
by the Japan Electromechanical Commission. Furthermore, the MM4P-JD and MM4XP-JD satisfy the ratings of multi-contact relays provided in  
JEC-174D (1979) standards for power auxiliary relays.  
These models work at operation level B specified by JEC-174D (1979) standards and the hot start of the relays is possible after the coils radiate  
heat.  
In accordance with JEC-2500 (1987) standards, the coil of each model withstands a 130% DC load or 115% AC load.  
Note:
1.
W
hen ordering, add the rated coil
v
oltage to the model n
u
m
b
er. Rated coil
v
oltages are gi
v
en in the coil ratings ta
b
le.  
Example: MM2, 6
V
AC  
Rated coil
v
oltage  
2. Latching
 
Relays
b
ased on the MM Series are also a
v
aila
b
le. Refer to the MMK.  
3. Models
 
w
ith
bu
ilt-in
v
aristors (AC operation) are also a
v
aila
b
le in addition to those
w
ith
bu
ilt-in diodes. Ask yo
u
r OMRO
N
repre-  
sentati
v
e for details.  
4. Models
 
w
ith
bu
ilt-in diodes are also a
v
aila
b
le for the MM
□
XP
N
Series.  
Ask yo
u
r OMRO
N
representati
v
e for rated
v
oltages and other information.  
2

MM  
Model Number Legend  
MM
@@@@
–
@  
1
2
3
4
5
1. Contact
 
Form  
4. Operation
 
Indicator  
2:  
3:  
4:  
DPDT  
3PDT  
4PDT  
None: Not
 
provided  
N:  
5. Built-in
 
Diode  
None: Not
 
provided  
D: Provided  
Provided  
2. Type
 
(See Note.)  
None: Standard  
X:  
DC-switching  
Note:
The suffix “JD” indicates models conforming to auxiliary power  
3. Terminal
 
Shape  
None: Solder  
relay specifications.  
B:  
P:  
Screw  
Plug-in  
■
Accessories (Order Separately)  
Mounting Brackets  
Mounting Bracket (S bracket)
 
R99-03MM  
Sockets  
Relay model  
DIN Track/Front-connecting Socket  
(screw terminals)  
Back-connecting Socket  
(solder terminals)  
MM2(X)P(N)(-D)  
MM3P(N)  
8PFA  
PL08  
11PFA  
PL11  
MM3XP(N), MM4(X)P(N)(-D)  
MM4(X)P-JD  
14PFA  
14PFA  
PL15  
—  
3

MM  
Specifications  
■
Coil Ratings  
Open Coils (with Solder or Screw Terminals)  
Rated voltage  
(V)  
Rated current (mA)  
DP 3P
 
or 4P  
50 Hz
 
60 Hz  
Coil resistance (
Ω
)  
Must-  
operate release  
voltage voltage  
Must-  
Max.  
Powe
r
c
onsumption  
(VA or W)  
voltage  
DP  
3P or 4P  
50 Hz  
790  
60 Hz  
655  
% of rated voltage  
Initial  
Rated  
AC  
6
1,120  
560  
280  
134  
67  
950  
1.1  
4.7  
19  
0.5  
80% max.
 
30% min.
 
110%  
Approx.  
Approx.  
(60 Hz)  
25% min.  
(50 Hz)  
4.1 (DP)
 
3.5 (DP)  
Approx. Approx.  
6.3 (3P or
 
5.1 (3P or  
4P) 4P)  
12  
24  
50  
395  
195  
94  
325  
160  
78  
480  
2.0  
240  
8.5  
114  
82  
36  
100/(110) 47  
39/45  
57/66  
28.5/33  
340  
150  
620  
13.4  
54  
200/(220) 23.5  
19.5/ 22.5
 
33.5  
1,540  
17.5  
68  
DC  
6
340  
450  
220  
94  
70% max.
 
10% min.  
Approx. 2.1 (DP)  
Approx. 2.7 (3P or  
4P)  
12  
176  
24  
87  
275  
255  
930  
4,500  
18,000  
48  
41  
52  
1,180  
5,750  
23,200  
100/110  
200/220  
17/19  
8.6/9.5  
22/24.5  
11/12  
Note: 1.
 
The rated current and coil resistance are measured at a coil temperature of 23
°
C with tolerances of +15%/–20% for AC rated current and  
15% for DC coil resistance.  
2.
The AC coil resistance values are reference values.  
3.
Performance characteristic data are measured at a coil temperature of 23
°
C.  
4.
The maximum voltage is one that is applicable instantaneously to the Relay coil at an ambient temperature of 23
°
C and not continuousl
y
.  
Cased Coils (Plug-in Terminals)  
The rated current may vary if the Relay has a built-in operating indicator (See note 4.).  
Rated voltage  
(V)  
Rated current (mA)  
Coil resistance  
Coil inductance (H)  
Must- Must-  
Max.  
Power  
(
Ω
)  
operate release voltage
 
consumption  
voltage voltage  
(VA or W)  
DP  
3P or 4P  
DP  
3P or  
4P  
DP 3P
 
or 4P  
Contact Contact Contact Contact  
release operate release operate  
50 Hz
 
60 Hz
 
50 Hz
 
60 Hz  
% of rated voltage  
Initial Rated  
AC  
DC  
6
690  
345  
170  
82  
590  
295  
145  
70  
975  
490  
245  
117  
850  
430  
210  
102  
1.1  
0.5  
0.02 0.02  
0.07 0.01  
0.28 0.41  
0.01 0.03  
0.04 0.07  
0.18 0.28  
0.75 1.2  
80%  
max.  
30%  
min.  
(60 Hz)  
25%  
min.  
110% Ap-  
Ap-  
prox.  
3.5  
(DP)  
Ap-  
prox.  
4.1  
(DP)  
Ap-  
prox.  
12  
24  
50  
4.7  
19  
82  
2.0  
8.5  
36  
1.2  
4.8  
20  
1.7  
(50 Hz)  
prox.  
100/(110) 41  
35/40 58.5  
51/58 340  
150  
6.7  
3
4.5  
19  
6.3 (3P
 
5.1 (3P  
or 4P)
 
or 4P)  
200/(220) 20.5  
17.5/ 29  
20  
25.5/ 1,540 620  
29  
25.6  
12  
6
340  
176  
87  
450  
220  
94  
17.5  
68  
13.4  
54  
0.2  
0.36  
0.23 0.35  
0.87 1.4  
70%  
max.  
10%  
min.  
Approx. 2.1 (DP)  
Approx. 2.7 (3P  
or 4P)  
12  
24  
48  
0.74 1.0  
4.2 5.8  
20.4 26  
5,750 4,500 81.6 92.5  
23,200 18,000 340
 
380  
275  
255  
5.6  
9.2  
41  
52  
1,180 930  
27.3 45.5  
61.4 96.5  
100/110 17/19  
200/220 8.6/9.5  
22/24.5  
11/12  
158  
250  
Note: 1.
 
The rated current and coil resistance are measured at a coil temperature of 23
°
C with tolerances of +15%/–20% for AC rated current and  
15% for DC coil resistance.  
2.
The AC coil resistance and coil inductance values are for reference onl
y
.  
3.
Performance characteristic data are measured at a coil temperature of 23
°
C.  
4.
The maximum voltage is one that is applicable instantaneously to the Relay coil at an ambient temperature of 23
°
C and not continuousl
y
.  
5.
The rated current of a model with a built-in LED indicator at 6, 12, 24, or 50 VAC or 6, 12, 24, or 48 VDC increases by approx. 10 mA due  
to the current consumption of the LED. The rated current of a model with a built-in neon lamp indicator at 100/(110) or 200/(220) VAC or  
100/110 or 200/220 VDC increases by approx. 0.2 mA due to the current consumption of the neon lamp.  
4

MM  
Coils (Conforming to Auxiliary Power Relay Specifications)  
Rated voltage  
(V)  
Rated current (mA)  
Coil  
resis-  
Coil inductance (H)  
Must-  
operate release  
voltage voltage  
Must-  
Max.  
Opera- Powe
r
c
onsumption  
voltage tion
 
level  
(JEC-  
(VA or W)  
tance (
Ω
)  
174D)  
50 Hz  
60 Hz  
210  
Contact Contact  
% of rated voltage  
Initial  
Rated  
release  
0.18  
operate  
0.28  
AC 24  
50  
245  
117  
8.5  
80% max.
 
30% min.
 
110%  
B
Approx.  
Approx.  
5.1  
(60 Hz)  
25% min.  
(50 Hz)  
Hot start
 
6.3  
after coil  
102  
51/58  
46  
36  
0.75  
3
1.2  
4.5  
5.5  
6.2  
19  
100/(110) 58.5  
150  
heated  
110  
115  
53  
51  
182  
3.6  
4
44  
210  
200/(220) 29  
220 26.5  
DC 24  
25.5/29  
23  
620  
12  
780  
15  
21  
94  
255  
5.6  
27.3  
61.4  
90  
9.2  
45.5  
96.5  
130  
250  
70% max.
 
10% min.  
Approx. 2.7  
48  
52  
930  
100/110  
125  
22/24.5  
22  
4,500  
5,800  
18,000  
200/220  
11/12  
158  
Note: 1.
The rated current and coil resistance are measured at a coil temperature of 23
°
C with tolerances of +15%/–20% for AC rated current and
 
15% for DC coil  
resistance.  
2.
The AC coil resistance and coil inductance values are for reference onl
y
.  
3.
Performance characteristic data are measured at a coil temperature of 23
°
C.  
4.
The maximum voltage is one that is applicable instantaneously to the Relay coil at 23
°
C and not continuousl
y
.  
■
Contact Ratings  
Standard Relays  
Item  
Open Relays  
Cased Relays  
MM2(B), MM3(B), MM4(B)  
MM2P(N, -D), MM3P(N), MM4P(N, -D)  
Resistive load  
(cos
φ
= 1)  
Inductive load  
(cos
φ
=0.4, L/R=7 ms)  
Resistive load  
(cos
φ
= 1)  
Inductive load  
(cos
φ
=0.4, L/R=7 ms)  
Contact type  
Single  
Ag  
Contact material  
Rated load  
15 A at 220 VAC  
10 A at 24 VDC  
7.5 A at 220 VAC  
5 A at 24 VDC  
Rated carry current  
15 A  
7.5 A  
Max. switching voltage  
Max. switching current  
250 VAC, 250 VDC  
15 A  
250 VAC, 250 VDC  
7.5 A  
Max. switching power  
(reference value)  
3,300 VA at 240 W  
1,700 VA at 120 W  
Minimum permissible load  
(reference value) (See note.)  
5 VDC
 
10 mA  
Note:
This value is measured at 60 operations/min.  
DC-switching Relays/Built-in Diode Relays  
Item  
Open Relays  
Cased Relays  
MM2XP(-D), MM3X
P
,
M
M4XP(-D)  
Resistive load
 
Inductive load  
(cos
φ
= 1)
 
(L/R=7 ms)  
MM2X(B), MM3X(B), MM4X(B)  
Resistive load  
(cos
φ
= 1)  
Inductive load  
(L/R=7 ms)  
Contact type  
Single  
Ag  
Contact material  
Rated load  
10 A at 110 VDC  
15 A  
7 A at 110 VDC  
7 A at 110 VDC  
6 A at 110 VDC  
Rated carry current  
Max. switching voltage  
Max. switching current  
7.5 A  
250 VAC, 250 VDC  
15 A  
250 VAC, 250 VDC  
7.5 A  
Max. switching power  
(reference value)  
1,200 W at 20 VA
*1  
800 W at 20 VA
*1  
800 W at 20 VA
*1  
660 W at 20 VA
*1  
Minimum permissible load  
5 VDC at 10 mA  
(reference value)
 
*2  
Note: 1.
When switching DC inductive loads at 125 V or more, an unstable region exists for a contact current of between 0.5 and 2.5 A. The Relay will not turn OFF  
in this region. Use a contact current of 0.5 A or less when switching 125 VDC or more.  
2.
If L/R exceeds 7 ms when switching DC inductive loads, an arc-breaking time of up to 50 ms must be considered in application and the circuit must be designed  
to ensure that an arc-breaking time of 50 ms is not exceeded.  
3.
The switching capacity for an AC load is minute.  
*1.
Refer to
Switching an AC Load with a DC-switching Model (“X” Model)
on page 16.  
*2.
This value is measured at 60 operations/min.  
5

MM  
Contacts (Conforming to Auxiliary Power Relay Specifications)  
Item  
MM4P-JD  
MM4XP-JD  
Resistive load  
Inductive load  
(cos
φ
= 0.4, L/R = 7 ms)  
Resistive load  
Inductive load  
(cos
φ
= 0.4, L/R = 7 ms)  
Contact type  
Single  
Ag  
Contact material  
Rated load  
5 A at 220 VAC, 5 A at 24 VDC  
5 A  
5 A at 110 VDC  
Rated carry current  
Max. switching voltage
 
250 VAC, 250 VDC  
Max. switching current
 
5 A  
Max. switching power  
(reference value)  
1,100 VA, 120 W, 30 W (L/R = 40 ms)  
20 VA, 550 W, 40 W (L/R = 40 ms)  
Note: 1.
 
A model for DC loads is not in stable operation when switching an inductive load within a operating current range between 0.5 and 2.5 A  
at a minimum of 125 VDC, where the load cannot be switched.  
2.
If L/R exceeds 7 ms when switching DC inductive loads, an arc-breaking time of up to 50 ms must be considered in application and the  
circuit must be designed to ensure that an arc-breaking time of 50 ms is not exceeded.  
■
Characteristics  
Standard Relays  
Item  
Open Relays  
Cased Relays  
Contact resistance (See note 2.)  
Operate time (See note 3.)  
Release time (See note 3.)  
Max. operating frequency  
25 m
Ω
max.  
AC: 25 ms max. DC: 50 ms max.  
50 m
Ω
max.  
30 ms max. (100 ms max. for Built-in Diode Relays)  
Mechanical:7,200 operations/hr  
Electrical:1,800 operations/hr (under rated load)  
Insulation resistance (See note 4.)  
Dielectric strength  
100 M
Ω
min. (at 500 VDC)  
1,500 VAC, 50/60 Hz for 1 min between contacts of same polarity  
2,000 VAC, 50/60 Hz for 1 min between contacts of different polarity (and between coil and contacts)  
Vibration resistance  
Shock resistance  
Destruction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)  
Malfunction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)  
Destruction: 1,000 m/s

2  

Malfunction: 100 m/s

2  

Endurance  
Mechanical: 5,000,000 operations min. (at 7,200 operations/hr)  
Electrical: 500,000
 
operations min. (at 1,800 operations/hr under rated load) (See note 5.)  
Ambient temperature  
Ambient humidity  
Weight  
Operating:–10
°
C to 55
°
C (with no icing or condensation)  
Operating:5% to 85%  
Standard models: DC-switching models  
MM2 approx. 160 g  
MM3 approx. 270 g  
MM4 approx. 300 g  
MM2P approx. 220 g  
MM3P approx. 360 g  
MM4P approx. 410 g  
MM2X approx. 165 g
 
MM2XP approx. 225 g  
MM3X approx. 275 g
 
MM3XP approx. 395 g  
MM4X approx. 310 g
 
MM4XP approx. 420 g  
Note: 1.
 
The data shown above are initial values.  
2.
The contact resistance was measured with 1 A at 5 VDC using the voltage drop method.  
3.
The operate or release time was measured with the rated voltage imposed with any contact bounce ignored at an ambient temperature  
of 23
°
C.  
4.
The insulation resistance was measured with a 500-VDC megger applied to the same places as those used for checking the dielectric  
strength.  
5.
The electrical endurance was measured at an ambient temperature of 23
°
C.  
6

MM  
Relays (Conforming to Auxiliary Power Relay Specifications)  
Item  
Cased Relays  
Contact resistance (See note 2.)  
Operate time (See note 3.)  
Release time (See note 3.)  
Max. operating frequency  
50 m
Ω
max.  
AC: 25 ms max., DC: 50 ms max.  
30 ms max.  
Mechanical: 1,800
 
operations/hr  
Electrical:  
1,800 operations/hr (under rated load)  
Insulation resistance (See note 4.)  
Dielectric strength  
100 M
Ω
min.  
Between coil and contact:  
Between contacts of different polarity: 2,000 VAC, 50/60 Hz for 1 minute  
Between contacts of same polarity:
 
1,500 VAC, 50/60 Hz for 1 minute  
2,000 VAC, 50/60 Hz for 1 minute  
Vibration resistance  
Shock resistance  
Destruction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)  
Malfunction: 10 to 22 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)  
Destruction: 300 m/s

2  

Malfunction: 30 m/s

2  

Endurance  
Mechanical: 5,000,000 operations min. (at 1,800 operations/hr)  
Electrical: 500,000
 
operations min. (at 1,800 operations/hr with rated load) (see note 5)  
Error rate (level P)  
(Reference value)  
(See note 6.)  
10 mA at 5 VDC  
Ambient temperature  
Ambient humidity  
Weight  
Operating: –10
°
C to 40
°
C (with no icing or condensation)  
Operating: 5% to 85%  
MM4P-JD: approx.
 
410 g  
MM4XP-JD: approx. 420 g  
Note: 1.
 
The data shown above are initial values.  
2.
The contact resistance was measured with 1 A at 5 VDC using the voltage drop method.  
3.
The operate or release time was measured with the rated voltage imposed with any contact bounce ignored at an ambient temperature  
of 23
°
C.  
4.
The insulation resistance was measured with a 500-VDC megger applied to the same places as those used for checking the dielectric  
strength.  
5.
The electrical endurance was measured at an ambient temperature of 23
°
C.  
6.
This value was measured at a switching frequency of 60 operations per minute.  
Engineering Data  
■
Standard Relays  
Maximum Switchin
g
Power  
Open Relays  
Cased Relays  
MM
@
(B)  
MM
@
P(N, -D)  
AC resisti
v
e load  
AC resisti
v
e load  
AC ind
u
cti
v
e  
load  
(cos
φ
= 0.4)  
AC ind
u
cti
v
e  
load  
(cos
φ
= 0.4)  
DC resisti
v
e load  
DC ind
u
cti
v
e  
load L/R = 7 ms  
DC ind
u
cti
v
e  
load L/R = 7 ms  
DC resisti
v
e load  
S
w
itching
v
oltage (
V
)  
S
w
itching
v
oltage (
V
)  
7

MM  
Endurance Curves  
Open Relays  
Cased Relays  
MM
@
(B)  
MM
@
P(N, -D)  
10,000  
7,000  
10,000  
7,000  
5,000  
5,000  
220
V
AC  
resisti
v
e load  
ind
u
cti
v
e load  
(cos
φ
= 0.4)  
220
V
AC  
3,000  
3,000  
resisti
v
e load  
ind
u
cti
v
e load  
(cos
φ
= 0.4)  
1,000  
1,000  
24
V
DC  
24
V
DC  
resisti
v
e load  
700  
500  
700  
500  
resisti
v
e load  
ind
u
cti
v
e load  
L/R = 7 ms  
ind
u
cti
v
e load  
L/R = 7 ms  
300  
300  
100  
100  
S
w
itching c
u
rrent (A)  
S
w
itching c
u
rrent (A)  
■
DC-switching Relays  
Maximum Switchin
g
Power  
Open Relays  
Cased Relays  
MM
@
X(B)  
MM
@
XP(N, -D)  
DC resisti
v
e load  
DC resisti
v
e load  
DC ind
u
cti
v
e load  
L/R = 7 ms  
DC ind
u
cti
v
e load  
L/R = 7 ms  
S
w
itching
v
oltage (
V
)  
S
w
itching
v
oltage (
V
)  
Endurance Curves  
Open Relays  
Cased Relays  
10,000  
10,000  
5,000  
5,000  
3,000  
3,000  
1,000  
24
V
DC resisti
v
e load  
110
V
DC resisti
v
e load  
24
V
DC resisti
v
e load  
110
V
DC resisti
v
e load  
1,000  
500  
300  
500  
300  
110
V
DC ind
u
cti
v
e load  
L/R = 7 ms  
110
V
DC ind
u
cti
v
e load  
L/R = 7 ms  
100  
100  
50  
30  
50  
30  
10  
10  
S
w
itching c
u
rrent (A)  
S
w
itching c
u
rrent (A)  
8

MM  
■
Relays Conforming to Auxiliary Power Relay Specifications  
Maximum Switchin
g
Power  
MM4P-JD  
MM4XP-JD  
AC resisti
v
e load  
AC ind
u
cti
v
e load  
cos
φ
= 0.4  
DC resisti
v
e load  
DC ind
u
cti
v
e load  
L/R = 7 ms  
DC resisti
v
e load  
DC ind
u
cti
v
e load  
L/R = 7 ms  
S
w
itching
v
oltage (
V
)  
S
w
itching
v
oltage (
V
)  
Endurance Curves  
MM4P-JD  
MM4XP-JD  
110
V
DC: resisti
v
e load  
ind
u
cti
v
e load  
220
V
AC: resisti
v
e load  
ind
u
cti
v
e load  
L/R = 7 ms  
cos
φ
= 0.4  
24
V
DC resisti
v
e load  
Ind
u
cti
v
e load  
L/R = 7 ms  
S
w
itching c
u
rrent (A)  
S
w
itching c
u
rrent (A)  
9

MM  
Ambient Temperature vs. Must-operate  
and Must-release Volta
g
e  
MM2P AC (60 Hz)  
MM2P DC  
Nu
m
b
er of Relays: 5  
M
u
st-operate
v
oltage  
M
u
st-release
v
oltage  
Nu
m
b
er of Relays: 5  
M
u
st-operate
v
oltage  
M
u
st-release
v
oltage  
Am
b
ient temperat
u
re (
°
C)  
Am
b
ient temperat
u
re (
°
C)  
Ambient Temperature vs.  
Coil Temperature Rise  
MM2P 110 VAC (60 Hz)  
MM2P DC  
Contact carry c
u
rrent  
Contact carry c
u
rrent  
Nu
m
b
er of Relays: 5  
Nu
m
b
er of Relays: 5  
Am
b
ient temperat
u
re (
°
C)  
Am
b
ient temperat
u
re (
°
C)  
Contact Reliability  
(Improved Allen-Bradley Test Circuit)  
Malfunctionin
g
Shock  
MM2P AC  
MM4P 24 VDC  
Contact load: 10 mA at 5
V
DC  
(resisti
v
e load)  
Contact load: 1 mA at  
5
V
DC (resisti
v
e load)  
Error rate l = 0.2794  
x 10

−
6

/operations  
(le
v
el
N
)  
Error rate l = 0.0202 x  
10

−
6

/operations (le
v
el Q)  
N
O contact  
N
C contact  
Unit: m/s

2  

Nu
m
b
er of samples: 5  
Shock direction  
Meas
u
rement conditions:  
Impose a shock of 100 m/s

2

in  
the X,
Y
,
 
a
nd Z
 
directions  
three times each
w
ith the  
Relay energized and not  
energized to check the shock  
v
al
u
es that ca
u
se the Relay  
to malf
u
nction.  
Nu
m
b
er of s
w
itching  
Nu
m
b
er of s
w
itching  
operations (x 10

4

times)  
operations (x 10

4

times)  
10  

MM  
Relay Mountin
g
Adjacent Distance vs.  
Coil Temperature Rise  
MM4P 100 /(110) VAC  
Relay  
mo
u
nting  
position  
Upper  
Condition: The sat
u
rated  
coil temperat
u
re is  
meas
u
red
w
ith the rated  
carry c
u
rrent (7.5 A) at  
the rated coil
v
oltage  
(100
V
AC at 50 Hz).  
Lo
w
er  
A
v
erage of
N
o. 2, 4, 6, and
8  
A
v
erage of
N
o. 1, 3, 7, and 9  
Contact carry c
u
rrent (7.5 A)  
N
o contact carry c
u
rrent  
A
v
erage of
N
o. 2, 4, 6, and
8  
A
v
erage of
N
o. 1, 3, 7, and 9  
Mo
u
nting adjacent distance
l
(mm)  
Dimensions  
Note:
All units are in millimeters unless otherwise indicated.  
■
Standard Relays  
Open Relays  
Solder Terminals  
MM2(X), MM4(X), MM3(X)  
MM2(X)  
MM3(X)  
MM4(X)  
Side View  
2P  
1P  
3P 2P 1P  
4P 3P 2P  
1P  
Common C  
Stationary A  
Stationary B  
53.5  
max.  
61.5  
max.  
61.5  
max.  
13  
22  
51 max.  
Fo
u
r, M4  
mo
u
nting  
scre
w  
22  
40 max.  
2
8  
50 max.  
34  
Fo
u
r, M4  
mo
u
nting  
scre
w  
Fo
u
r, M4  
mo
u
nting  
scre
w  
63 max.  
holes  
MM2  
holes  
holes  
Note:
Connect the common (C) of MM
@
X to positi
v
e (+).  
Screw Terminals  
MM2(X)B, MM3(X)B,  
MM4(X)B  
MM2(X)B  
MM3(X)B  
MM4(X)B  
Fo
u
rteen, M3.5  
x 5.5 scre
w
s  
4P 3P
 
2P 1P  
Side View  
Eight, M3.5 x 5.5  
scre
w
s  
Ele
v
en, M3.5 x  
5.5 scre
w
s  
Common C  
2P 1P  
Stationary A  
Stationary B  
3P 2P 1P  
59.5 max.  
67.5 max.  
67.5 max.  
1
8
.5  
22  
22  
Fo
u
r, M4  
mo
u
nting  
scre
w  
55 max.  
56 max.  
2
8  
34  
MM2B  
Fo
u
r, M4  
mo
u
nting  
scre
w  
Fo
u
r, M4  
mo
u
nting  
scre
w  
holes  
67 max.  
60 max.  
holes  
holes  
Note:
Connect the common (C) of MM
@
XB to positi
v
e (+).  
11  

MM  
Mountin
g
Holes  
(Bottom View)  
Direct mo
u
nting  
Fo
u
r, 4.5-dia. mo
u
nting holes  
Length of
l
 
22 0.2  
DPDT: 22
 
0.2  
3PDT: 2
8
0.2  
4PDT: 34
 
0.2  
Mountin
g
Bracket (S Bracket)  
R99-03 (S KANAGU) FOR MM
@  
H
R99-03 (S KA
N
AGU) R99-03
 
(S KA
N
AGU)  
The S Bracket can
b
e  
u
sed to mo
u
nt a Relay  
w
ith open solder or scre
w  
terminals.  
W
FOR MM2 (611)  
FOR MM3. 4 (61)  
(DPDT)  
3PD
T
,
4
PDT  
l
22  
2
8
, 34  
22  
0.2  
5
8  
0.2  
44  
D
W
H
71 max.  
36 max.  
6 max.  
71 max.  
46 max.  
6 max.  
22 0.2  
l
12  

MM  
Cased Relays  
Case-protection  
plate  
Plu
g
-in Terminals  
8
0.5  
max.  
MM2P(N, -D)  
MM2XP(N, -D)  
59.5  
max.  
7
3.5  
24  
47.5 max.  
73 max.  
MM2P  
Note:
As sho
w
n in the diagram, there are three 10-dia. holes in the side of the case for the MM2XP(
N
, -D).  
W
hen a case-protection plate is attached, the
w
idth of the Relay
w
ill
b
e 4
8
mm max.  
Terminal Arrangement (Bottom View)  
Make sure that all common connections have the same polarity for the MM2XP-N/-D. The  
markings of the common connections on the casing all show “+” but the polarity of the  
common connections can be either negative or positive as long as they are all the same.  
l
MM2P  
MM2P-D  
MM2PN  
MM2PN  
MM2PN  
6, 12, 24, 50
V
AC  
6, 12, 24, 4
8 V
DC  
100/(110), 200/(220)
V
AC  
100/110, 200/220
V
DC  
MM2XP  
MM2XP-D  
MM2XPN  
MM2XPN  
MM2XPN  
6, 12, 24, 50
V
AC  
6, 12, 24, 4
8 V
DC  
100/(110), 200/(220)
V
AC  
100/110, 200/220
V
DC  
Note:
Wire the terminals correctly with no mistakes in coil polarit
y
.  
MM3P(N)  
8
0.5  
max.  
59.5  
max.  
3.5  
7
8
1 max.  
24  
61.5 max.  
MM3P  
Terminal Arrangement (Bottom View)  
MM3P  
MM3PN  
MM3PN  
6, 12, 24, 4
8 V
DC  
MM3PN  
6, 12, 24, 50
V
AC  
100/(110), 200/(220)
V
AC  
100/110, 200/220
V
DC  
Note:
Wire the terminals correctly with no mistakes in coil polarit
y
.  
13  

MM  
MM3PXP(N)  
MM4P(N, -D)  
MM4XP(N, -D)  
Case-protection  
plate  
8
0.5  
max.  
59.5  
max.  
3.5  
7
8
1.5 max.  
24  
MM4P  
79.5 max.  
(See note 2.)  
Note 1:
As sho
w
n in the diagram, there are three 10-dia. holes in the side of the case for MM
@
XP(
N
, -D).  
2:
W
hen a case-protection plate is attached, the
w
idth of the Relay
w
ill
b
e
8
0 mm max.  
Terminal Arrangement (Bottom View)  
Make sure that all common connections have the same polarity for the MM
@
XP-N/-D. The  
markings of the common connections on the casing all show “+” but the polarity of the  
common connections can be either negative or positive as long as they are all the same.  
MM3XP  
MM3XPN  
MM3XPN  
MM3XPN  
6, 12, 24, 4
8 V
DC  
6, 12, 24, 50
V
AC  
100/(110), 200/(220)
V
AC  
100/110, 200/220
V
DC  
MM4P  
MM4P-D  
MM4PN  
MM4PN  
MM4PN  
6, 12, 24, 50
V
AC  
100/(110), 200/(220)
V
AC  
100/110, 200/220
V
DC  
6, 12, 24, 4
8 V
DC  
MM4XP  
MM4XP-D  
MM4XPN  
MM4XPN  
MM4XPN  
6, 12, 24, 50
V
AC  
6, 12, 24, 4
8 V
DC  
100/(110), 200/(220)
V
AC  
100/110, 200/220
V
DC  
Note:
Wire the terminals correctly with no mistakes in coil polarit
y
.  
14  

MM  
MM4P-JD  
Terminal Arrangement  
(Bottom View)  
70.5 max.  
59.5 max.  
81.5 max.  
79.5 max.  
MM4XP-JD  
70.5 max.  
59.5 max.  
81.5 max.  
Note:
Make sure that all common connections  
are the same in polarit
y
.
T
he markings of  
the common connections on the casing  
all show “+” but the polarity of the com-  
mon connections can be either all nega-  
tive or all positive.  
80 max.  
■
Relays with Operation Indicators  
Dimensions are the same as those for standard Relays except that there are three 10-mm holes in the case as shown below.  
Accessories  
■
Sockets  
Relay model  
DIN Track/Front-connecting Socket  
(screw terminals)  
Back-connecting Socket  
(solder terminals)  
MM2(X)P(N)(-D)  
8PFA  
PL08  
MM3P(N)  
11PFA  
PL11  
MM3XP(N), MM4(X)P(N)(-D)  
MM4(X)P-JD  
14PFA  
14PFA  
PL15  
—  
Note:
When using the MM4(X)P-JD (i.e., a model conforming to auxiliary power relay specifications) by itself, the PL15 Back-connecting Socket  
cannot be used.  
Height with Socket  
DIN Track/Front-connecting Socket  
Back-connecting Socket  
MM3XP  
MM4(X)  
MM3XP  
MM4(X)P  
MM2(X)P  
95.5  
MM3P  
MM2(X)P  
MM3P  
110  
113  
86.5  
92  
109.5 113.5  
86  
78  
MM4(X)P-JD  
8PFA  
11PFA  
14PFA  
PL08  
PL11  
PL15  
15  

MM  
Safety Precautions  
Refer to
Safety Precautions for All Relays
.  
■
Connection  
■
Soldering  
When soldering solder terminals, do not let flux or other foreign mat-  
ter adhere to contacts or do not let the coil terminals become bent.  
Also, solder as quickly as possible because excessive heat may  
damage the coil.  
•
Use proper crimp terminals or 1.2- to 2-mm-dia. single-conductor  
wire to connect screw terminals.  
•
Connect loads to DC-switching Relays so that arcs from adjacent  
terminals will not strike each other. E.g., connect all common termi-  
nals to the same polarit
y
.  
•
Screw
T
e
rminal Model:  
■
Diode Built into Relays  
A diode is built into the Relays to absorb reverse electromotive force  
from the relay coil. The diode will be destroyed if a large external surge  
voltage is applied. If there is a possibility of a large external surge  
voltage being applied, take suitable measures to absorb the surge.  
Do not bend the coil terminals, otherwise the coil wire may be dis-  
connected. Make sure that the tightening torque applied to each  
terminal is 0.78 to 1.18 N·m and the insertion force is 49 N for 10 s.  
•
Do not reverse polarity when connecting open DC-switching  
Relays, including 3- and 4-pole models.  
■
Installation  
■
Storage  
A model for DC loads incorporates a permanent magnetic for arc  
suppression. Keep floppy disks away from the Rela
y
,
o
therwise the  
data on the floppy disk may be damaged.  
•
Do not install the Relays where iron dust can adhere to the contacts  
or coil. Such dust can prevent the armature from moving freely and  
inhibit proper electrical contact.  
•
Relays can generate arcs externall
y
.
E
ither install the Relay in a  
location where a nearby object will not burn or use a covered Rela
y
.  
•
DC-switching Relays contain a permanent magnet in the insulation  
base. Do not place a magnet or magnetic object near this base.  
Doing so will reduce the power of the permanent magnet, thus  
reducing Relay capacit
y
.  
■
Operating Environment  
Do not use the Relay in places with flammable gas, otherwise an  
explosion may result due to an arc generated from the Relay  
•
Insert PL Back-mounting Sockets from the back of the panel.  
■
Switching an AC Load with a  
•
T
o
m
inimize the influence of heat, separate Relays from each other  
by at least 20 mm for cooling when mounting multiple Relays  
together.  
DC-switching Model (“X” Model)  
20 mm  
T
o
p  
DC-switching Relays (“X” models) use a magnet to extinguish arcs.  
The polarity must be correct when you connect the switching section.  
However, if you connect an AC load, the positive and negative poles  
of the power supply alternate. This can cause short-circuits due to  
the collision of arcs that occur when the Relay turns OF
F
.  
Therefore, the switching capacity for an AC load is specified as 20 VA  
or less to prevent short circuits caused by arc collisions.  
T
a
ke sufficient caution if you switch an AC Load with a DC-switching  
model (“X” models).  
min.  
MM  
MM  
Mo
u
nting orientation  
Bottom  
•
Relays should be mounted with the armature facing down.  
■
Wiring  
When connecting a load to the contact terminals of a model for DC  
loads, consider the polarity of the contact terminals so that the gen-  
erated arcs on the adjacent poles will not collide. If the common con-  
nections of the Relay are all positive or all negative, no arc collision  
will occur.  
Common C  
+
-
■
MMXP  
The MMXP has a hole in the Relay case to allow gas to escape. Do  
not use this Relay in locations subject to excessive dust.  
Arc collision  
■
Refer to the technical guide on  
your OMRON website for  
technical descriptions and  
FAQs on the product.  
■
Contact Loads  
The contact load should be greater than the power consumption of  
the coil. If it is less than this power consumption or if the Relay is  
operated very infrequentl
y
,
t
he contact can change chemically thus  
causing unstable operation.  
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.  
To
c
onvert millimeters into inches, multiply by 0.03937.
T
o
c
onvert grams into ounces, multiply by 0.03527.  
In the interest of product improvement, specifications are subject to change without notice.  
16  

T
e
rms and Conditions Agreement  
Read and understand this catalog.  
Please read and understand this catalog before purchasing the products.
 
Please consult your OMRON representative if you  
have any questions or comments.  
Warranties.  
(a) Exclusive Warranty
. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship  
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron  
disclaims all other warranties, express or implied.  
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT  
NON-INFRINGEMEN
T
,
M
ERCHAN
T
A
BILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER  
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE  
PRODUCTS WILL SUI
T
ABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.  
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the  
Products or otherwise of any intellectual property right. (c) Buyer Re
med
y
. Omron’s sole obligation hereunder shall be, at  
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or  
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount  
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,  
repair, indemnity or any other claims or expenses regarding the Products unless Omron
’s analysis confirms that the Products  
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate  
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall  
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or  
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,  
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above  
warranty.  
See

or contact your Omron representative for published information.  
Limitation on Liability; Etc.  
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIREC
T
,
I
NCIDEN
T
A
L, OR CONSEQUENTIAL DAMAGES,  
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,  
WHETHER SUCH CLAIM IS BASED IN CONTRAC
T
,
W
ARRANT
Y
,
N
EGLIGENCE OR STRICT LIABILIT
Y
.  
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.  
Suitability of Use.  
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the  
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicabl
e  
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself  
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,  
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product  
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.  
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE  
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,  
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE  
OVERALL EQUIPMENT OR SYSTEM.  
Programmable Products.  
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence  
thereof.  
Performance Data.  
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining  
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must cor
relate  
it to actual application requirements. Actual performance is subject to the Om
ron’s Warranty and Limitations of Liability.  
Change in Specifications.  
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our  
practice to change part numbers when published ratings or features are changed, or when significant construction changes are  
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers  
may be assigned to fix or establish key specifications for your application.
Please consult with your Omron’s representative at  
any time to confirm actual specifications of purchased Product.  
Errors and Omissions.  
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is  
assumed for clerical, typographical or proofreading errors or omissions.  
2020.5  
In the interest of product improvement, specifications are subject to change without notice.  
OMRON Corporation  
Industrial Automation Company  
(c)Copyright OMRON Corporation 2020 All Right Reserved.