Omron-Electronics-P2CF-08-E

Part #Omron-Electronics-P2CF-08-E
Download 
Omron-Electronics-P2CF-08-E
Temperature Controller  
E5C2  
CSM_E5C2_DS_E_7_2  
DIN-sized (48 x 48 mm) Temperature  
Controller with Analog Setting  
• Compact, low-cost Temperature Controller.  
• Incorporates proportional control and reset adjustment function.  
• Consecutive mounting possible using mounting adapter.  
• Incorporates a plug-in socket, thus allows to DIN-track and flush  
mounting.  
Refer to
Safety Precautions for All Temperature  
Controllers.  
For the most recent information on models that have been certified for  
safety standards, refer to your OMRON website.  
Model Number Structure  
■
Model Number Legend  
E5C2-
@ @ @ @  
1
2
3
4 5  
1. Control
 
Outputs  
R: Relay  
2. Control
 
Method  
3. Input  
Note:
A functional explanation is provided  
here for illustration, but models are  
not necessarily available for all  
K:  
J:  
K-type thermocouple  
J-type thermocouple  
possible combinations. Refer to  
Ordering Information
when ordering.  
Examples  
•
Relay control output, ON/OFF  
control, type-K thermocouple input:  
E5C2-R20K  
20: ON-OFF
 
control  
40: Proportional
 
control  
P-D: Platinum
 
resistance thermometer  
(Pt100)  
G:  
Thermistor with replaceable ele-  
ment  
•
Relay control output, proportional  
control, thermocouple input: E5C2-  
R40P-D  
Ordering Information  
■
Temperature Controllers  
Input  
Thermocouple  
Resistance Thermometer  
Thermistor  
K (CA)  
Chromel vs. alumel  
J (IC)  
Iron vs. constantan  
Platinum resistance  
thermometer Pt100  
Thermistor  
(replaceable element)  
1,200  
Themistor nominal resistance  
6 k
Ω
6 k
Ω
30 k
Ω
550
Ω
4 k
Ω  
(0°C) (0°C) (0°C)
 
(200°C)(200°C)  
1,200  
1,000  
800  
600  
400  
300  
200  
100  
0
1,000  
Standard  
scale  
800  
600  
(°C)  
400  
300  
400  
400  
0
300  
200  
300  
200  
300  
200  
0
150  
50  
200  
100  
50 80 50
 
100  
50  
100  
0
150  
2
0
0
0
0
0
0
0
0
0
0
0
0
0
−
100  
−
50
−
20  
−
50  
Indica-  
Setting tion  
method method
 
mode  
Minimum  
scale division  
(°C)  
Control  
5
10 10 20 20 25 25  
5
10  
10  
2
2
1
2
5
10 10  
2
2
2
2
Output  
Analog No  
ON/OFF Relay Model  
Propor-  
E5C2-R20K  
E5C2-R40K  
E5C2-R20J  
—  
E5C2-R20P-D  
—  
E5C2-R20G  
—  
setting indi-  
—  
cation  
tional  
(P)  
Relay Model  
Note:
When placing an order, specify the temperature range in addition to the model number.  
1

E5C2  
Standard Models  
Indication method  
No indication  
Indication method  
Control mode  
Output  
No indication  
Control mode  
ON/OFF  
Proportional  
(P)  
ON/OFF  
Input  
Relay  
Input  
Output  
0 to 200  
0 to 300  
Relay  
Input/ Resis-
 
Platinum
−
50 to 50  
E5C2-R20P-D  
E5C2-R20P-D  
E5C2-R20P-D  
E5C2-R20P-D  
E5C2-R20P-D  
E5C2-R20P-D  
E5C2-R20P-D  
E5C2-R20G  
E5C2-R20G  
E5C2-R20G  
E5C2-R20G  
E5C2-R20G  
Input/ Thermo- K
 
(CA)  
E5C2-R20K  
E5C2-R20K  
E5C2-R20K  
E5C2-R20K  
E5C2-R20K  
E5C2-R40K  
stan- tance
 
resistance  
−
20 to 80  
stan- couple  
dard  
Chromel  
dard Ther- thermom-  
E5C2-R40K  
vs. alumel  
scale mome-
 
eter Pt100  
0 to 50  
scale  
(°C)  
(°C)  
ter  
0 to 400  
0 to 600  
0 to 800  
E5C2-R40K  
0 to 100  
0 to 200  
0 to 300  
0 to 400  
−
50 to 50  
0 to 100  
50 to 150  
100 to 200  
150 to 300  
E5C2-R40K  
E5C2-R40K  
0 to 1,000
 
E5C2-R20K  
0 to 1,200
 
E5C2-R20K  
—  
—  
—  
—  
—  
Ther- THE
 
(re-  
mistor placeable  
element)  
J (IC)  
Iron vs.  
constantan  
0 to 200  
0 to 300  
0 to 400  
E5C2-R20J  
E5C2-R20J  
E5C2-R20J  
■
Accessories (Order Separately)  
Sockets  
Protective Cover  
Name  
Front Connecting Socket  
Back Connecting Socket  
Front Connecting Socket with Finger Protection
 
P2CF-08-E  
Model  
P2CF-08  
P3G-08  
Type  
Model  
Y92A-48B  
Hard Protective Cover  
Protective Cover (for finger protection)  
Y92A-48G  
Specifications  
■
Ratings  
Supply voltage  
■
Characteristics  
Setting accuracy  
2% FS max. (Influence of EMS :
 
4% FS max.)  
(See note 1.)  
100 to 240 VAC 50/60 Hz  
Operatin
g
v
oltage
90% to 110% of rated supply voltage  
range  
Hysteresis  
Approx. 0.5% FS (fixed)  
3% FS (fixed)  
Proportional band  
Control period  
Reset range  
Power  
consumption  
Approx. 3.6 VA  
Approx. 20 s  
5
1% FS min. (See note 2.)  
Input  
Thermocouple (with sensor burnout detection  
circuit), platinum resistance thermometer, or  
thermistor with replaceable element  
Insulation  
resistance  
20 M
Ω
min. (at 500 VDC)  
Dielectric strength  
2,000 VAC, 50/60 Hz for 1 min between charged termi-  
nals and uncharged metallic parts  
Control method  
Setting method  
ON/OFF or proportional control  
Analog setting  
Vibration  
resistance  
Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for  
10 min each in X, Y, and Z directions  
Indication  
method  
No indication  
Destruction: 16.7 Hz, 2-mm double amplitude for 2 hrs  
each in X, Y, and Z directions  
Malfunction: 147 m/s

2

, 3 times each in 6 directions  
Destruction: 294 m/s

2

, 3 times each in 6 directions  
Control output  
Relay output:
 
SPDT, 3 A at 250 VAC, resistive  
load (switching capacity: 330 VA)  
Shock resistance  
Ambient operat-
 
−
10
°
C to 55
°
C (with no icing or condensation)  
Life expectancy  
Weight  
Electrical: 100,000
 
operations min. (3 A at 110 VAC,  
resistive load)  
ing temperature  
Approx. 100 g (with flush-mounting adapter)  
Ambient operat-
 
45% to 85%  
ing humidity  
Degree of protection
 
Front panel: IEC standard IP40 (See note 3.)  
Terminals: IEC
 
standard IP00  
Applicable Socket  
P2CF-08 (order separately),  
P3G-08 (order separately)  
Note:
Do not use an inverter output as the power supply. (Refer to  
Safety Precautions for All
T
e
mperature Controllers
.)  
Applicable Protec-  
tive Cover  
Y92A-48B (order separately)  
Note: 1.
 
At EN 61326-1 (Industrial electromagnetic environment  
(EN/IEC 61326-1 Table 2))  
2.
No reset function is incorporated by any E5C2 model with  
ON/OFF control.  
The reset function is used to correct offset for proportional  
control. If there is an offset below the set value, turn the  
reset adjustment clockwise.  
3.
A special Watertight Cover is used to achieve this degree of  
protection (IP66, NEMA4). Refer to
Y92A-
@@
N
.  
2

E5C2  
■
Connections  
Connecting the Input  
•
Connect a thermocouple, the E52-THE
@
Thermistor (replaceable  
element) or a platinum resistance thermometer to terminals 1  
(positive) and 2 (negative) on the E5C2 as shown in the following  
illustration.  
Output  
•
If the load circuit is a heating control system, be sure to connect the  
load to terminals 4 and 5. If the load circuit is a cooling control  
system, be sure to connect the load to terminals 4 and 6.  
•
We recommend using an external relay to extend the electrical life  
of internal relays when driving a large capacity load. This is  
particularly important when the output relay is switched frequently  
(e.g., with proportional control).  
Platin
u
m resistance  
thermometer inp
u
t  
Power Supply  
Thermoco
u
ple inp
u
t  
•
If a single power supply is used for the E5C2 and the load, the  
supply voltage of the power supply may vary greatly when the load  
is open or closed if the capacity of the power supply is not large  
enough. Make sure that the capacity of the power supply is large  
enough so that the supply voltage range will be always from 90% to  
110% of the rated supply voltage.  
Po
w
er s
u
pply  
100/110/120
V
AC (same model) or  
200/220/240
V
AC (same model)  
50/60 Hz  
Thermistor
w
ith  
replacea
b
le element  
•
The E5C2 operates at either 50 or 60 Hz.  
•
On the E52-
@@
1D, the lead wires are thermocouple element wires,  
making them difficult to solder because solder will not stick to them  
easil
y
.
R
emove the crimp terminal and polish the ends before  
attempting to solder them.  
Nomenclature  
Operation Indicator  
T
e
mperat
u
re setting kno
b  
Indicator  
Output  
NO contacts (4 and 5)
 
NC contacts (4 to 6)  
Operation indicator  
Red Lit  
Not lit  
ON  
OFF  
ON  
OFF  
RESET adj
u
stment shaft  
N
o reset f
u
nction is incorporated
b
y any  
E5C2 model
w
ith O
N
/OFF control.  
3

E5C2  
Dimensions  
Note:
All units are in millimeters unless otherwise indicated.  
Terminal Arrangement  
(Bottom View)  
48 x 48  
44.8 x 44.8  
Dimensions with Flush-mounting Adapter (Accessory),  
and Back Connecting Socket (Sold Separately)  
Panel  
Y92F-30 Flush-mounting adapter  
Flush-mounting  
adapter  
P3G-08 Back  
connecting socket  
Tightening screw  
(96)  
Panel Cutout  
Side-by-side Mounting  
of N Controllers  
Qty.  
L
2
3
4
5
6
93

+

0

1

141

+

0

1

189

+

0

1

237

+

0

1

285

+

0

1  

60 min.  
Note: 1.
Recommended panel thickness is 1 to 4 mm.  
2.
Close side-by-side mounting is possible (in a single direction).  
■
Accessories (Order Separately)  
Connection Sockets  
P2CF-08 Front Connecting Socket  
Mounting Holes  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Eight, M3.5 x 7.5 sems  
T
w
o, 4.5 dia. or two, M4  
70 max.  
T
w
o,  
4.5-dia.  
holes  
Note:
Can also be  
mounted to a  
DIN track.  
50 max.  
20 max.  
Note:
A finger-protection model (P2CF-08-E) is also available.  
P3G-08 Back Connecting Socket (for Flush Mounting)  
Terminal Arrangement/  
Internal Connections  
(Bottom View)  
27 dia.  
Note:
A Protective Cover for finger protection (Y92A-48G) is also available.  
4

E5C2  
Hard Protective Cover  
Applicable Thermistor  
A Hard Protective Cover (Y92A-48B) is available. It can be used in  
the following cases.  
Connect a Thermistor with a replaceable element (E52-THE5A, E52-  
THE6D, or E52-THE6F) to the E5C2-R20G. Refer to
E52
for details.  
•
T
o
p
rotect the setting section, against dust and dirt  
•
T
o
p
revent accidently changing settings by touching the front of the  
Controller.  
•
T
o
p
rotect the Controller from water drips  
Appearance  
Model  
Y92A-48B  
Safety Precautions  
Refer to
Safety Precautions for All
T
e
mperature Controllers
.  
■
Correct Use  
The P3G-08 can be wired in the same way as the P2CF-08.  
Mounting  
Track Mounting (E5C2 with P2CF-08)  
When mounting two or more E5C2 models with track-mounting  
sockets, leave a space of approximately 20 mm on both sides of the  
sockets where hooks are located.  
Hook  
Duct  
Dismounting  
If flush mounted, loosen the screw of the adapter and disengage the  
hooks for dismounting.  
P2CF-08  
20  
Panel  
Flush Mounting  
Insert E5C2 into the square hole of the panel and insert an adapter  
from the back so that there will be no space between E5C2 and the  
panel. Then, secure the E5C2 with a screw.  
Temperature Setting  
Do not turn the temperature setting knob of the E5C2 with excessive  
force, otherwise the stopper of the knob may break.  
Others  
•
Do not remove the housing of the E5C2, otherwise the housing  
may break.  
Tightening screw  
•
T
o
c
lean the surface of the E5C2, use a soft cloth wet with neutral  
detergent or alcohol. Do not use any organic solvent, such as paint  
thinner or benzine, strong acid or strong alkali to clean the surface  
of the E5C2, otherwise the surface of the E5C2 will become  
damaged.  
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.  
To
c
onvert millimeters into inches, multiply by 0.03937.
T
o
c
onvert grams into ounces, multiply by 0.03527.  
In the interest of product improvement, specifications are subject to change without notice.  
5

T
e
rms and Conditions Agreement  
Read and understand this catalog.  
Please read and understand this catalog before purchasing the products.
 
Please consult your OMRON representative if you  
have any questions or comments.  
Warranties.  
(a) Exclusive Warranty
. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship  
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron  
disclaims all other warranties, express or implied.  
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT  
NON-INFRINGEMEN
T
,
M
ERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER  
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE  
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.  
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the  
Products or otherwise of any intellectual property right. (c) Buyer Re
medy. Omron’s sole obligation hereunder shall be, at  
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or  
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount  
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,  
repair, indemnity or any other claims or expenses regarding the Products unless Omron
’s analysis confirms that the Products  
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate  
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall  
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or  
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,  
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above  
warranty.  
See

or contact your Omron representative for published information.  
Limitation on Liability; Etc.  
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIREC
T
,
I
NCIDENTAL, OR CONSEQUENTIAL DAMAGES,  
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,  
WHETHER SUCH CLAIM IS BASED IN CONTRAC
T
, WARRANT
Y
,
N
EGLIGENCE OR STRICT LIABILIT
Y
.  
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.  
Suitability of Use.  
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the  
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable  
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself  
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,  
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product  
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.  
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE  
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,  
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE  
OVERALL EQUIPMENT OR SYSTEM.  
Programmable Products.  
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence  
thereof.  
Performance Data.  
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining  
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate  
it to actual application requirements. Actual performance is subject to the Om
ron’s Warranty and Limitations of Liability.  
Change in Specifications.  
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our  
practice to change part numbers when published ratings or features are changed, or when significant construction changes are  
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers  
may be assigned to fix or establish key specifications for your application.
Please consult with your Omron’s representative at  
any time to confirm actual specifications of purchased Product.  
Errors and Omissions.  
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is  
assumed for clerical, typographical or proofreading errors or omissions.  
2015.8  
In the interest of product improvement, specifications are subject to change without notice.  
OMRON Corporation  
Industrial Automation Company  
(c)Copyright OMRON Corporation 2015 All Right Reserved.