General Application Guidelines  
A relay may encounter a variety of  
ambient conditions during actual use  
resulting in unexpected failure
.
T
herefore,  
testing over a practical range under actual  
operating conditions is necessar
y
.  
Application considerations should be  
reviewed and determined for proper use  
of the rela
y
.  
SAFETY PRECAUTIONS  
• Use that exceeds the specification  
ranges such as the coil rating, contact  
rating and switching life should be  
absolutely avoided. Doing so may lead to  
abnormal heating, smoke, and fire.  
• Never touch live parts when power is  
applied to the rela
y
.
D
oing so may cause  
electrical shock. When installing,  
maintaining, or troubleshooting a relay  
(including connecting parts such as  
terminals and sockets) be sure that the  
power is turned off.  
• When connecting terminals, please  
follow the internal connection diagrams in  
the catalog to ensure that connections are  
done correctl
y
.
B
e warned that an  
incorrect connection may lead to  
unexpected operation error, abnormal  
heating, and fire.  
• If the possibility exists that faulty  
adhesion or contact could endanger  
assets or human life, take double safety  
precautions and make sure that operation  
is foolproof.  
METHOD OF DETERMINING SPECIFICATIONS  
In order to use the relays properl
y
,
t
he  
characteristics of the selected relay  
the environmental conditions, and at the  
same time, the coil conditions, contact  
conditions, and the ambient conditions for  
the relay that is actually used must be  
sufficiently known in advance. In the table  
below, a summary has been made of the  
points of consideration for relay selection.  
It may be used as a reference for  
investigation of items and points of  
caution.  
should be well known, and the conditions  
of use of the relay should be investigated  
to determine whether they are matched to  
Specification item  
Consideration points regarding selection  
a) Rating  
b) Pick-up
 
voltage (current)  
c) Drop-out
 
voltage (current)  
d) Maximum
 
continuous  
impressed voltage (current)  
e) Coil
 
resistance  
1) Select
 
relay with consideration for power source ripple.  
2) Give
 
sufficient consideration to ambient temperature and for the coil temperature rise.  
3) When
 
used in conjunction with semiconductors, additional attention to the application  
should be taken.  
Coil  
4) Be
 
careful of voltage drops when starting up.  
f)
T
e
mperature
 
rise  
1) It
 
is desirable to use a standard product with more than the required number of contacts.  
2) It
 
is beneficial to have the relay life balanced with the life of the device it is used in.  
3) Is
 
the contact material matched to the type of load?  
It is necessary to take care particularly with low level usage.  
4) The
 
rated life may become reduced when used at high temperatures.  
Life should be verified in the actual atmosphere used.  
a) Contact
 
arrangement  
b) Contact
 
rating  
c) Contact
 
material  
d) Life  
Contacts  
e) Contact
 
resistance  
5) Depending
 
on the circuit, the relay drive may synchronize with the AC load. As this will  
cause a drastic shortening of life should be verified with the actual machine.  
a) Operate
 
time  
b) Release
 
time  
c) Bounce
 
time  
1) Working
 
life verification under actual conditions is required when switching frequency is  
high because this will shorten life.  
Operate time  
d) Switching
 
frequency  
a) Vibration
 
resistance  
b) Shock
 
resistance  
c) Ambient
 
temperature  
d) Life  
1) Give
 
consideration to performance under vibration and shock in the use location.  
2) In
 
particular, when used in high temperature applications, relay with class B or class F coil  
insulation may be required.  
Mechanical  
characteristics  
1) Selection
 
can be made for connection method with plug-in type, printed circuit board type,  
soldering, and screw fastening type.  
2) For
 
use in an adverse atmosphere, sealed construction type should be selected.  
3) When
 
used in adverse environments, use the sealed type.  
4) Are
 
there any special conditions?  
a) Breakdown
 
voltage  
b) Mounting
 
method  
c) Size  
Other items  
d) Protective
 
construction  
BASICS ON REL
A
Y
H
ANDLING  
•
T
o
m
aintain initial performance, care  
should be taken to avoid dropping or  
hitting the rela
y
.  
one of the sealed types (sealed type, etc.)  
temperature values listed in the catalog.  
• Use the flux-resistant type or sealed type  
if automatic soldering is to be used.  
• Use alcohol based cleaning solvents  
when cleaning is to be performed using a  
sealed type rela
y
.  
• Avoid ultrasonic cleaning of all types of  
relays.  
• Avoid bending terminals, because it may  
cause malfunction.  
• As a guide, use terminal mounting  
pressure of 40 to 70N {4 to 7kgf} for relays  
with plag-in terminals.  
• For proper use, read the main text for  
details.  
should be considered.  
• Proper usage requires that the rated  
voltage be impressed on the coil.  
• Be sure the coil impressed voltage does  
not continuously exceed the maximum  
allowable voltage.  
• Under normal use, the relay is designed  
so that the case will not detach.
T
o  
maintain initial performance, the case  
should not be removed. Relay  
characteristics cannot be guaranteed if  
the case is removed.  
• The rated switching power and life are  
given only as guides. The physical  
phenomena at the contacts and contact  
life greatly vary depending on the type of  
load and the operating conditions.  
Therefore, be sure to carefully check the  
type of load and operating conditions  
before use.  
• Use of the relay in an atmosphere at  
standard temperature and humidity with  
minimal amounts of dust, SO

2

, H

2

S, or  
organic gases is recommended.  
Also note that use of silicon-based resins  
near the relay may result in contact failure.  
For installation in adverse environments,  
• Do not exceed the usable ambient  
16  

General Application Guidelines  
PROBLEM POINTS WITH REGARD TO USE  
In the actual use of relays, various  
tests are necessary under the possible  
relay is a mass production item, and as a  
matter of principle, it must be recognized  
that the relay is to be used to the extent of  
such variations without the need for  
ambient conditions are encountered, and  
because unforeseen events occur which  
can not be thought of on the drawing  
board, with regard to such conditions,  
range of operation. For example,  
consideration must always be given to  
variation of performance when relay  
characteristics are being reviewed. The  
adjustment.  
REL
A
Y
C
OIL  
1. Power source for DC input  
As a power source for the DC type rela
y
, a  
battery or either a half wave or full wave  
rectifier circuit with a smoothing capacitor  
is used
.
T
he characteristics with regard to  
the excitation voltage of the relay will  
change depending upon the type of power  
source, and because of this, in order to  
display stable characteristics, the most  
desirable method is perfect DC.  
~
R
Relay  
Smoothing capacitor  
Ripple portion  
In the case of ripple included in the DC  
power source, particularly in the case of  
half wave rectifier circuit with a smoothing  
capacitor, if the capacity of the capacitor  
is too small, due to the influence of the  
ripple, humming develops and an  
unsatisfactory condition is produced. It is  
necessary to give consideration to the use  
of a power source with less than a 5%  
ripple, with the actual circuit to be used, it  
is absolutely necessary to confirm the  
characteristics. (Fig. 1)  
DC portion  
Emean.  
Emax. Emin.  
Emax.
–
Emin  
Emean.  
Emax. = Maximum value of ripple portion  
Ripple percentage =  
×
100%  
Emin. = Minimum value of ripple portion  
Emean.= Average value of ripple portion  
Fig. 1  
[1] It is desirable to have less than a 5%  
ripple for the reed type relay (including NR  
relay also).  
[4] Shown on below, is a circuit driven by  
the same power supply (batter
y
,
e
tc.) for  
both the coil and contact.  
[2] For the hinge type rela
y
, a
h
alf wave  
rectifier cannot be used, alone unless you  
use a smoothing capacitor
.
T
he ripple and  
the characteristics must be evaluated for  
proper usage.  
[3] For the hinge type rela
y
,
t
here are  
certain applications that may or maynot  
use the full wave rectifier on it’s own.  
Please check specifications with the  
original manufacture.  
Coil applied voltage and the drop in  
voltage. Please verify that the actual  
voltage is applied to the coil at the actual  
load. Electrical life will be affected by the  
drop in voltage in the coil when the load is  
turned on.  
2. Coil temperature rise  
continuous current passage, it is rather  
small. The various relays are essentially  
the same in this respect.  
• Pick-up voltage change due to coil  
temperature rise (hot start)  
Proper usage requires that the rated  
voltage be impressed on the coil. Note,  
however, that if a voltage greater than or  
equal to the maximum continuous  
impressed voltage is impressed on the  
coil, the coil may burn or its layers short  
due to the temperature rise. Furthermore,  
do not exceed the usable ambient  
temperature range listed in the catalog.  
•
T
emperature rise due to pulse voltage  
(Please refer to this when PWM control  
will be used.)  
When a pulse voltage with ON time of less  
than 2 minutes is used, the coil  
temperature rise bares no relationship to  
the ON time. This varies with the ratio of  
ON time to OFF time, and compared with  
In DC relays, after continuous passage of  
current in the coil, if the current is turned  
OF
F
,
t
hen immediately turned ON again,  
due to the temperature rise in the coil, the  
pick-up voltage will become somewhat  
higher. Also, it will be the same as using it  
in a higher temperature atmosphere. The  
resistance/temperature relationship for  
copper wire is about 0.4% for 1
°
C, and  
with this ratio the coil resistance  
increases. That is, in order to cause  
operation of the rela
y
,
t
he current  
necessary becomes higher than the pick-  
up current, accompanying the rise in the  
resistance value.  
Current passage time  
%
T
e
mperature rise  
value is 100%  
For continuous passage  
ON : OFF = 3 : 1  
ON : OFF = 1 : 1  
ON : OFF = 1 : 3  
About 80%  
About 50%  
About 35%  
1 : 1  
Time  
17  

General Application Guidelines  
3. Operate time  
In the case of DC operation, to the extent  
of large coil input, the operating time is  
rapid, but if it is too rapid, the
“
A
”
contact  
bounce time is extended.  
Please be warned that load conditions (in  
particular when inrush current is large or  
load is close to the load rating) may cause  
the working life to shorten and slight  
welding.  
4. Phase synchronization in AC load switching  
If switching of the relay contacts is  
synchronized with the phase of the AC  
power, reduced electrical life, welded  
contacts, or a locking phenomenon  
Load  
R
y  
Load  
voltage  
Load  
voltage  
V
in.  
(incomplete release) due to contact  
material transfer may occur. Therefore,  
check the relay while it is operating in the  
actual system. However, if problems  
V
in.  
Fig. 2  
develop, control the relay using an  
appropriate phase. (Fig. 2)  
5. Long term current carrying  
In applications which involve lengthy duty  
cycles, the preferred con
fi
guration would  
be the use of the form B or N.C. contacts  
for long term dut
y
.
I
n those instances  
where the form A contact is held closed  
for extensive time periods, coil heating will  
increase contact
“
T
”
rise and may result in  
shorter than optimum life. Alternatel
y
,  
latching types may be considered for  
these applications, using a storage  
capacitor to
“
Reset
”
the relay on power-  
down.  
18  

General Application Guidelines  
CONTACT  
The contacts are the most important  
elements of relay construction. Contact  
performance conspicuously in
fl
uenced by  
contact material, and voltage and current  
values applied to the contacts (in  
particular, the voltage and current  
waveforms at the time of application and  
release), the type of load, frequency of  
switching, ambient atmosphere, form of  
contact, contact switching speed, and of  
bounce.  
1. Contact circuit voltage, current, and  
load  
[Voltage, AC and DC]  
separately below, occurs in relation to the  
contact wear. Ordinaril
y
,
t
he approximate  
control capacity is mentioned in catalogs  
or similar data sheets, but this alone is not  
suf
fi
cient
.
W
ith special contact circuits, for  
the individual case, the maker either  
estimates from the past experience or  
makes test on each occasion.  
When there is inductance included in the  
circuit, a rather high counter emf is  
generated as a contact circuit voltage,  
and since, to the extent of the value of that  
voltage, the energy applied to the  
contacts causes damage with  
consequent wear of the contacts, and  
transfer of the contacts, it is necessary to  
exercise care with regard to control  
capacit
y
.
I
n the case of DC, there is no  
zero current point such as there is with  
AC, and accordingl
y
,
o
nce a cathode arc  
has been generated, because it is dif
fi
cult  
to quench that arc, the extended time of  
the arc is a major cause. In addition, due  
to the direction of the current being
fi
xed,  
the phenomenon of contact shift, as noted  
[Current]  
The current at both the closing and  
opening time of the contact circuit exerts  
important in
fl
uence. For example, when  
the load is either a motor or a lamp, to the  
extent of the inrush current at the time of  
closing the circuit, wear of the contacts,  
and the amount of contact transfer  
increase, and contact welding and contact  
transfer make contact separation  
impossible.  
Because of contact transfer, welding,  
abnormal wear, increase in contact  
resistance, and the various other  
damages which bring about unsuitable  
operation, the following items require full  
investigation.  
2. Characteristics of Common Contact Materials  
Characteristics of contact materials are given below. Refer to them when selecting a rela
y
.  
Electrical conductivity and thermal conductivity are the highest of all metals. Exhibits low contact resistance, is  
inexpensive and widely used. A disadvantage is it easily develops a sul
fi
de
fi
lm in a sul
fi
de atmosphere. Care is  
required at low voltage and low current levels.  
Ag  
(silver)  
AgCdO  
Exhibits the conductivity and low contact resistance of silver as well as excellent resistance to welding.  
(silver-cadmium)  
Like silver, it easily develops a sul
fi
de
fi
lm in a sul
fi
de atmosphere.  
AgSnO

2  

Exhibits superior welding resistance characteristics equal or better than AgCdO.  
(silver-tin)  
Like silver, it easily develops a sul
fi
de
fi
lm in a sul
fi
de atmosphere.  
Contact  
Material  
Hardness and melting point are high, arc resistance is excellent, and it is highly resistant to material transfer.  
However, high contact pressure is required. Furthermore, contact resistance is relatively high and resistance to  
corrosion is poor. Also, there are constraints on processing and mounting to contact springs.  
AgW  
(silver-tungsten)  
AgNi  
(silver-nickel)  
Equals the electrical conductivity of silver. Excellent arc resistance.  
AgPd  
At standard temperature, good corrosion resistance and good sul
fi
dation resistance. However, in dry circuits,  
(silver-palladium)  
organic gases adhere and it easily develops a polymer. Gold clad is used to prevent polymer buildup. Expensive.  
PGS alloy  
(platinum, gold, silver)  
Excellent corrosion resistance. Mainly used for low current circuits. (Au : Ag : Pt = 69 : 25 : 6)  
Combines perfect corrosion resistance and hardness. As plated contacts, used for relatively light loads. In an  
organic gas atmosphere, care is required as polymers may develop. Therefore, it is used in hermetic seal relays  
(reed relays, etc.) . Expensive.  
Rh plating  
(rhodium)  
Au with its excellent corrosion resistance is pressure welded onto a base metal. Special characteristics are  
uniform thickness and the nonexistence of pinholes. Greatly effective especially for low level loads under relatively  
adverse atmospheres. Often dif
fi
cult to implement clad contacts in existing relays due to design and installation.  
Au clad  
(gold clad)  
Surface  
Finish  
Au plating  
(gold plating)  
Similar effect to Au cladding. Depending on the plating process used, supervision is important as there is the  
possibility of pinholes and cracks. Relatively easy to implement gold plating in existing relays.  
Au
fl
ash plating  
Purpose is to protect the contact base metal during storage of the switch or device with built-in switch. However,  
(gold thin-
fi
lm plating)
 
a certain degree of contact stability can be obtained even when switching loads.  
19  

General Application Guidelines  
3. Contact Protection  
with the polarity shown in Fig. 1 (b) at the  
• Material Transfer Phenomenon  
Material transfer of contacts occurs when  
one contact melts or boils and the contact  
material transfers to the other contact. As  
the number of switching operations  
increases, uneven contact surfaces  
develop such as those shown in Fig. 2.  
After a while, the uneven contacts lock as  
if they were welded together. This often  
occurs in circuits where sparks are  
produced at the moment the contacts  
“
make
”
such as when the DC current is  
large for DC inductive or capacitive loads  
or when the inrush current is large  
(several amperes or several tens of  
amperes).  
• Counter EMF  
instant the inductive load is switched off.  
The counter emf passes through the  
power supply line and reaches both  
contacts.  
Generall
y
,
t
he critical dielectric  
breakdown voltage at standard  
When switching inductive loads with a DC  
relay such as relay sequence circuits, DC  
motors, DC clutches, and DC solenoids, it  
is always important to absorb surges (e.g.  
with a diode) to protect the contacts.  
When these inductive loads are switched  
off, a counter emf of several hundred to  
several thousand volts develops which  
can severely damage contacts and  
greatly shorten life. If the current in these  
loads is relatively small at around 1A or  
less, the counter emf will cause the  
ignition of a glow or arc discharge. The  
discharge decomposes organic matter  
contained in the air and causes black  
deposits (oxides, carbides) to develop on  
the contacts. This may result in contact  
failure.  
temperature and pressure in air is about  
200 to 300 volts. Therefore, if the counter  
emf exceeds this, discharge occurs at the  
contacts to dissipate the energy (

1

/

2

Li

2

)  
stored in the coil. For this reason, it is  
desirable to absorb the counter emf so  
that it is 200V or less.  
A memory oscilloscope, digital memor
y
,  
peak hold meter, etc., can be used to  
measure the counter emf. However, since  
the waveform is extremely steep,  
considerable discrepancies may result  
depending on the precision of the  
equipment used. The table shows the  
counter emf of various relays measured  
on a high precision peak hold meter.  
Actual measurement of counter emf on a  
peak hold meter  
The aim here is to use a contact  
protection circuit or choose a contact  
material that is suitable for the load.  
Generall
y
, a
c
oncave formation appears  
on the cathode and a convex formation  
appears on the anode. For DC capacitive  
loads (several amperes to several tens of  
amperes), it is always necessary to  
conduct actual con
fi
rmation tests.  
ON OFF  
E
0
Peak voltage  
+
–
meter  
–
Several hundred  
to several  
thousand volts  
+
e
+
R
E
–
di  
dt  
Nominal Coil  
e =
–
L  
Voltage  
12V DC  
(a)  
(b)  
Relay
T
y
pe  
CM relay  
CM relay  
Fig. 1 Example of counter emf and actual  
measurement on a peak hold meter  
Min. 1,600V  
Approx. 85V  
di  
dt  
Meterial transfer of contacts  
In Fig
.
1
(
a), an emf (e =
–
L )
 
with a steep  
waveform is generated across the coil  
(Resistor inside type)  
Fig. 2  
• Contact Protection Circuit  
Use of contact protective devices or  
protection circuits can suppress the  
counter emf to a low level. However, note  
that incorrect use will result in an adverse  
effect.
T
y
pical contact protection circuits  
are given in the table below.  
(G: Good, NG: No Good, C: Care)  
Application  
Circuit  
Features/Others  
Devices Selection  
AC DC  
If the load is a timer, leakage current
fl
ows  
through the CR circuit causing faulty operation.  
* If used with AC voltage, be sure the impedance  
of the load is suf
fi
ciently smaller than that of the  
CR circuit  
Contact  
As a guide in selecting r and c,  
r: 0.5 to 1
Ω
per 1V contact voltage  
c: 0.5 to 1µF per 1A contact current  
C*  
G
G
G
G
G
G
r
c
Values vary depending on the properties of the  
load and variations in relay characteristics.  
Capacitor c acts to suppress the discharge the  
moment the contacts open. Resistor r acts to limit  
the current when the power is turned on the next  
time.
T
e
st to con
fi
rm. Use a capacitor with a  
breakdown voltage of 200 to 300
V
.
U
se AC type  
capacitors (non-polarized) for AC circuits.  
Contact  
If the load is a relay or solenoid, the release time  
lengthens. Effective when connected to both  
contacts if the power supply voltage is 24 or 48V  
and the voltage across the load is 100 to 200
V
.  
r
c
The diode connected in parallel causes the energy  
stored in the coil to
fl
ow to the coil in the form of  
current and dissipates it as joule heat at the resistance
 
least as large as the load current. In electronic circuits  
component of the inductive load. This circuit further  
delays the release time compared to the CR circuit.  
(2 to 5 times the release time listed in the catalog)  
Use a diode with a reverse breakdown voltage at least  
10 times the circuit voltage and a forward current at  
Contact  
NG  
NG  
G
Diode  
where the circuit voltages are not so high, a diode can  
be used with a reverse breakdown voltage of about 2  
to 3 times the power supply voltage.  
Contact  
Effective when the release time in the diode  
circuit is too long.  
Use a zener diode with a zener voltage about the  
same as the power supply voltage.  
Using the stable voltage characteristics of the varistor,  
this circuit prevents excessively high voltages from being  
applied across the contacts. This circuit also slightly  
delays the release time. Effective when connected to  
both contacts if the power supply voltage is 24 or 48V  
and the voltage across the load is 100 to 200
V
.  
Contact  
Varistor  
—
20  

General Application Guidelines  
•
Avoid using the protection circuits shown  
in the
fi
gures on the right.  
Contact  
Contact  
Although DC inductive loads are usually  
more dif
fi
cult to switch than resistive  
loads, use of the proper protection circuit  
will raise the characteristics to that for  
resistive loads.  
Power  
Power  
supply  
C
C
No good  
No good  
supply  
Although extremely effective in arc suppression
 
Although extremely effective in arc suppression  
as the contacts open, the contacts are
 
as the contacts open, the contacts are  
susceptible to welding since energy is stored in
 
susceptible to welding since charging current  
C when the contacts open and discharge  
fl
ows to C when the contacts close.  
current
fl
ows from C when the contacts close.  
• Mounting the Protective Device  
In the actual circuit, it is necessary to  
locate the protective device (diode,  
resistor, capacitor, varistor, etc.) in the  
immediate vicinity of the load or contact
.
I
f  
located too far awa
y
,
t
he effectiveness of  
the protective device may diminish. As a  
guide, the distance should be within  
50cm.  
• Abnormal Corrosion During High  
Frequency Switching of DC Loads  
(spark generation)  
If, for example, a DC valve or clutch is  
switched at a high frequenc
y
, a blue-green  
corrosion may develop. This occurs from  
the reaction with nitrogen in the air when  
sparks (arc discharge) are generated  
during switching. For relays with a case,  
the case must be removed or air holes  
drilled in the case. A similar phenomenon  
occurs in the presence of ammonia-based  
gas
.
T
herefore, care is required in circuits  
where sparks are generated at a high  
frequenc
y
.  
Release time will slow down if, as shown  
in the diagram, a diode is connected in  
parallel to the coil in order to absorb relay  
coil counter electromotive force. Please  
test under actual load conditions because  
electrical life will be affected depending on  
the type of load.  
4. Cautions on Use Related to Contacts  
• Connection of load and contacts  
Connect the load to one side of the power  
supply as shown in Fig. 3 (a). Connect the  
contacts to the other side. This prevents  
high voltages from developing between  
contacts. If contacts are connected to  
both side of the power supply as shown in  
Fig. 3 (b), there is a risk of shorting the  
power supply when relatively close  
contacts short.  
R
y  
E
E
(a)  
(b)  
R
y  
R
y  
R
y  
(a) Good example  
(b) Bad example  
Fig. 3  
• Avoid Circuits Where Shorts Occur Between Form A and B Contacts  
1) The clearance between form A and B  
contacts in compact control components  
R
1  
is small. The occurrence of shorts due to  
arcing must be assumed.  
2) Even if the three N.C., N.O., and COM  
contacts are connected so that they short,  
a circuit must never be designed to allow  
R
1  
Push-botton  
switch  
N.C.  
N.O.  
COM  
M
R
Relay coil  
R
R
2  
the possibility of burning or generating an  
R
2  
overcurrent.  
1) R

1

, R
2
: Contacts for R  
2)  
3) R
1
, R
2
: Contacts for R  
: Double pole relay  
R
: Double pole relay  
R
3) A forward and reverse motor rotation  
circuit using switching of form A and B  
contacts must never be designed.  
Fig. 4 Bad example of Form A and B use  
• Shorts Between Different Electrodes  
Although there is a tendency to select  
miniature control components because of  
the trend toward miniaturizing electrical  
control units, care must be taken when  
selecting the type of relay in circuits where  
different voltages are applied between  
electrodes in a multi-pole rela
y
,
e
specially  
when switching two different power supply  
circuits. This is not a problem that can be  
determined from sequence circuit  
diagrams. The construction of the control  
component itself must be examined and  
suf
fi
cient margin of safety must be  
provided especially in creepage between  
electrodes, space distance, presence of  
barrier, etc.  
21  

General Application Guidelines  
• Type of Load and Inrush Current  
The type of load and its inrush current characteristics, together  
with the switching frequenc
y
,
a
re important factors which cause  
contact welding. Particularly for loads with inrush currents,  
measure the steady state and inrush current
.
T
hen select a relay  
which provides an ample margin of safet
y
.
T
he table on the right  
shows the relationship between typical loads and their inrush  
currents.  
T
y
pe of load  
Resistive load  
Inrush current  
Steady state current  
Solenoid load  
10 to 20 times the steady state current  
5 to 10 times the steady state current  
10 to 15 times the steady state current  
Approx. 3 times the steady state current  
1 to 3 times the steady state current  
20 to 40 times the steady state current  
5 to 15 times the steady state current  
Motor load  
Incandescent lamp load  
Mercury lamp load  
Sodium vapor lamp load  
Capacitive load  
Also, verify the actual polarity used since, depending on the rela
y
,  
electrical life is affected by the polarity of COM and NO.  
T
r
ansformer load  
Load Inrush Current Wave and Time  
(1) Incandescent Lamp Load  
(2) Mercury Lamp Load  
(3) Fluorescent Lamp Load  
i/i
O
]
3 times  
i/i
O
]
5 to 10 times  
L
Contacts  
i
i
i

o  

i
o  
C
i
i
o  
(for high power factor type)  
3 to  
5 minutes  
10 seconds  
or less  
Incandescent lamp  
The discharge tube, transformer, choke coil,  
capacitor, etc., are combined in common  
discharge lamp circuits. Note that the inrush  
current may be 20 to 40 times, especially if  
the power supply impedance is low in the  
high power factor type.  
Approx. 1/3 second  
Inrush current/rated current  
=i/i

o

= 10 to 15 times  
(4) Motor Load i/i

O

]
5 to 10 times  
(5) Solenoid Load  
(6) Electromagnetic Contact Load
 
(7) Capacitive Load  
i/i

O

]
10 to 20 times  
i/i

O

]
3 to 10 times  
i/i

O

]
20 to 40 times  
i
o  
i
i
i
o  
i
i
o  
i
o  
i
0.07  
to 0.1 second  
0.2 to 0.5 second  
•
Conditions become more harsh if plugging or inching  
is performed since state transitions are repeated.  
•
When using a relay to control a DC motor and brake,  
the on time surge current, normal current and off  
time brake current differ depending on whether the  
load to the motor is free or locked. In particular, with  
non-polarized relays, when using from b contact of  
from contact for the DC motor brake, mechanical life  
might be affected by the brake current. Therefore,  
please verify current at the actual load.  
1 to 2 cycles  
(1/60 to 1/30 seconds)  
Note that since inductance is great,  
the arc lasts longer when power is cut.  
The contact may become easily worn.  
1/2 to 2 cycles (1/120 to 1/30 seconds)  
• When Using Long Wires  
• Electrical life at high temperatures  
Verify at the actual load since electrical  
life may be affected by use at high  
temperatures.  
• If you plan to use in ways other than  
those shown in the examples in this  
catalog, please inquire beforehand to a  
sales office, or verify the usage under  
actual load conditions.  
Equivalent circuit  
If long wires (100 to 300m) are to be used  
in a relay contact circuit, inrush current  
may become a problem due to the stray  
capacitance existing between wires. Add  
a resistor (approx. 10 to 50
Ω
) in series  
with the contacts.  
+
Contacts  
Stray capacitance  
of wire  
Added resistor  
Wire  
10 to 50
Ω  
(100 to 300m)  
• Phase Synchronization in Switching AC Loads  
If switching of the relay contacts is  
synchronized with the phase of the AC  
power, reduced electrical life, welded  
contacts, or a locking phenomenon  
(incomplete release) due to contact  
material transfer may occur. Therefore,  
check the relay while it is operating in the  
actual system. However, if problems  
develop, control the relay using an  
appropriate phase.  
R
y  
Load  
voltage  
Load  
voltage  
Load  
V
in  
V
in  
22  

General Application Guidelines  
HANDLING CAUTIONS FOR TUBE
P
ACKAGING  
Some types of relays are supplied in tube  
packaging. If you remove any relays from  
Slide in the plug.  
the tube packaging, be sure to slide the  
stop plug at one end to hold the remaining  
relays
fi
rmly together so they would not  
Stop plug  
move in the tube. Failing to do this may  
lead to the appearance and/or  
performance being damaged.  
AMBIENT ENVIRONMENT  
1. Ambient Temperature and  
4. Usage, Storage, and Transport  
Conditions  
1) During usage, storage, or  
transportation, avoid locations subject to  
direct sunlight and maintain normal  
temperature, humidit
y
,
a
nd pressure  
conditions.  
The allowable speci
fi
cations for  
environments suitable for usage, storage,  
and transportation are given below.  
•
T
e
mperature
:
T
he allowable temperature  
range differs for each rela
y
,
s
o refer to the  
relay
’
s individual speci
fi
cations.  
In addition, when transporting or storing  
relays while they are tube packaged,  
there are cases when the temperature  
may differ from the allowable range.  
In this situation, be sure to consult the  
individual speci
fi
cations.  
2) Condensation  
Condensation forms when there is a  
sudden change in temperature under high  
temperature, high humidity conditions.  
Condensation will cause deterioration of  
the relay insulation.  
3) Freezing  
Condensation or other moisture may  
freeze on the relay when the  
temperatures is lower than 0
°
C
32
°
F
.  
This causes problems such as sticking of  
movable parts or operational time lags.  
4) Low temperature, low humidity  
environments  
The plastic becomes brittle if the relay is  
exposed to a low temperature, low  
humidity environment for long periods of  
time.  
Atmosphere  
Be sure the ambient temperature at the  
installation does not exceed the value  
listed in the catalog. Furthermore,  
environmentally sealed types (plastic  
sealed type) should be considered for  
applications in an atmosphere with dust,  
sulfur gases (SO

2

, H

2

S), or organic gases.  
2. Silicon Atmosphere  
Silicon-based substances (silicon rubber,  
silicon oil, silicon-based coating material,  
silicon caulking compound, etc.) emit  
volatile silicon gas. Note that when silicon  
is used near rela
y
, switching the contacts  
in the presence of its gas causes silicon to  
adhere to the contacts and may result in  
contact failure.  
In this case, use a substitute that is not  
silicon-based. Also, although absorption  
by plastic does occur, it is insigni
fi
cant in  
actual practice.  
5.Vibration
,
I
mpact and Pressure when  
Shipping  
•
Humidity: 5 to 85% R.H.  
•
Pressure: 86 to 106 kPa  
The humidity range varies with the  
temperature. Use within the range  
indicated in the graph below.  
When shipping, if strong vibration, impact  
or heavy weight is applied to a device in  
which a relay is installed, functional  
damage may occur. Therefore, please  
package in a wa
y
,
u
sing shock absorbing  
material, etc., so that the allowable range  
for vibration and impact is not exceeded.  
3. Vibration and Shock  
If a relay and magnetic switch are  
mounted next to each other on a single  
plate, the relay contacts may separate  
momentarily from the shock produced  
when the magnetic switch is operated and  
result in faulty operation.  
Humidity, %R.H.  
85  
Tolerance range  
Countermeasures include mounting them  
on separate plates, using a rubber sheet  
to absorb the shock, and changing the  
direction of the shock to a perpendicular  
angle.  
(Avoid freezing when  
used at temperatures  
lower than 0
°
C
32
°
F
)  
(Avoid  
condensation when  
used at temperatures  
higher than 0
°
C
32
°
F
)  
5
–
40  
–
40  
0
+70  
+158  
+32  
Temperature,
°
C
°
F  
23  

General Application Guidelines  
ENVIRONMENTAL
L
Y
S
EALED TYPE REL
A
Y
S  
Sealed type relays are available
.
T
hey are  
effective when problems arise during PC  
board mounting (e.g. automatic soldering  
and cleaning). They also, of course,  
feature excellent corrosion resistance.  
Note the cautions below regarding the  
features and use of environmentally  
sealed type relays to avoid problems  
when using them in applications.  
2. Operating Environment of Sealed  
Type Relays (generation of NOx)  
When a plastic sealed type relay is used  
in an atmosphere high in humidity to  
switch a load which easily produces an  
arc, the NOx created by the arc and the  
water absorbed from outside the relay  
combine to produce nitric acid. This  
corrodes the internal metal parts and  
adversely affects operation.  
3. Cleaning  
When cleaning a printed circuit board  
after soldering, we recommend using  
alcohol based cleaning
fl
uids. Please  
avoid ultrasonic cleaning. The ultrasonic  
energy from this type of cleaning may  
cause coil line breakage and light sticking  
of contacts.  
1. Operating Environment  
Plastic sealed type relays are especially  
not suited for use in environments which  
require airtight relays. Although there is  
no problem if they are used at sea level,  
avoid atmospheric pressures beyond  
96±10kPa. Also avoid using them in an  
atmosphere containing
fl
ammable or  
explosive gases.  
Avoid use at an ambient humidity of  
85%RH or higher (at 20
°
C
68
°
F
). If use at  
high humidity is unavoidable, consult us.  
MOUNTING CONSIDERATIONS  
1
.
T
op View and Bottom View  
Relays used for PC boards, especially the  
fl
at type relays, have their top or bottom  
surface indicated in the terminal wiring  
diagrams.  
Furthermore, it is not desirable to switch  
3. Adjacent Mounting  
both a large load and a low level load with  
a single rela
y
.
T
he scattered contact  
material produced when switching the  
large load adheres to the contacts when  
switching the low level load and may  
cause contact failure. Therefore, avoid  
mounting the relay with its low level load  
contacts located below the large load  
contacts.  
When many relays are mounted close  
together, abnormally high temperatures  
may result from the combined heat  
generated. Mount relays with suf
fi
cient  
spacing between them to prevent heat  
buildup.  
This also applies when a large number of  
boards mounted with relays are installed  
as in a card rack. Be sure the ambient  
temperature of the relay does not exceed  
the value listed in the catalog.  
Relay with terminals  
viewed from the bottom  
(terminals cannot be  
seen from the top)  
2. Mounting Direction  
Mounting direction is important for  
optimum relay characteristics.  
4. Plug-in Terminals  
Vibration  
As a guide, use a connect mounting  
pressure of 40 to 70N {4 to 7 kgf} for  
relays with plug-in terminals.  
• Shock Resistance  
It is ideal to mount the relay so that the  
movement of the contacts and movable  
parts is perpendicular to the direction of  
vibration or shock. Especially note that  
the vibration and shock resistance of  
Form B contacts while the coil is not  
excited is greatly affected by the mounting  
direction of the rela
y
.  
• Contact Reliability  
Mounting the relay so the surfaces of its  
contacts (
fi
xed contacts or movable  
contacts) are vertical prevents dirt and  
dust as well as scattered contact material  
(produced due to large loads from which  
arcs are generated) and powdered metal  
from adhering to them.  
Vibration  
REGARDING CONNECTION OF LEAD WIRES  
•
When making the connections,  
Permissible current  
(A)  
Cross-section  
(mm

2

)  
0.2  
0.3  
0.5  
0.75  
1.25  
2
depending upon the size of load, the wire  
cross-section should be at least as large  
as the values shown in the table.  
2
3
5
7.5  
12.5  
15  
20  
30  
2
3.5  
24  

General Application Guidelines  
CAUTIONS FOR USE–Check List  
Check Item  
1. Is
 
the correct rated voltage applied?  
2. Is
 
the applied coil voltage within the allowable continuous voltage limit?  
3. Is
 
the ripple in the coil voltage within the allowable level?  
4. For
 
voltage applied to a polarized coil, is polarity observed?  
5. When
 
hot start is required, is the increase in coil resistance resulting from coil temperature rise taken into  
account in setting coil voltage?  
Coil Drive Input  
6. Is
 
the coil voltage free from momentary drop caused by load current? (Pay special attention for self-  
holding relays.)  
7. Is
 
supply voltage
fl
uctuation taken into account when setting the rated coil voltage?  
8. The
 
relay status may become unstable if the coil voltage (current) is gradually increased or decreased.  
Was the relay tested in a real circuit or with a real load?  
9. When
 
driving with transistors, did you consider voltage drops?  
1. Is
 
the load rated within the contact ratings?  
2. Does
 
the load exceed the contacts
’
minimum switching capacity?  
3. Special
 
attention is required for contact welding when the load is a lamp, motor, solenoid, or  
electromagnetic contractor. Was the relay tested with a real load?  
4. A
 
DC load may cause contact lock-up due to large contact transfer. Was the relay tested with a real load?  
5. For
 
an inductive load, is a surge absorber used across the contacts?  
6. When
 
an inductive load causes heavy arc discharge across the relay contacts, the contacts may be  
corroded by chemical reaction with nitrogen in the atmosphere. Was the relay tested with a real load?  
Load  
7. Platinum
 
contacts may generate brown powder due to a catalyzer effect or vibration energ
y
. Was the  
relay tested with a real load?  
(Relay contacts)  
8. Is
 
the contact switching frequency below the speci
fi
cation?  
9. When
 
there are more than two sets of contacts (2T) in a rela
y
,
m
etallic powder shed from one set of  
contacts may cause a contact failure on the other set (particularly for light loads). Was the relay tested in  
a real load?  
10. A
 
delay capacitor used across relay contacts may cause contact welding
.
W
as the relay tested with a real  
load?  
11. A
 
high voltage may be induced at transformer load. Was the relay tested with a real load?  
1. Does
 
circuit design take into account electrolytic corrosion of the coil?  
2. Are
 
transistors and other circuit components protected from counter electromotive force that develops  
across the relay coil?  
3. Is
 
the circuit designed so the relay coil is left deenergized while the relay is inactive for long period of  
time?  
4. Is
 
the relay operated within the ratings approved by the relevant international standard (if compliance is  
required)?  
5. Is
 
the circuit protected from malfunction when the relay
’
s operation and/or release time varies  
considerably?  
Circuit Design  
6. Is
 
the circuit protected from malfunctions that might result from relay contact bounce?  
7. When
 
there are two or more sets of contacts (2T) in a rela
y
,
a
rc discharges from load switching may  
cause short circuits across the two or more sets of contacts. Is the circuit designed to suppress such arc  
discharges?  
8. Item
 
7 above also requires special attention when loads are supplied from separate power sources.  
9. Is
 
the circuit protected from malfunction when the relay is to be driven by transistors?  
10. When
 
the SCR is used for on/off control, the relay activation tends to synchronize with the line frequenc
y
,  
resulting in an extremely shortened life. Was the relay tested in a real circuit or with a real load?  
11. Does
 
the PC board design take into account use of on-board relay?  
25  

General Application Guidelines  
Check Item  
1. Is
 
the ambient temperature in the allowable operating temperature range?  
2. Is
 
relative humidity below 85 percent?  
3. Is
 
the operating atmosphere free from organic and sul
fi
de gases?  
4. Is
 
the operating atmosphere free from silicon gas? Depending on the load type, silicon gas may cause a  
black substance to from on the contacts, leading to contact failure.  
5. Is
 
the operating atmosphere free from excessive airborne dust?  
Operating  
Environment  
6. Is
 
the relay protected from oil and water splashes?  
7. Is
 
the relay protected from vibration and impact which may cause poor contact with the socket?  
8. Is
 
ambient vibration and impact below the level allowable for the relay?  
9. Is
 
the relay free from mechanical resonance after it is installed in position?  
10. Is
 
insulation coating applied to the relay along with the PC board? Depending on the load type, a black  
substance may form to cause contact failure.  
1. Is
 
the relay protected from solder chips and
fl
ux when it is manually soldered?  
2. Are
 
preparations for
fl
ux application and automatic soldering complete?  
3. Is
 
the PC board cleaning process designed to minimize adverse affects to the relays?  
4. Are
 
adequate separations provided between polarized or reed relays to prevent magnetic coupling?  
5. Are
 
the relay terminals free from stress in the socket?  
6. Polarized
 
relay’s characteristics may be affected by strong external magnetic
fi
eld. Are the relays  
installed away from such
fi
elds?  
7. If
 
very long leads (100 to 300 meters) are used to connect the load, the stray capacity existing across the  
leads may cause a surge current. Was the relay tested with a real load?  
Installation and  
Connection  
8. Unless
 
otherwise speci
fi
ed, all relay terminals should be soldered at 250
°
C
482
°
F
within 5 sec. or at  
350
°
C
662
°
F
within 3 sec.  
9. A
 
badly warped PC board can cause stress to the relay terminals which may lead to degraded relay  
characteristics.  
10. Glass
 
shot should not be used to clean the PC board of solder
fl
ux. This may cause relay malfunction  
due to glass powder becoming lodged in the relay’s internal structure.  
11. Relays
 
should always be used with their plastic shields installed, or degraded relay performance may  
result.  
12. Do
 
not cut away any relay terminal as the stress may cause degraded relay performance.  
1. Is
 
the relay subject to freezing or condensation (especially when shipping)?  
2. Is
 
the temperature in the allowable temperature range?  
3. Is
 
the humidity in the allowable humidity range?  
4. Is
 
the storing atmosphere free from organic and sul
fi
de gases?  
5. Is
 
the storing atmosphere free from excessive airborne dust?  
6. Is
 
the relay protected from oil and water splashes?  
Storage and  
T
r
ansport  
7. Is
 
the relay subject to the application of heavy weight?  
8. When
 
shipping does vibration and impact exceed the allowable range?  
26