Phoenix-Contact-2903278

Part #Phoenix-Contact-2903278
Download 
Phoenix-Contact-2903278
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user’s  
documentation. Our General Terms of Use for Downloads are valid  
(http://download.phoenixcontact.com)  
Pre-assembled relay module with push-in connection, consisting of: relay base, power contact relay, and  
retaining bracket. Contact type: 3 PDTs. Input voltage: 24 V DC  
Key commercial data  
Packing unit  
1 pc  
Weight per Piece (excluding packing)  
Custom tariff number  
Country of origin  
212.0 GRM  
85364110  
Germany  
Technical data  
Dimensions  
Width  
Height  
Depth  
43 mm  
111 mm  
90 mm  
Ambient conditions  
Ambient temperature (operation)  
-40 °C … 60 °C  
-40 °C … 85 °C  
Ambient temperature (storage/transport)  
Coil side  
Nominal input voltage U

N  

Input voltage range in reference to U

N  

Nominal input current at U

IN  

Typical response time  
24 V DC  
(see diagram)  
56 mA  
20 ms  
Typical release time  
20 ms  
Operating voltage display  
Yellow LED  
3/7/14 Page
 
1 / 7  

Technical data  
Coil side  
Protective circuit  
Damping diode  
Polarity protection diode  
Contact side  
Contact type  
3 PDTs  
Contact material  
AgNi  
Maximum switching voltage  
440 V AC  
250 V DC  
Minimum switching voltage  
Maximum inrush current  
10 V (At 24 mA)  
50 A (20 ms, N/O contact)  
10 mA (at 24 V)  
Min. switching current  
Limiting continuous current  
Interrupting rating (ohmic load) max.  
10 A (see diagram)  
240 W (at 24 V DC)  
124 W (at 48 V DC)  
108 W (at 60 V DC)  
52 W (at 110 V DC)  
70 W (at 220 V DC)  
2500 VA (for 250 V AC)  
4000 VA (At 440 V AC)  
2 A (24 V (DC13))  
Switching capacity in acc. with DIN VDE 0660/IEC 60947  
1.5 A (230 V (AC15))  
3.8 A (400 V (AC3))  
1500 W  
3-phase motor load  
Motor load according to UL 508  
1/3 HP, 120 V AC (single-phase AC motor)  
1/2 HP, 240 V AC (single-phase AC motor)  
1/2 HP, 240 V AC (three-phase induction motor)  
Connection data  
Connection method  
Push-in connection  
Input  
Connection name  
Connection method  
Push-in connection  
0.14 mm²  
Conductor cross section solid min.  
Conductor cross section solid max.  
1.5 mm²  
Conductor cross section stranded min.  
Conductor cross section stranded max.  
Conductor cross section stranded, with ferrule with plastic sleeve min.  
Conductor cross section stranded, with ferrule with plastic sleeve max.  
Conductor cross section stranded, with ferrule without plastic sleeve min.  
0.14 mm²  
1.5 mm²  
0.14 mm²  
1.5 mm²  
0.14 mm²  
3/7/14 Page
 
2 / 7  

Technical data  
Connection data  
Conductor cross section stranded, with ferrule without plastic sleeve max.
 
1.5 mm²  
Conductor cross section AWG/kcmil min.  
Conductor cross section AWG/kcmil max  
Stripping length  
26  
16  
8 mm  
Connection name  
Output  
Connection method  
Push-in connection  
0.14 mm²  
2.5 mm²  
0.14 mm²  
2.5 mm²  
0.14 mm²  
2.5 mm²  
0.14 mm²  
Conductor cross section solid min.  
Conductor cross section solid max.  
Conductor cross section stranded min.  
Conductor cross section stranded max.  
Conductor cross section stranded, with ferrule with plastic sleeve min.  
Conductor cross section stranded, with ferrule with plastic sleeve max.  
Conductor cross section stranded, with ferrule without plastic sleeve min.  
Conductor cross section stranded, with ferrule without plastic sleeve max.
 
2.5 mm²  
Conductor cross section AWG/kcmil min.  
Conductor cross section AWG/kcmil max  
Stripping length  
26  
14  
10 mm  
General  
2.5 kV

rms

(50 Hz, 1 min.)  
2.5 kV

rms

(50 Hz, 1 min.)  
100% operating factor  
IP20 (Relay socket)  
RT I (Relay)  
Test voltage relay winding/relay contact  
Test voltage relay contact/relay contact  
Operating mode  
Degree of protection  
Approx. 10

7

cycles  
Mechanical service life  
Standards/regulations  
DIN EN 50178  
IEC 62103  
Rated insulation voltage  
Pollution degree  
250 V AC  
2
Surge voltage category  
Mounting position  
III  
any  
Assembly instructions  
In rows with zero spacing  
3/7/14 Page
 
3 / 7  

Articles in set  
RIF-4… relay base, for high-power relay with 2 or 3 PDTs or 3 N/O contacts, push-in connection, plug-in option for input/  
suppressor modules, for mounting on NS 35/7,5  
Plug-in high-power relay with power contacts, 3 PDTs, coil voltage: 24 V DC  
Plug-in module, for mounting on RIF-1, RIF-2, RIF-3, and RIF-4, with freewheeling diode and yellow LED, polarity: A1+,  
A2-, input voltage: 12 – 24 V DC ±20%  
Relay retaining bracket, with holder for marking material, suitable for RIF-4 relay base, for high-power relay  
Classifications  
eCl@ss  
eCl@ss 4.0  
eCl@ss 4.1  
eCl@ss 5.0  
eCl@ss 5.1  
eCl@ss 6.0  
eCl@ss 7.0  
27371102  
27371102  
27371601  
27371601  
27371601  
27371601  
3/7/14 Page
 
4 / 7  

Classifications  
eCl@ss  
eCl@ss 8.0  
27371601  
ETIM  
ETIM 3.0  
ETIM 4.0  
ETIM 5.0  
EC001456  
EC001456  
EC001437  
UNSPSC  
UNSPSC 6.01  
UNSPSC 7.0901  
UNSPSC 11  
30211917  
39121516  
39121516  
39121516  
39121516  
UNSPSC 12.01  
UNSPSC 13.2  
Approvals  
Approvals  
Approvals  
CSA  
Ex Approvals  
Approvals submitted  
Approval details  
CSA  
Drawings  
3/7/14 Page
 
5 / 7  

Circuit diagram  
Diagram  
32 22 12  
34 24 14  
1,8  
1,7  
1,6  
1,5  
1,4  
1,3  
1,2  
1,1  
1,0  
0,9  
0,8  
0,7  
0,6  
31 21 11  
A2-  
A1+  
DC coils  
20  
30  
40  
50  
60  
70  
80  
Ambient temperature [°C]  
DC coil (observe contact derating)  
AC coil (observe contact derating)  
Operating voltage range  
Diagram  
Diagram  
11  
10  
20  
10  
9
8
7
6
5
4
3
2
1
6
4
2
1
0,5  
0,3  
0,2  
0,1  
10  
20  
30  
50 70
 
100  
200 300  
20  
30  
40  
50  
60  
70  
80  
Switching voltage [V]  
Ambient temperature [°C]  
DC coil  
AC coil  
AC, ohmic load  
DC, ohmic load  
Contact derating  
Diagram  
Interrupting rating  
Diagram  
7
10  
10  
1
0,9  
0,8  
0,7  
0,6  
0,5  
0,4  
0,3  
6
5
10  
4
10  
0
1
2
3
4
1
0,9  
0,8  
0,7  
0,6  
0,5  
0,4  
0,3  
0,2  
Switching capacity [kVA]  
j
COS  
250 V AC, ohmic load  
!
Electrical service life  
Service life reduction factor  
3/7/14 Page
 
6 / 7  

© Phoenix Contact 2013 – all rights reserved  
3/7/14 Page
 
7 / 7