Phoenix-Contact-2903293
| Part # | Phoenix-Contact-2903293 |
| Download | Phoenix-Contact-2903293 |
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user’s
documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Pre-assembled relay module with push-in connection, consisting of: relay base, power contact relay, plug-in
display/suppressor module, and retaining bracket. Contact type: 3 PDTs. Input voltage: 120 V AC
The figure shows the 24 V DC
version
Key commercial data
Packing unit
1 pc
Custom tariff number
Country of origin
85364900
Germany
Technical data
Dimensions
Width
Height
Depth
40 mm
103 mm
90 mm
Ambient conditions
Ambient temperature (operation)
-40 °C … 50 °C
-40 °C … 85 °C
Ambient temperature (storage/transport)
Coil side
Nominal input voltage U
N
Input voltage range in reference to U
N
Nominal input current at U
IN
Typical response time
120 V AC
(see diagram)
23 mA
5 ms … 15 ms
5 ms … 20 ms
Yellow LED
Varistor
Typical release time range
Operating voltage display
Protective circuit
3/7/14 Page
1 / 6
Technical data
Contact side
Contact type
3 PDTs
Contact material
AgNi
Maximum switching voltage
Minimum switching voltage
Maximum inrush current
Min. switching current
250 V AC/DC
10 V (At 24 mA)
30 A (20 ms, N/O contact)
10 mA (at 24 V)
Limiting continuous current
Interrupting rating (ohmic load) max.
6 A (see diagram)
144 W (at 24 V DC)
124 W (at 48 V DC)
108 W (at 60 V DC)
52 W (at 110 V DC)
48 W (at 220 V DC)
1500 VA (for 250 V AC)
2 A (24 V (DC13))
1.5 A (230 V (AC 15))
Switching capacity in acc. with DIN VDE 0660/IEC 60947
Connection data
Connection method
Push-in connection
0.14 mm²
1.5 mm²
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section stranded min.
0.14 mm²
1.5 mm²
Conductor cross section stranded max.
Conductor cross section stranded, with ferrule with plastic sleeve min.
Conductor cross section stranded, with ferrule with plastic sleeve max.
Conductor cross section stranded, with ferrule without plastic sleeve min.
0.14 mm²
1.5 mm²
0.14 mm²
Conductor cross section stranded, with ferrule without plastic sleeve max.
1.5 mm²
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
Stripping length
26
16
8 mm
General
2.5 kV
rms
(50 Hz, 1 min.)
2 kV
rms
(50 Hz, 1 min.)
100% operating factor
IP20 (Relay socket)
RT I (Relay)
Test voltage relay winding/relay contact
Test voltage relay contact/relay contact
Operating mode
Degree of protection
Approx. 2 x 10
7
cycles
DIN EN 50178
Mechanical service life
Standards/regulations
3/7/14 Page
2 / 6
Technical data
General
IEC 62103
Rated insulation voltage
Pollution degree
250 V AC
2
Surge voltage category
Mounting position
III
any
Assembly instructions
In rows with zero spacing
Articles in set
RIF-3… relay base, for octal relay with 3 PDTs, push-in connection, plug-in option for input/suppressor modules, for
mounting on NS 35/7,5
Pluggable octal relay with power contacts, 3 PDT, test button, mechanical switching position indication, coil voltage 120 V
AC
Plug-in module, for mounting on RIF-1, RIF-2, RIF-3, and RIF-4, with varistor, input voltage: 120 – 230 V AC/DC ±20%
Relay retaining bracket, with holder for marking material, suitable for RIF-3 relay base, for octal relay
3/7/14 Page
3 / 6
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27371102
27371102
27371603
27371603
27371603
27371603
27371603
ETIM
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001456
EC001456
EC001437
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
30211917
39121516
39121516
39121516
39121516
UNSPSC 12.01
UNSPSC 13.2
Approvals
Approvals
Approvals
CSA
Ex Approvals
Approvals submitted
Approval details
CSA
3/7/14 Page
4 / 6
Drawings
Circuit diagram
Diagram
32 22 12
34 24 14
1,8
1,7
1,6
1,5
1,4
1,3
1,2
1,1
1,0
0,9
0,8
0,7
0,6
31 21 11
A2
A1
AC coils
0
10
20
30
40
50
60
70
80
Ambient temperature [°C]
DC coil (observe contact derating)
AC coil (observe contact derating)
Operating voltage range
Diagram
Diagram
11
10
20
10
9
8
7
6
5
4
3
2
1
6
4
2
1
0,5
0,3
0,2
0,1
10
20
30
50 70
100
200 300
20
30
40
50
60
70
80
Switching voltage [V]
Ambient temperature [°C]
AC, ohmic load
DC, ohmic load
DC coil
AC coil
Interrupting rating
Contact derating
3/7/14 Page
5 / 6
Diagram
Diagram
10
7
1
10
6
0,9
0,8
0,7
10
5
0,6
0,5
0,4
10
4
0
0,2 0,4 0,6 0,8 1,0 1,2 1,4 1,6 1,8 2,0 2,2 2,4 2,6
0,3
1
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
Switching capacity [kVA]
j
COS
250 V AC, ohmic load
!
Electrical service life
Service life reduction factor
© Phoenix Contact 2013 – all rights reserved
3/7/14 Page
6 / 6
