Pre-assembled relay module with push-in connection, consisting of: relay base, power contact relay, plug-in  
display/suppressor module, and retaining bracket. Contact type: 2 PDTs. Input voltage: 120 V AC  
The figure shows the 24 V DC  
version  
Key commercial data  
Packing unit  
1 pc  
Weight per Piece (excluding packing)  
Custom tariff number  
Country of origin  
110.0 GRM  
85364900  
Germany  
Technical data  
Dimensions  
Width  
Height  
Depth  
31 mm  
96 mm  
75 mm  
Ambient conditions  
Ambient temperature (operation)  
-40 °C … 50 °C  
-40 °C … 85 °C  
Ambient temperature (storage/transport)  
Coil side  
Nominal input voltage U

N  

Input voltage range in reference to U

N  

Nominal input current at U

IN  

Typical response time  
120 V AC  
(see diagram)  
13 mA  
5 ms … 15 ms  
5 ms … 20 ms  
Yellow LED  
Typical release time range  
Operating voltage display  
3/7/14 Page
 
1 / 6  

Technical data  
Coil side  
Protective circuit  
Varistor  
Contact side  
Contact type  
2 PDT  
Contact material  
AgNi  
Maximum switching voltage  
Minimum switching voltage  
Maximum inrush current  
Min. switching current  
250 V AC/DC  
5 V (At 24 mA)  
30 A (20 ms, N/O contact)  
5 mA (at 24 V)  
Limiting continuous current  
Interrupting rating (ohmic load) max.  
8.5 A (see diagram)  
204 W (at 24 V DC)  
124 W (at 48 V DC)  
108 W (at 60 V DC)  
52 W (at 110 V DC)  
48 W (at 220 V DC)  
2125 VA (for 250 V AC)  
2 A (24 V (DC13))  
1.5 A (230 V (AC 15))  
Switching capacity in acc. with DIN VDE 0660/IEC 60947  
Connection data  
Connection method  
Push-in connection  
0.14 mm²  
1.5 mm²  
Conductor cross section solid min.  
Conductor cross section solid max.  
Conductor cross section stranded min.  
0.14 mm²  
1.5 mm²  
Conductor cross section stranded max.  
Conductor cross section stranded, with ferrule with plastic sleeve min.  
Conductor cross section stranded, with ferrule with plastic sleeve max.  
Conductor cross section stranded, with ferrule without plastic sleeve min.  
0.14 mm²  
1.5 mm²  
0.14 mm²  
Conductor cross section stranded, with ferrule without plastic sleeve max.
 
1.5 mm²  
Conductor cross section AWG/kcmil min.  
Conductor cross section AWG/kcmil max  
Stripping length  
26  
16  
8 mm  
General  
2.5 kV

rms

(50 Hz, 1 min.)  
2.5 kV

rms

(50 Hz, 1 min.)  
100% operating factor  
IP20 (Relay socket)  
RT I (Relay)  
Test voltage relay winding/relay contact  
Test voltage relay contact/relay contact  
Operating mode  
Degree of protection  
3/7/14 Page
 
2 / 6  

Technical data  
General  
Approx. 2 x 10

7

cycles  
Mechanical service life  
Standards/regulations  
DIN EN 50178  
IEC 62103  
Rated insulation voltage  
Pollution degree  
250 V AC  
2
Surge voltage category  
Mounting position  
III  
any  
Assembly instructions  
In rows with zero spacing  
Articles in set  
RIF-2… relay base, for industrial relay with 2 or 4 PDTs, push-in connection, plug-in option for input/suppressor modules,  
for mounting on NS 35/7,5  
Plug-in industrial relay with power contacts, 2 PDTs, test key, status LED, mechanical switch position indicator, input  
voltage: 120 V AC  
Plug-in module, for mounting on RIF-1, RIF-2, RIF-3, and RIF-4, with varistor, input voltage: 120 – 230 V AC/DC ±20%  
3/7/14 Page
 
3 / 6  

Articles in set  
Relay retaining bracket, with ejector function and holder for marking material, suitable for RIF-2 relay base, for industrial  
relay  
Classifications  
eCl@ss  
eCl@ss 4.0  
eCl@ss 4.1  
eCl@ss 5.0  
eCl@ss 5.1  
eCl@ss 6.0  
eCl@ss 7.0  
eCl@ss 8.0  
27371102  
27371102  
27371603  
27371603  
27371603  
27371603  
27371603  
ETIM  
ETIM 3.0  
ETIM 4.0  
ETIM 5.0  
EC001456  
EC001456  
EC001437  
UNSPSC  
UNSPSC 6.01  
UNSPSC 7.0901  
UNSPSC 11  
30211917  
39121516  
39121516  
39121516  
39121516  
UNSPSC 12.01  
UNSPSC 13.2  
Approvals  
Approvals  
Approvals  
CSA  
Ex Approvals  
3/7/14 Page
 
4 / 6  

Approvals  
Approvals submitted  
Approval details  
CSA  
Drawings  
Circuit diagram  
Diagram  
42  
44  
12  
14  
1,8  
1,7  
1,6  
1,5  
1,4  
1,3  
1,2  
1,1  
1,0  
0,9  
0,8  
0,7  
0,6  
41  
11  
A2  
A1  
AC coils  
0
10  
20  
30  
40  
50  
60  
70  
80  
Ambient temperature [°C]  
DC coil (observe contact derating)  
AC coil (observe contact derating)  
Operating voltage range  
Diagram  
Diagram  
11  
10  
20  
10  
9
8
7
6
5
4
3
2
1
6
4
2
1
0,5  
0,3  
0,2  
0,1  
10  
20  
30  
50 70
 
100  
200 300  
20  
30  
40  
50  
60  
70  
80  
Switching voltage [V]  
Ambient temperature [°C]  
AC, ohmic load  
DC, ohmic load  
DC coil  
AC coil  
Interrupting rating  
Contact derating  
3/7/14 Page
 
5 / 6  

Diagram  
Diagram  
7
10  
1
0,9  
6
0,8  
10  
0,7  
0,6  
0,5  
0,4  
5
10  
0
1
2
3
0,3  
1
0,9  
0,8  
0,7  
0,6  
0,5  
0,4  
0,3  
0,2  
Switching capacity [kVA]  
j
COS  
250 V AC, ohmic load  
!
Electrical service life  
Service life reduction factor  
© Phoenix Contact 2013 – all rights reserved  
3/7/14 Page
 