Phoenix-Contact-2908046

Part #Phoenix-Contact-2908046
Download 
Phoenix-Contact-2908046
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user’s  
documentation. Our General Terms of Use for Downloads are valid  
(http://phoenixcontact.com/download)  
Plug-in high-power relay with power contacts, specifically for switching high DC loads, 1 N/O contact, blowout  
magnet, coil voltage: 220 V DC  
The figure shows version REL-  
PR1-24DC/1/MB  
Key Commercial Data  
Packing unit  
1 STK  
Weight per Piece (excluding packing)  
Custom tariff number  
Country of origin  
80.000 g  
85364900  
Poland  
Technical data  
Dimensions  
Width  
Height  
Depth  
38.6 mm  
45.5 mm  
36.1 mm  
Ambient conditions  
Ambient temperature (operation)  
-40 °C … 70 °C  
-40 °C … 85 °C  
Ambient temperature (storage/transport)  
Coil side  
Nominal input voltage U

N  

Input voltage range in reference to U

N  

Typical input current at U

N  

Typical response time  
220 V DC  
see diagram  
7.3 mA  
20 ms  
Typical release time  
15 ms  
09/30/2016 Page
 
1 / 4  

Technical data  
Contact side  
Contact type  
1 N/O contact  
Single contact  
AgNi  
Type of switch contact  
Contact material  
Maximum switching voltage  
440 V AC  
350 V DC  
Minimum switching voltage  
Min. switching current  
5 V (At 24 mA)  
5 mA (at 24 V)  
50 A (20 ms)  
Maximum inrush current  
30 A (4 s)  
Limiting continuous current  
16 A  
Interrupting rating (ohmic load) max.  
384 W (at 24 V DC)  
768 W (at 48 V DC)  
930 W (at 60 V DC)  
1650 W (at 110 V DC)  
2640 W (at 220 V DC)  
4000 VA (for 250 V AC)  
120 mW  
Switching capacity min.  
Switching capacity in acc. with DIN VDE 0660/IEC 60947  
1 A (at 220 V, DC13)  
1.5 A (at 240 V, AC15)  
General  
Test voltage relay winding/relay contact  
Operating mode  
2.5 kV  
100% operating factor  
RT I  
Degree of protection  
Mechanical service life  
Degree of pollution  
Approx. 2 x 10

7

cycles  
3
Overvoltage category  
Designation  
III  
Standards/regulations  
IEC 61810  
Standards/regulations  
Mounting position  
any  
Standards and Regulations  
Rated surge voltage  
Degree of pollution  
Overvoltage category  
Designation  
4 kV  
3
III  
Standards/regulations  
IEC 61810  
Standards/regulations  
09/30/2016 Page
 
2 / 4  

Classifications  
eCl@ss  
eCl@ss 4.0  
eCl@ss 4.1  
eCl@ss 5.0  
eCl@ss 5.1  
eCl@ss 6.0  
eCl@ss 7.0  
eCl@ss 8.0  
eCl@ss 9.0  
27371104  
27371104  
27371601  
27371601  
27371601  
27371601  
27371601  
27371601  
ETIM  
ETIM 2.0  
ETIM 3.0  
ETIM 4.0  
ETIM 5.0  
EC001437  
EC001437  
EC001437  
EC001437  
UNSPSC  
UNSPSC 6.01  
UNSPSC 7.0901  
UNSPSC 11  
30211916  
39121515  
39121515  
39121515  
39121515  
UNSPSC 12.01  
UNSPSC 13.2  
Approvals  
Approvals  
Approvals  
EAC  
Ex Approvals  
Approval details  
EAC 7500651.22.01.00244  
09/30/2016 Page
 
3 / 4  

Accessories  
Additional products  
RIF-4… relay base, for high-power relay with 2 or 3 PDTs or 3 N/O contacts, push-in connection, plug-in option for input/  
suppressor modules, for mounting on NS 35/7,5  
Phoenix Contact 2016 © – all rights reserved  