Phoenix-Contact-2912604
| Part # | Phoenix-Contact-2912604 |
| Download | Phoenix-Contact-2912604 |
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user’s
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
PLC-INTERFACE, consisting of PLC-BSP…/21-21AU basic terminal block with spring-cage connection and plug-
in miniature relay with multi-layer gold contact, for mounting on DIN rail NS 35/7,5, 2 PDTs, input voltage 60 V DC
Product Features
Slim design
Efficient connection to system cabling using V8 adapter
RT III sealed relay
Safe isolation according to DIN EN 50178 between coil and contact
Integrated input circuit and interference suppression circuit
Functional plug-in bridges
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
61.2 GRM
85364190
Germany
Technical data
Note
EMC: class A product, see manufacturer’s declaration in the download
area
Utilization restriction
Dimensions
Width
Height
Depth
14 mm
80 mm
94 mm
Ambient conditions
10/27/2014 Page
1 / 6
Technical data
Ambient conditions
Ambient temperature (operation)
-40 °C … 60 °C
-40 °C … 85 °C
Ambient temperature (storage/transport)
Coil side
Nominal input voltage U
N
Typical input current at U
N
Typical response time
Typical release time
60 V DC
10 mA
8 ms
10 ms
Operating voltage display
Protective circuit
Yellow LED
Protection against polarity reversal Polarity protection diode
Free-wheeling diode Damping diode
Contact side
Contact type
2 PDT
Contact material
AgNi, hard gold-plated
30 V AC
Maximum switching voltage
36 V DC
Minimum switching voltage
Maximum inrush current
Min. switching current
100 mV (at 10 mA)
50 mA
1 mA (at 24 V)
Limiting continuous current
Interrupting rating (ohmic load) max.
Note
50 mA
1.2 W (at 24 V DC)
the following values are applicable if a gold layer is destroyed
250 V AC/DC
Maximum switching voltage
Minimum switching voltage
Limiting continuous current
Maximum inrush current
Min. switching current
5 V AC/DC
6 A
15 A (300 ms)
10 mA
Interrupting rating (ohmic load) max.
140 W (at 24 V DC)
85 W (at 48 V DC)
60 W (at 60 V DC)
44 W (at 110 V DC)
60 W (at 220 V DC)
1500 VA (for 250 V AC)
2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.2 A (at 250 V, DC13)
2 A (at 24 V, AC15)
Switching capacity in acc. with DIN VDE 0660/IEC 60947
10/27/2014 Page
2 / 6
Technical data
Contact side
2 A (at 120 V, AC15)
2 A (at 250 V, AC15)
General
Operating mode
100% operating factor
RT III (Relay)
Degree of protection
Mechanical service life
Inflammability class according to UL 94
Designation
3 x 10
7
cycles
V0
Standards/regulations
Standards/regulations
IEC 60664
EN 50178
IEC 62103
Rated surge voltage / insulation
Pollution degree
6 kV / Basic isolation
2
Surge voltage category
Mounting position
III
any
Assembly instructions
In rows with zero spacing
Connection data
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section AWG/kcmil max
Conductor cross section AWG/kcmil min.
0.14 mm²
2.5 mm²
0.14 mm²
2.5 mm²
14
26
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27371102
27371102
27371001
27371001
27371001
27371001
27371001
10/27/2014 Page
3 / 6
Classifications
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000196
EC000196
EC000196
EC000196
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
30211916
39121515
39121515
39121515
39121515
UNSPSC 12.01
UNSPSC 13.2
Approvals
Approvals
Approvals
UL Listed / cUL Listed / GL / UL Recognized / cUL Recognized / cULus Recognized / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
GL
10/27/2014 Page
4 / 6
Approvals
UL Recognized
cUL Recognized
cULus Recognized
cULus Listed
Drawings
Circuit diagram
21
24
22
A2
A1
11
14
12
10/27/2014 Page
5 / 6
Diagram
Curve A
Maximum permissible continuous voltage U
max
with limiting continuous current on the contact side (see relevant technical data)
Curve B
Minimum permissible operate voltage U
op
after pre-excitation (see relevant technical data)
Phoenix Contact 2014 © – all rights reserved
10/27/2014 Page