Schneider-ABE7R16T330
| Part # | Schneider-ABE7R16T330 |
| Download | Schneider-ABE7R16T330 |
Product data sheet
Characteristics
ABE7R16T330
Sub-base with plug-in electromechanical relay
ABE7 – 16 channels – relay 12.5 mm
Main
Range of Product
Modicon ABE7
Product or Component
Type
Sub-base with plug-in electromechanical relay
Sub-base type
Output sub-base
[Us] rated supply
voltage
19…30 V IEC 61131-2
Number of Channels
16
Complementary
Supply voltage type
Product Compatibility
Contacts type and composition
Status LED
DC
ABR7S33
1 C/O
Channel status 1 LED per channel Green)
Power ON 1 LED Green)
Polarity distribution
Short-circuit protection
Fixing mode
Volt-free
1 A internal fuse, 5 x 20 mm, fast blow PLC end)
By clips 35 mm symmetrical DIN rail)
By screws solid plate with fixing kit)
Maximum supply current
1 A
Voltage drop on power supply fuse
[Ui] rated insulation voltage
0.3 V
2000 V terminals/mounting rails
300 V coil circuit/contact circuits IEC 60947-1
[Uimp] rated impulse withstand voltage
Installation category
Tightening torque
2.5 kV
II IEC 60664-1
5.31 lbf.in (0.6 N.m) flat Ø 3.5 mm
2.87 lb(US) (1.3 kg)
Net Weight
Environment
Product Certifications
UL
CSA
BV
DNV
GL
LROS (Lloyds register of shipping)
EAC
IP degree of protection
IP2x conforming to IEC 60529
1382 °F (750 °C) IEC 60695-2-11
15 gn 11 ms IEC 60068-2-27
2 gn 10…150 Hz)IEC 60068-2-6
Resistance to incandescent wire
Shock resistance
Vibration resistance
Resistance to electrostatic discharge
4 KV contact) level 3 IEC 61000-4-2
8 kV air) level 3 IEC 61000-4-2
Resistance to radiated fields
Resistance to fast transients
Ambient air temperature for operation
Ambient air temperature for storage
Pollution degree
9.14 V/m (10 V/m) 26000000…1000000000 Hz)IEC 61000-4-3 level 3
2 kV level 3 IEC 61000-4-4
23…140 °F (-5…60 °C) IEC 61131-2
-40…176 °F (-40…80 °C) IEC 61131-2
2 IEC 60664-1
Jan 12, 2022
1
Ordering and shipping details
Category
22375 – INTERFACE MODULE(ABA,R,S)
Discount Schedule
GTIN
CP2
3389110705096
Nbr. of units in pkg.
Package weight(Lbs)
Returnability
1
2.43 lb(US) (1.103 kg)
Yes
LV
Country of origin
Packing Units
Unit Type of Package 1
PCE
Package 1 Height
3.39 in (8.6 cm)
3.94 in (10 cm)
11.50 in (29.2 cm)
S03
Package 1 width
Package 1 Length
Unit Type of Package 2
Number of Units in Package 2
Package 2 Weight
Package 2 Height
6
15.47 lb(US) (7.018 kg)
11.81 in (30 cm)
11.81 in (30 cm)
15.75 in (40 cm)
Package 2 width
Package 2 Length
Offer Sustainability
Sustainable offer status
California proposition 65
Green Premium product
WARNING: This product can expose you to chemicals including: Lead and
lead compounds, which is known to the State of California to cause cancer
and birth defects or other reproductive harm. For more information go to
REACh Regulation
Yes
REACh free of SVHC
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
Circularity Profile
WEEE
The product must be disposed on European Union markets following specific
waste collection and never end up in rubbish bins.
Contractual warranty
Warranty
18 months
2
Product data sheet
Dimensions Drawings
ABE7R16T330
Dimensions
(1) ABE7BV10
/ BV20, ABE7BV10E / BV20E
3
Product data sheet
Mounting and Clearance
ABE7R16T330
Mounting
4
Product data sheet
Connections and Schema
ABE7R16T330
HE10 16 Channels
Wiring Diagram with Supplied Relays
(1) Inductive
load
(2) ABR7S33
(1 “OF” “DPDT”) Ith = 10 A (supplied)
Wiring Diagram
5
(1) Inductive
load
(2) ABR7S33
(1 “OF” “DPDT”) Ith = 10 A (supplied)
(3) ABR7S37
(2 “OF” “DPDT”) Ith = 8 A (supplied)
(4) ABS7SC3E
(5…48 VDC) Imax. = 1.5 A (not supplied)
(5) ABS7SA3M
(24…240 VAC) Imax. = 1.5 A (not supplied)
(6) ABS7SC3BA
(24 VDC) Imax. = 2 A (not supplied)
(7) ABE7ACC21
(24 VDC) Imax. = 0.5 A (not supplied)
6
Product data sheet
Performance Curves
ABE7R16T330
Curves for Determining Cable Type and Length According to the Current
16-channel Sub-base
L
Cable length
I
T
Total current per sub base (A)
I
A
(1)
Average current per channel (mA)
TSXCDP••2 and ABFH20H••0 cables with c.s.a. 0.08 mm
2
(AWG 28).
TSXCDP••3 cables with c.s.a. 0.34 mm
2
(AWG 22).
Cables with c.s.a. 0.13 mm
2
(AWG 26).
(2)
(3)
The curves are given for a voltage drop of 1 V in the cable. For n volts tolerance, multiply the length determined from the graph by n.
Temperature Derating Curves
(1) 100
% of channels used
(2) 50
% of channels used
Electrical Durability (in Millions of Operating Cycles) Conforming to IEC 60947-5-1
DC Loads
DC12 curves
DC12control of resistive loads and of solid state loads isolated by optocoupler, l/R ≤ 1 ms.
7
DC13 curves
DC13 Switching
electromagnets, L/R ≤ 2 x (Ue x Ie) in ms, Ue: rated operational voltage, Ie: rated operational current
(with a protective diode on the load, DC12 curves must be used with a coefficient of 0.9 applied to the number in millions of
operating cycles)
AC Loads
AC12 curves
AC12control of resistive loads and of solid state loads isolated by optocoupler, cos ϕ ≥ 0.9.
AC14 curves
AC14control of small electromagnetic loads ≤ 72 VA, make: cos ϕ = 0.3, break: cos ϕ = 0.3.
AC15 curves
AC15control of electromagnetic loads > 72 VA, make: cos ϕ = 0.7, break: cos ϕ = 0.4.
8