Schneider-RSL1GB4BD
| Part # | Schneider-RSL1GB4BD |
| Download | Schneider-RSL1GB4BD |
Product data sheet
Characteristics
RSL1GB4BD
Harmony, Slim interface plug-in relay, 6 A, 1
CO, low level, 24 V DC
Main
Range of Product
Harmony Electromechanical Relays
Slim interface relay
Series name
Product or Component
Type
Plug-in relay
Device short name
RSL
Contacts type and
composition
1 C/O
Contact operation
Low level
24 V DC
[Uc] control circuit
voltage
[Ithe] conventional
enclosed thermal
current
6 A -40…131 °F (-40…55 °C)
Status LED
Without
Control Type
Without push-button
Complementary
Shape of pin
Flat (PCB type)
Average resistance
3390 Ohm at 73 °F (23 °C) +/- 15 %
18…33.6 V DC
Rated operational voltage limits
[Ui] rated insulation voltage
250 V EN/IEC
277 V cUL
[Uimp] rated impulse withstand voltage
Contacts material
6 kV IEC
Silver alloy – gold plated (AgSnO2)
[Ie] rated operational current
Minimum switching current
Maximum switching voltage
Minimum switching voltage
Maximum switching capacity
6 A AC-1/DC-1)IEC/UL
1 mA
277 V
24 V
1500 VA
50 W
Minimum switching capacity
Operating rate
24 mW
<= 360 cycles/hour under load
<= 18000 cycles/hour no-load
Mechanical durability
Electrical durability
Operating time
10000000 cycles
60000 cycles, 6 A at 250 V, AC-1 C/O
5 ms reset
12 ms
Protection category
Test levels
RT III
Level A
Operating position
Width
Any position
0.20 in (5 mm)
1.10 in (28 mm)
0.73 in (18.5 mm)
Height
Depth
Terminals description ISO n°1
(A1-A2)CO
(11-12-14)OC
Net Weight
0.01 lb(US) (0.0054 kg)
6 A 250 V AC 0.5 mm mounting distance
0.17 W
Load current
Average coil consumption
Drop-out voltage threshold
Safety reliability data
>= 0.05 Uc
B10d = 60000
Jul 8, 2022
1
Mounting Support
Socket or PCB
Device presentation
Complete product
Environment
Dielectric strength
1000 V AC between contacts
4000 V AC between coil and contact
Standards
UL 508
CSA C22.2 No 14
EN/IEC 61810-1
Product Certifications
EAC
CSA
UL
Ambient Air Temperature for Storage
Vibration resistance
-40…158 °F (-40…70 °C)
+/- 1 mm 10…55 Hz)EN/IEC 60068-2-6
IP40 conforming to EN/IEC 60529
IP degree of protection
Shock resistance
5 gn 11 ms) not operating EN/IEC 60068-2-27
5 gn 11 ms) in operation EN/IEC 60068-2-27
Ambient air temperature for operation
-40…131 °F (-40…55 °C)
Ordering and shipping details
Category
21127-ZELIO ICE CUBE RELAYS
Discount Schedule
GTIN
CP2
3606480077968
Nbr. of units in pkg.
Package weight(Lbs)
Returnability
1
0.18 oz (5.0 g)
No
Packing Units
Unit Type of Package 1
PCE
Package 1 Height
0.20 in (0.5 cm)
0.79 in (2 cm)
1.18 in (3 cm)
BB1
Package 1 width
Package 1 Length
Unit Type of Package 2
Number of Units in Package 2
Package 2 Weight
Package 2 Height
10
2.50 oz (71.0 g)
0.39 in (1 cm)
0.98 in (2.5 cm)
11.81 in (30 cm)
S01
Package 2 width
Package 2 Length
Unit Type of Package 3
Number of Units in Package 3
Package 3 Weight
Package 3 Height
250
4.23 lb(US) (1.92 kg)
5.91 in (15 cm)
5.91 in (15 cm)
15.75 in (40 cm)
Package 3 width
Package 3 Length
Offer Sustainability
California proposition 65
WARNING: This product can expose you to chemicals including: Nickel
compounds, which is known to the State of California to cause cancer, and
Di-isodecyl phthalate (DIDP), which is known to the State of California to
cause birth defects or other reproductive harm. For more information go to
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Mercury free
Yes
Yes
RoHS exemption information
China RoHS Regulation
2
Environmental Disclosure
Circularity Profile
Contractual warranty
Warranty
18 months
3
Product data sheet
Dimensions Drawings
RSL1GB4BD
Dimensions
Relay with Flat Pins (PCB Type)
(1): 5.04 mm / 0.19 in.
4
Product data sheet
Connections and Schema
RSL1GB4BD
Wiring Diagram
Relay with Flat Pins (PCB Type)
1 C/O contact
5
Product data sheet
Performance Curves
RSL1GB4BD
Curves for Resistive Load
Maximum Switching Capacity on DC Load
Resistive load
X DC Current
Y DC Voltage
Electrical Durability
Only tested at 6A/250VAC, projection for the rest
250 Vac Resistive load
X Switching current (A)
Y Cycles
Note :
These are typical curves, actual durability depends on load, environment, duty cycle, etc.
6