Schneider-RXG25B7
| Part # | Schneider-RXG25B7 |
| Download | Schneider-RXG25B7 |
Product data sheet
Characteristics
RXG25B7
Harmony, Interface plug-in relay, 5 A, 2 CO,
clear cover, 24 V AC
Main
Range of Product
Harmony Electromechanical Relays
Interface relay
Series name
Product or Component
Type
Plug-in relay
Device short name
RXG
Contacts type and
composition
2 C/O
Complementary
Contacts material
Silver alloy (AgSnO2In2O3)
100 mOhm
Maximum contact resistance
[Ithe] conventional enclosed thermal current
[Ie] rated operational current
5 A -40…131 °F (-40…55 °C)
5 A 30 V DC) UL
5 A 30 V DC) IEC
5 A 250 V AC) IEC
5 A 250 V AC) UL
Maximum switching voltage
250 V AC
30 V DC
Load current
5 A 250 V AC
Maximum switching capacity
Minimum switching capacity
Operating rate
1250 VA
50 mW at 10 mA, 5 V DC
<= 1800 cycles/hour under load
<= 18000 cycles/hour no-load
Utilisation coefficient
Mechanical durability
Electrical durability
20 %
10000000 cycles
100000 Cycles NO resistive at 55 °C
100000 cycles NC resistive at 55 °C
[Ui] rated insulation voltage
250 V IEC
300 V CSA
300 V UL
[Uimp] rated impulse withstand voltage
Dielectric strength
6 kV 1.2/50 µs
1000 V AC between contacts with micro disconnection
5000 V AC between coil and contact with reinforced insulation
3000 V AC between poles with basic insulation
Coil resistance
260 Ohm +/- 10 %
1000 MOhm at 500 V DC
Level A
Insulation resistance
Test levels
Mounting position
Any position
0.82 VA 60 Hz
>= 0.3 Uc AC
0.8…1.1 Uc AC
Class F
Average consumption in VA
Drop-out voltage threshold
Control circuit voltage limits
Coil insulation class
Operate time
20 ms
Release time
20 ms
[Uc] control circuit voltage
Safety reliability data
24 V AC 50/60 Hz
B10d = 100000
Jan 12, 2022
1
Colour of cover
Torque Value
Transparent
7.08 lbf.in (0.8 N.m)
0.04 lb(US) (0.019 kg)
Complete product
Net Weight
Device presentation
Environment
Vibration resistance
3 gn +/- 0.75 mm 10…150 Hz)in operation
5 gn +/- 0.75 mm 10…150 Hz)not in operation
IP Degree of Protection
Shock resistance
IP40
20 gn in operation
100 gn not in operation
Protection category
Standards
RT I
UL 508
CSA C22.2 No 14
IEC 61810-1
Product Certifications
UL
CE
EAC
CSA
DNV-GL
Pollution degree
2
Overvoltage category
III
Ambient Air Temperature for Storage
Ambient air temperature for operation
Relative humidity
-40…185 °F (-40…85 °C)
-40…158 °F (-40…70 °C)
10…85 %
Ordering and shipping details
Category
21127 – ZELIO ICE CUBE RELAYS
Discount Schedule
GTIN
CP2
3606480689321
Nbr. of units in pkg.
Package weight(Lbs)
Returnability
1
7.72 oz (219 g)
Yes
CN
Country of origin
Packing Units
Unit Type of Package 1
PCE
Package 1 Height
1.36 in (34.5 mm)
3.64 in (92.5 mm)
3.39 in (86 mm)
BB1
Package 1 width
Package 1 Length
Unit Type of Package 2
Number of Units in Package 2
Package 2 Weight
Package 2 Height
10
7.34 oz (208 g)
1.38 in (3.5 cm)
2.95 in (7.5 cm)
3.43 in (8.7 cm)
S01
Package 2 width
Package 2 Length
Unit Type of Package 3
Number of Units in Package 3
Package 3 Weight
Package 3 Height
240
11.50 lb(US) (5.217 kg)
5.91 in (15 cm)
5.91 in (15 cm)
15.75 in (40 cm)
Package 3 width
Package 3 Length
2
Offer Sustainability
Sustainable offer status
California proposition 65
Green Premium product
WARNING: This product can expose you to chemicals including: Nickel
compounds, which is known to the State of California to cause cancer, and
Di-isodecyl phthalate (DIDP), which is known to the State of California to
cause birth defects or other reproductive harm. For more information go to
REACh Regulation
Yes
REACh free of SVHC
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Mercury free
Yes
Yes
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
3
Product data sheet
Dimensions Drawings
RXG25B7
Dimensions
4
Product data sheet
Connections and Schema
RXG25B7
Wiring Diagram
5
Product data sheet
Performance Curves
RXG25B7
Performance Curves
Maximum Switching Capacity
X : Switching voltage (V)
Y : Switching current (A)
(1) AC Resistive Load
(2) AC Inductive Load cos(Ø)=0.4
(3) DC Resistive Load
(4) DC Inductive Load (L/R=7ms)
Life Expectancy
Resistive Load
X : Contact Current (A)
Y : Operating Cycle Number
Life Expectancy
Inductive Load
X : Contact Current (A)
Y : Operating Cycle Number
NOTE: These are typical curves, actual durability depends on load, environment, duty cycle, etc.
Coil Operating Range
6
AC Coil Operating Range VS Ambient Temperature
X : Ambient temperature (°C)
Y : Coil voltage (U/Uc)
(1) Permitted operating range area