TDK-B84143A0020R107

Part #TDK-B84143A0020R107
Download 
TDK-B84143A0020R107
EMC filters  
3-line filters  
for converters and power electronics  
Series/Type:  
B84143A*R107  
Date:  
June
2021  
TDK Electronics AG 2021. Reproduction, publication and dissemination of this publication, enclosures hereto  
and the information contained therein without TDK Electronics’ prior express consent is prohibited.  

3-line filters  
B84143A*R107  
for converters and power electronics  
Power line filters for 3-phase systems  
Rated voltage V

R

: 300/520 V AC  
Rated current I

R

: 10 A to 100 A  
Construction  
3-line filters  
Metal case  
Schematic picture  
Features  
High insertion loss  
Optimized leakage current  
Discharge time < 60 V in 1 s for V

R

(L-L)
≤
400 V  
Easy to install  
Low weight  
Compact design  
Degree of protection: IP 20

1)  

Short circuit current rating SCCR:  
35 A … 100 A: 50 kA  
ENEC, UL and cUL approval  
Typical applications  
Frequency converters for motor drives, e.g.  
– elevators  
– pumps  
– conveyor
 
systems  
– HVAC
 
systems (heating, ventilation and air conditioning)  
Power supplies  
Textile machines, packaging machines, machine-tools  
Terminals  
Finger-safe terminals  
Marking  
Marking on component:  
Manufacturer’s logo, ordering code, rated voltage, rated  
current, rated temperature, climatic category, date code,  
approvals, SCCR value  
Minimum data on packaging:  
Manufacturer’s logo, ordering code, quantity, date code  
1) According
 
to IEC 60529  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
2
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
Typical circuit diagrams  
Technical data and measuring conditions  
Rated voltage V

R  

300/520 V AC (50/60 Hz)  
265/460 V AC (50/60 Hz)  
See also chapter “Technical information”, section 8 “Energy  
supply networks”.  
Rated voltage for IT mains  
supply  
Rated current I

R  

T
e
st voltage V

test  

Referred to 50
°
C rated temperature  
2236 V DC, 2 s (line/line)  
2720 V DC, 2 s (line/case)  
Overload capability (thermal)  
1.5 I

R

for 3 min per hour or  
2.5 I

R

for 30 s per hour  
Leakage current l

LK  

Climatic category (IEC 60068-1)  
Approvals  
At V

R

and 50 Hz  
25/100/21 (-25
°
C/+100
°
C/21 days damp heat test)  
IEC 60939, UL 1283, CSA C22.2 No.8  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
3
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
Characteristics and ordering codes  
I

R  

Terminal cross
 
I

LK  

section  
R

typ  

Approx.  
weight  
Ordering code  
Approvals  
A
mm

2  

mA  
m
Ω  
kg  
V

R

= 300/520 V AC  
10  
20  
35  
50  
65  
80  
4
3.1  
3.1  
3.4  
3.4  
3.4  
3.4  
3.4  
5.5  
3.3  
1.7  
1.1  
0.4  
0.6  
0.9  
1.4  
B84143A0010R107  
B84143A0020R107  
B84143A0035R107  
B84143A0050R107  
B84143A0065R107  
B84143A0080R107  
B84143A0100R107  
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
4
10  
25  
25  
25  
0.94 1.9  
0.60 2.4  
0.48 2.9  
100 50  
x = Approval granted  
SCCR values  
50 kA for 35 A … 65 A types, nominal values of circuit breaker  
80 A and V

[L–PE / L–L]

min. 347/600 V  
50 kA for 80 A … 100 A types, nominal values of circuit breaker  
125 A and V

[L–PE / L–L]

min. 347/600 V  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
4
6/
21  

3-line filters  
B84143A*R107  
for converters and power electronics  
Dimensional drawings  
B84143A0010R107, B84143A0020R107 (10 A, 20 A)  
General tolerances according to ISO 2768-cL  
Dimensions in mm  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
5
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
B84143A0035R107 (35 A)  
General tolerances according to ISO 2768-cL  
Dimensions in mm  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
6
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
B84143A0050R107, B84143A0065R107 (50 A, 65 A)  
General tolerances according to ISO 2768-cL  
Dimensions in mm  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
7
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
B84143A0080R107 (80 A)  
General tolerances according to ISO 2768-cL  
Dimensions in mm  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
8
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
B84143A0100R107 (100 A)  
General tolerances according to ISO 2768-cL  
Dimensions in mm  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
9
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
Insertion loss
(typical values at Z = 50
Ω
)  
unsymmetrical, adjacent branches terminated  
common mode, all branches in parallel (asymmetrical)  
differential mode (symmetrical)  
. . . . .  
Filters for 10 A  
Filters for 20 A  
Filters for 35 A  
Filters for 50 A  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
10
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
Insertion loss
(typical values at Z = 50
Ω
)  
unsymmetrical, adjacent branches terminated  
common mode, all branches in parallel (asymmetrical)  
differential mode (symmetrical)  
. . . . .  
Filters for 65 A  
Filters for 80 A  
Filters for 100 A  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
11
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
Cautions and warnings  
Please read all warning and safety notes carefully before installing the filter and putting it into op-  
eration (see
 
). The same applies to the warning signs on the filter. Please ensure that the signs  
are not removed nor their legibility impaired by external influences.  
Death, serious bodily injury and substantial material damage to equipment may occur if the appro-  
priate safety measures are not carried out or the warnings in the text are not observed.  
Using according to the terms  
The filters may be used only for their intended application within the specified values in low-  
voltage networks in compliance with the instructions given in the data sheets and the data book.  
The conditions at the place of application must comply with all specifications for the filter used.  
Warning  
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such  
as planning, assembly, installation, operation, repair and maintenance. They must be provided  
with the corresponding documentation.  
Danger of electric shock. Filters contain components that store an electric charge. Dangerous  
voltages can continue to exist at the filter terminals for longer than five minutes even after the  
power has been switched off.  
The protective earth connections shall be the first to be made when the filter is installed and the  
last to be disconnected. Depending on the magnitude of the leakage currents, the particular  
specifications for making the protective earth connection must be observed.  
Impermissible overloading of the filter or filter, such as with circuits able to cause resonances,  
impermissible voltages at higher frequencies etc. can lead to bodily injury and death as well as  
cause substantial material damages (e.g. destruction of the filter housing).  
Filters must be protected in the application against impermissible exceeding of the rated cur-  
rents by overcurrent protective devices.  
In case of leakage currents >3.5 mA you shall mount the PE conductor stationary with the re-  
quired cross section before beginning of operation and save it against disconnecting. For leak-  
1)  
age currents I

L

≤
10 mA the PE conductor must have a KU value

2)

of 4.5

3
)

; for leakage currents  
I

L

>10 mA the PE conductor must have a KU value of 6

4)

.
 
Output chokes and output filters must be protected in the application against impermissible ex-  
ceeding of the component temperature.  
The converter output frequency must be within the specified range to avoid resonances and un-  
controlled warming of the output chokes and output filters.  
Because the product can become very hot during operation, there is the risk of burns if  
touched. The product can remain hot for some time after the power is switched off!  
1) I =
 
leakage current let-go  
L
2) The
 
KU value (symbol KU) is a classification parameter of safety-referred failure types designed to ensure protection  
against hazardous body currents and excessive heating.  
3) A
 
value of KU = 4.5 with respect to interruptions is attained with: a) permanently connected protective earth connection  
2
2
≥
1.5 mm
 
and b) a protective earth connection
≥
2.5 mm
 
via connectors for industrial equipment (IEC 60309-2)  
2
4) KU
 
= 6 with respect to interruptions is achieved for fixed-connection lines
≥
10 mm
 
where the type of connection and  
installation correspond to the requirements for PEN conductors as specified in relevant standards.  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
12
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
The table below summarizes the safety instructions that must be observed without fail. A detailed  
description can be found in the relevant chapters of the databook.  
Topic  
Instructions  
Referenc
e
c
hapter  
(data book),  
paragraph  
Selecting a filter  
When selecting a filter, it is mandatory to observe the
 
Selection guide for  
rated data of the equipment (such as its rated input cur-
 
converter filters  
rent, rated voltage, harmonic content etc.) as well as  
the derating instructions in Chapters 9 and 10.  
Rated voltage  
When power distribution systems deviating from the
 
Power distribution  
symmetric TN-S system is to check the suitability of the
 
systems,  
filters and the allowed voltages including the fault
 
7  
cases.  
Protection from  
residual voltages  
Active parts must be discharged within 5 s to a volt-
 
Safety regulations,  
age of less than 60 V (or 50 µC). If this limit
 
cannot 6.1  
Discharge resistors
 
be observed due to the operating mode, the hazard-  
ous point must be permanently marked in a
 
clearly  
visible way.  
Filters which are not permanently connected (e.g. Safety
 
regulations,  
when the test voltage is applied to the filter at the
 
6.2  
incoming goods inspection) must be discharged after  
the voltage has been switched off.  
Installing and  
When installing and removing our filters, a voltage-free
 
Safety regulations,  
removing of filters
 
state must be set up and secured with
 
observance 6.4  
of the five safety
 
rules described in
 
EN 50110-1.  
Installation  
Use in IT systems
 
The special features of the IT system (“first fault case”
 
Power distribution  
and other fault cases) shall be observed.  
system  
(network types),  
7.6  
Safety notes on  
leakage currents  
The filter leakage currents specified in the data book
 
Leakage current,  
are intended for user information only.The maximum
 
8.4  
leakage current of the entire electrical equipment or  
Leakage current,  
appliance has to be limited for safety reasons. Please  
8.6  
obtain the applicable limits for your application from  
the relevant regulations, provisions and standards.  
Voltage derating  
If the permissible limits for the higher-frequency
 
volt- Voltage
 
derating,  
ages at the filter are exeeded, the filter may be 9.8  
damaged or destroyed.  
Hazards caused by  
overloading the  
filters  
Current derating at
 
Non-observance of the current derating may lead to
 
Current derating,  
elevated ambient  
temperatures  
overheating and consequently represents a fire 10.1  
hazard.  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
13
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
Topic  
Instructions  
Referenc
e
c
hapter  
(data book),  
paragraph  
Protective earth  
connection at  
For operating currents greater than 250 A, we
 
re- Mounting  
commend the PE connection to be set up between the
 
instructions,  
operating currents
 
feed (filter: line) and output (filter: load) not via the
 
point 2  
>250 A  
PE terminal bolt in the filter housing.  
Mounting position  
Note the mounting position of the filters! It must al-
 
Mounting  
ways be ensured that natural convection is not im-
 
instructions,  
paired.  
point 13  
Long motor cables
 
Long motor cables cause parasitic currents in the in-
 
Mounting  
stallation. The cable lengths indicated for the output
 
instructions,  
chokes and output filters serve for orientation. The user
 
point 15  
must check the technical parameters and especially  
the choke temperatures for the respective application.  
Display of ordering codes for TDK Electronics products  
The ordering code for one and the same product can be represented differently in data sheets, data  
books, other publications, on the company website, or in order-related documents such as shipping  
notes, order confirmations and product labels.
The varying representations of the ordering  
codes are due to different processes employed and do not affect the specifications of the  
respective products
.  
Detailed information can be found on the Internet under  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
14
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
Symbols and terms  
Symbol English  
German  
α
Insertion loss  
Einfügungsdämpfung  
Bemessungskapazität  
C

R  

C

X  

C

Y  

Δ
V  
dv/dt  
f
Rated capacitance  
Capacitance X capacitor  
Capacitance Y capacitor  
Voltage drop (input to output)  
Rate of voltage rise  
Frequency  
Kapazität X-Kondensator  
Kapazität Y-Kondensator  
Spannungsabfall (Eingang zu Ausgang)  
Spannungsanstiegsgeschwindigkeit  
Frequenz  
f

M  

Converter output frequency  
Pulse frequency  
Motorfrequenz  
f

P  

Pulsfrequenz  
f

R  

Rated frequency  
Bemessungsfrequenz  
Resonanzfrequenz  
Strom durch Kondensator  
Filter-Ableitstrom  
f

res  

I

C  

Resonant frequency  
Current through capacitor  
Filter leakage current  
Maximum current  
I

LK  

I

max  

I

N  

Maximalstrom  
Nominal current  
Nennstrom  
I

op  

I

pk  

Operating current (design current)  
Rated peak withstand current  
Capacitive reactive current  
Rated current  
Betriebsstrom  
Bemessungsstoßstromfestigkeit  
Kapazitiver Blindstrom  
Bemessungsstrom  
I

q  

I

R  

I

S  

Interference current  
Inductance  
Störstrom  
L
Induktivität  
L

R  

Rated inductance  
Bemessungsinduktivität  
Streuinduktivität  
L

stray  

P

L  

Stray inductance  
Power loss  
Verlustleistung  
R
Resistance  
Widerstand  
R

is  

R

typ  

T

A  

T

max  

T

min  

T

R  

V

eff  

V

K  

v

k  

Insulation resistance  
DC resistance, typical value  
Ambient temperature  
Upper category temperature  
Lower category temperature  
Rated temperature  
RMS voltage  
Isolationswiderstand  
Gleichstromwiderstand typisch  
Umgebungstemperatur  
Obere Kategorietemperatur  
Untere Kategorietemperatur  
Bemessungstemperatur  
Effektivdivnung  
Voltage drop  
Spannungsabfall  
Referred voltage drop in %  
Voltage line to earth; voltage line to ground  
Nominal voltage  
Bezogener Spannungsabfall in %  
Spannung Phase zu Erdpotential  
Nenndivnung  
V

LE  

V

N  

V

R  

V

peak  

V

test  

Rated voltage  
Bemessungsdivnung  
Spitzendivnung  
Peak voltage  
Test voltage  
Prüfdivnung  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
15
6
/21  

3-line filters  
B84143A*R107  
for converters and power electronics  
Symbol English  
German  
V

X  

V

Y  

X

L  

Z
Voltage over X capacitor  
Voltage over Y capacitor  
Inductive reactance  
Impedance  
Spannung über X-Kondensator  
Spannung über Y-Kondensator  
Induktiver Blindwiderstand  
Scheinwiderstand  
|Z|  
Impedance, absolute value  
Scheinwiderstand (Betragswert)  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
16
6
/21  

Important notes  
The following applies to all products named in this publication:  
1. Some
 
parts of this publication contain
statements about the suitability of our products for  
certain areas of application
. These statements are based on our knowledge of typical  
requirements that are often placed on our products in the areas of application concerned. We  
nevertheless expressly point out
that such statements cannot be regarded as binding  
statements about the suitability of our products for a particular customer application.
As  
a rule, we are either unfamiliar with individual customer applications or less familiar with them  
than the customers themselves. For these reasons, it is always ultimately incumbent on the  
customer to check and decide whether a product with the properties described in the product  
specification is suitable for use in a particular customer application.  
2. We
 
also point out that
in individual cases, a malfunction of electronic components or  
failure before the end of their usual service life cannot be completely ruled out in the  
current state of the art, even if they are operated as specified.
In customer applications  
requiring a very high level of operational safety and especially in customer applications in which  
the malfunction or failure of an electronic component could endanger human life or health (e.g.  
in accident prevention or life-saving systems), it must therefore be ensured by means of suitable  
design of the customer application or other action taken by the customer (e.g. installation of  
protective circuitry or redundancy) that no injury or damage is sustained by third parties in the  
event of malfunction or failure of an electronic component.  
3.
The warnings, cautions and product-specific notes must be observed
.  
4. In
 
order to satisfy certain technical requirements,
some of the products described in this  
publication may contain substances subject to restrictions in certain jurisdictions (e.g.  
because they are classed as hazardous)
. Useful information on this will be found in our  
any more detailed questions, please contact our sales offices.  
5. We
 
constantly strive to improve our products. Consequently,
the products described in this  
publication may change from time to time
. The same is true of the corresponding product  
specifications. Please check therefore to what extent product descriptions and specifications  
contained in this publication are still applicable before or when you place an order.  
We also
reserve the right to discontinue production and delivery of products
.  
Consequently, we cannot guarantee that all products named in this publication will always be  
available. The aforementioned does not apply in the case of individual agreements deviating  
from the foregoing for customer-specific products.  
6. Unless
 
otherwise agreed in individual contracts,
all orders are subject to our General Terms  
and Conditions of Supply
.  
17
6
/21  

Important notes  
7.
Our manufacturing sites serving the automotive business apply the IATF 16949  
standard
. The IATF certifications confirm our compliance with requirements regarding the  
quality management system in the automotive industry. Referring to customer requirements  
and customer specific requirements (“CSR”) TDK always has and will continue to have the  
policy of respecting individual agreements. Even if IATF 16949 may appear to support the  
acceptance of unilateral requirements, we hereby like to emphasize that
only requirements  
mutually agreed upon can and will be implemented in our Quality Management System.  
For clarification purposes we like to point out that obligations from IATF 16949 shall only  
become legally binding if individually agreed upon.  
8. The
 
trade names EPCOS, CarXield, CeraCharge, CeraDiode, CeraLink, CeraPad, CeraPlas,  
CSMP,  
CTVS, DeltaCap, DigiSiMic, ExoCore, FilterCap, FormFit, LeaXield, MiniBlue,  
MiniCell, MKD, MKK, ModCap, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, PhiCap,  
PowerHap, PQSine, PQvar, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD, SiMic, SIMID,  
SineFormer, SIOV, ThermoFuse, WindCap, XieldCap are
trademarks registered or pending  
in Europe and in other countries. Further information will be found on the Internet at  
Release 2020-06  
18
6
/21