TDK-B84143K0600S081

Part #TDK-B84143K0600S081
Download 
TDK-B84143K0600S081
EMC filters  
3-line filters  
for converters and power electronics  
Series/Type:  
B84143B/K*S080/S081
ꢀ
 
Date:  
-DQXDUꢀꢁꢂꢁꢃ  
©
ꢀ
TDK
ꢀ
Electronics
ꢀ
AG
ꢀ
202
ꢁ
.
ꢀ
Reproduction,
ꢀ
publication
ꢀ
and
ꢀ
dissemination
ꢀ
of
ꢀ
this
ꢀ
publication,
ꢀ
enclosures
ꢀ
hereto
ꢀ  
and
ꢀ
the
ꢀ
information
ꢀ
contained
ꢀ
therein
ꢀ
without
ꢀ
TDK
ꢀ
Electronics’
ꢀ
prior
ꢀ
express
ꢀ
consent
ꢀ
is
ꢀ
prohibited.  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
Power line filters for 3-phase systems  
Rated voltage V

R

: 300/520 V AC and 440/760 V AC  
Rated current I

R

: 180 A to 1600 A  
Construction  
3-line filters  
Metal case  
Versions  
B84143B*S080 type for standard applications  
B84143B*S081 type for applications with higher  
voltages  
Schematic picture  
B84143K*S081 type without Y capacitors, very low  
leakage current  
Features  
Easy to install  
Very compact design  
Low weight  
Design complies with IEC 60939  
UL and cUL approval  
Typical applications  
Frequency converters for motor drives  
Photovoltaics  
Wind farms  
Power supplies  
Terminals  
Busbars  
Marking  
Marking on component:  
Manufacturer’s logo, ordering code, rated voltage, rated  
current, rated temperature, climatic category, date code,  
approvals  
Minimum data on packaging:  
Manufacturer’s logo, ordering code, quantity, date code  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 2 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
Typical circuit diagrams  
B84143B*S08*  
B84143K*S081  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 3 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
Technical data and measuring conditions  
Rated voltage V

R  

Type S080:  
300/520 V AC (50/60 Hz)  
Type S081:  
440/760 V AC (50/60 Hz)  
Rated voltage for IT mains supply  
Type S080:  
Type S081:  
230/400 V AC (50/60 Hz)  
320/560 V AC (50/60 Hz)  
See also chapter “Technical information”, section  
8 “Energy supply networks”.  
Rated current I

R  

Referred to 40
°
C rated temperature (250 A … 1600 A)  
Referred to 60
°
C rated temperature (180 A)  
Rated peak withstand current I

pk  

Test voltage V

test  

According IEC 60439-1:2011, chapter 3.8.10.2;  
limited by I

2

t characteristics of fuse  
Type S080:  
2240 V DC, 2 s (line/line)  
2720 V DC, 2 s (lines/case)  
Type S081:  
3270 V DC, 2 s (line/line)  
2890 V DC, 2 s (lines/case)  
Overload capability (thermal)  
1.5
ꢀ
I

R

for 3 min per hour or  
2.5
ꢀ
I

R

for 30 s per hour  
Leakage current l

LK  

Climatic category (IEC 60068-1)  
Approvals  
At V

R

and 50 Hz  
25/100/21 (
ꢁ
25
°
C/+100
°
C/21 days damp heat test)  
UL 1283; CSA C22.2 No.8  
(Type *S080: 290/500 V; Type *S081: 350/600 V)  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 4 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
Characteristics and ordering codes  
Approvals  
I

R  

A
I

pk  

kA  
I

LK  

mA  
R

typ  

m
Ω  
Approx. weight
 
Ordering code  
kg  
V

R

= 300/520 V AC  
180  
250  
320  
400  
600  
25  
25  
50  
50  
50  
75  
75  
75  
75  
14  
14  
14  
14  
14  
14  
14  
14  
14  
0.110 5.0  
0.110 5.0  
0.051 7.2  
0.048 7.5  
0.043 7.8  
0.029 18.4  
0.029 18.5  
0.022 24.5  
0.022 24.5  
B84143B0180S080
×  
×
×
×
×
×
ꢁ
×
×
×
B84143B0250S080
×  
B84143B0320S080
×  
B84143B0400S080
×  
B84143B0600S080
×  
B84143B0800S080
ꢁ  
B84143B1000S080
×  
B84143B1250S080
×  
B84143B1600S080
×  
800  
1000  
1250  
1600  
V

R

= 440/760 V AC  
180  
180  
250  
250  
320  
320  
400  
400  
600  
600  
800  
800  
1000  
1000  
1250  
1250  
1600  
1600  
25  
25  
25  
25  
50  
50  
50  
50  
50  
50  
75  
75  
75  
75  
75  
75  
75  
75  
20  
ꢁ
20  
ꢁ
20  
ꢁ
20  
ꢁ
20  
ꢁ
20  
ꢁ
20  
ꢁ
20  
ꢁ
0.110 5.0  
0.110 5.0  
0.110 5.0  
0.110 5.0  
0.051 7.2  
0.051 7.2  
0.048 7.5  
0.048 7.5  
0.043 7.8  
0.043 7.8  
0.029 18.4  
0.029 18.4  
0.029 18.5  
0.029 18.5  
0.022 24.5  
0.022 24.5  
0.022 24.5  
0.022 24.5  
B84143B0180S081
×  
B84143K0180S081
×  
B84143B0250S081
×  
B84143K0250S081
×  
B84143B0320S081
×  
B84143K0320S081
×  
B84143B0400S081
×  
B84143K0400S081
×  
B84143B0600S081
×  
B84143K0600S081
×  
B84143B0800S081
ꢁ  
B84143K0800S081
ꢁ  
B84143B1000S081
×  
B84143K1000S081
×  
B84143B1250S081
×  
B84143K1250S081
×  
B84143B1600S081
×  
B84143K1600S081
×  
×
×
×
×
×
×
×
×
×
×
ꢁ
ꢁ
×
×
×
×
×
×
20  
ꢁ
×
= Approval granted:  
Type *S080 for 290/500 V  
Type *S081 for 350/600 V  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 5 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
Dimensional drawings  
B84143B/K0180S08*, B84143B/K0250S08* (180 A, 250 A)  
General tolerances according to ISO 2768
ꢁ
cL  
Dimensions in mm  
Busbar connection see section “Mechanical properties”  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 6 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
B84143B/K0320S08*, B84143B/K0400S08* (320 A, 400 A)  
General tolerances according to ISO 2768
ꢁ
cL  
Dimensions in mm  
Busbar connection see section “Mechanical properties”  
B84143B/K0600S08* (600 A)  
General tolerances according to ISO 2768
ꢁ
cL  
Dimensions in mm  
Busbar connection see section “Mechanical properties”  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 7 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
B84143B/K0800S08*, B84143B/K1000S08* (800 A, 1000 A)  
General tolerances according to ISO 2768
ꢁ
cL  
Dimensions in mm  
Busbar connection see section “Mechanical properties”  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 8 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
B84143B/K1250S08*, B84143B/K1600S08* (1250 A, 1600 A)  
General tolerances according to ISO 2768
ꢁ
cL  
Dimensions in mm  
Busbar connection see section “Mechanical properties”  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 9 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
Insertion loss
(typical values at Z = 50
Ω
)  
Filters for 180 A and 250 A  
Filters for 320 A and 400 A  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 10 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
Insertion loss
(typical values at Z = 50
Ω
)  
Filters for 600 A  
Filters for 800 A and 1000 A  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 11 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
Insertion loss
(typical values at Z = 50
Ω
)  
Filters for 1250 A and 1600 A  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 12 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
Cautions and warnings  
Please read all warning and safety notes carefully before installing the filter and putting it into op-  
eration (see
 
). The same applies to the warning signs on the filter. Please ensure that the signs  
are not removed nor their legibility impaired by external influences.  
Death, serious bodily injury and substantial material damage to equipment may occur if the appro-  
priate safety measures are not carried out or the warnings in the text are not observed.  
Using according to the terms  
The filters may be used only for their intended application within the specified values in low-  
voltage networks in compliance with the instructions given in the data sheets and the data book.  
The conditions at the place of application must comply with all specifications for the filter used.  
Warning  
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such  
as planning, assembly, installation, operation, repair and maintenance. They must be provided  
with the corresponding documentation.  
Danger of electric shock. Filters contain components that store an electric charge. Dangerous  
voltages can continue to exist at the filter terminals for longer than five minutes even after the  
power has been switched off.  
The protective earth connections shall be the first to be made when the filter is installed and the  
last to be disconnected. Depending on the magnitude of the leakage currents, the particular  
specifications for making the protective earth connection must be observed.  
Impermissible overloading of the filter or filter, such as with circuits able to cause resonances,  
impermissible voltages at higher frequencies etc. can lead to bodily injury and death as well as  
cause substantial material damages (e.g. destruction of the filter housing).  
Filters must be protected in the application against impermissible exceeding of the rated cur-  
rents by overcurrent protective devices.  
In case of leakage currents >3.5 mA you shall mount the PE conductor stationary with the re-  
quired cross section before beginning of operation and save it against disconnecting. For leak-  
age currents I

L

≤
10 mA the PE conductor must have a KU value

2)

of 4.5

3)

; for leakage currents  
1)  
I

L

>10 mA the PE conductor must have a KU value of 6

4)

.  
Output chokes and output filters must be protected in the application against impermissible ex-  
ceeding of the component temperature.  
The converter output frequency must be within the specified range to avoid resonances and un-  
controlled warming of the output chokes and output filters.  
Because the product can become very hot during operation, there is the risk of burns if  
touched. The product can remain hot for some time after the power is switched off!  
1) I

L

= leakage current let-go  
2) The
 
KU value (symbol KU) is a classification parameter of safety-referred failure types designed to ensure protection against hazardous  
body currents and excessive heating.  
3) A
 
value of KU = 4.5 with respect to interruptions is attained with: a) permanently connected protective earth connection
≥
1.5 mm

2

and  
b) a protective earth connection
≥
2.5 mm

2

via connectors for industrial equipment (IEC 60309
ꢁ
2)  
4) KU
 
= 6 with respect to interruptions is achieved for fixed-connection lines
≥
10 mm

2

where the type of connection and installation corre-  
spond to the requirements for PEN conductors as specified in relevant standards.  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 13 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
The table below summarizes the safety instructions that must be observed without fail. A detailed  
description can be found in the relevant chapters of the databook.  
Reference chapter  
(data book),  
Topic  
Instructions  
paragraph  
Selecting a filter  
When selecting a filter, it is mandatory to observe the
 
Selection guide for  
rated data of the equipment (such as its rated input  
current, rated voltage, harmonic content etc.) as well  
as the derating instructions in Chapters 9 and 10.  
converter filters  
Rated voltage  
When power distribution systems deviating from the  
symmetric TN-S system is to check the suitability of  
the filters and the allowed voltages including the fault  
cases.  
Power distribution  
systems,  
7
Protection from  
Active parts must be discharged within 5 s to a Safety
 
regulations,  
residual voltages  
voltage of less than 60 V (or 50
μ
C). If this limit
 
6.1  
Discharge resistors
 
cannot be observed due to the operating mode, the  
hazardous point must be permanently marked in a  
clearly visible way.  
Filters which are not permanently connected (e.g.  
when the test voltage is applied to the filter at the  
incoming goods inspection) must be discharged after  
the voltage has been switched off.  
Safety regulations,  
6.2  
Installing and  
removing of filters  
When installing and removing our filters, a
 
Safety regulations,  
voltage-free state must be set up and secured with
 
6.4  
observance of the five safety rules described in  
EN 50110-1.  
Installation  
Use in IT systems
 
The special features of the IT system (“first fault case”
 
Power distribution  
and other fault cases) shall be observed.  
system (network  
types), 7.6  
Safety notes on  
leakage currents  
The filter leakage currents specified in the data book
 
Leakage current,  
are intended for user information only.The maximum
 
8.4  
leakage current of the entire electrical equipment or
 
Leakage current,  
appliance has to be limited for safety reasons. Please
 
8.6  
obtain the applicable limits for your application from  
the relevant regulations, provisions and standards.  
Voltage derating  
If the permissible limits for the higher-frequency Voltage
 
derating,  
voltages at the filter are exeeded, the filter may be
 
9.8  
damaged or destroyed.  
Hazards caused by  
overloading the  
filters  
Current derating at
 
Non-observance of the current derating may lead to
 
Current derating,  
elevated ambient  
temperatures  
overheating and consequently represents a fire 10.1  
hazard.  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 14 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
Reference chapter  
(data book),  
Topic  
Instructions  
paragraph  
Protective earth  
connection at  
For operating currents greater than 250 A, we Mounting  
recommend the PE connection to be set up between
 
instructions,  
operating currents
 
the feed (filter: line) and output (filter: load) not via the
 
point 2  
>250 A  
PE terminal bolt in the filter housing.  
Mounting position  
Note the mounting position of the filters! It must Mounting  
always be ensured that natural convection is not instructions,  
impaired.  
point 13  
Long motor cables
 
Long motor cables cause parasitic currents in the  
Mounting  
installation. The cable lengths indicated for the output
 
instructions,  
chokes and output filters serve for orientation. The  
user must check the technical parameters and  
especially the choke temperatures for the respective  
application.  
point 15  
Display of ordering codes for TDK Electronics products  
The ordering code for one and the same product can be represented differently in data sheets,  
data books, other publications, on the company website, or in order-related documents such as  
shipping notes, order confirmations and product labels.
The varying representations of the or-  
dering codes are due to different processes employed and do not affect the specifications  
of the respective products
.  
Detailed information can be found on the Internet under  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 15 of 18  

3-line filters  
B84143B/K*S080/S081  
for converters and power electronics  
Symbols and terms  
Symbol English  
German  
α
Insertion loss  
Einfügungsdämpfung  
Bemessungskapazität  
Kapazität X-Kondensator  
Kapazität Y-Kondensator  
Spannungsabfall (Eingang zu Ausgang)  
Spannungsanstiegsgeschwindigkeit  
Frequenz  
C

R  

C

X  

C

Y  

Δ
V  
dv/dt  
f
Rated capacitance  
Capacitance X capacitor  
Capacitance Y capacitor  
Voltage drop (input to output)  
Rate of voltage rise  
Frequency  
f

M  

f

P  

Converter output frequency  
Pulse frequency  
Motorfrequenz  
Pulsfrequenz  
f

R  

f

res  

I

C  

I

LK  

I

max  

I

N  

Rated frequency  
Bemessungsfrequenz  
Resonanzfrequenz  
Strom durch Kondensator  
Filter-Ableitstrom  
Maximalstrom  
Nennstrom  
Resonant frequency  
Current through capacitor  
Filter leakage current  
Maximum current  
Nominal current  
I

op  

I

pk  

I

q  

I

R  

Operating current (design current)  
Rated peak withstand current  
Capacitive reactive current  
Rated current  
Betriebsstrom  
Bemessungs-Stoßstromfestigkeit  
Kapazitiver Blindstrom  
Bemessungsstrom  
I

S  

L
Interference current  
Inductance  
Störstrom  
Induktivität  
L

R  

L

stray  

P

L  

R
Rated inductance  
Stray inductance  
Power loss  
Resistance  
Bemessungsinduktivität  
Streuinduktivität  
Verlustleistung  
Widerstand  
R

is  

R

typ  

T

A  

T

max  

T

min  

T

R  

u

k  

V

eff  

V

K  

V

LE  

V

N  

V

R  

V

peak  

V

test  

V

X  

V

Y  

X

L  

Z
Insulation resistance  
DC resistance, typical value  
Ambient temperature  
Upper category temperature  
Lower category temperature  
Rated temperature  
Referred voltage drop in %  
RMS voltage  
Isolationswiderstand  
Gleichstromwiderstand typisch  
Umgebungstemperatur  
Obere Kategorietemperatur  
Untere Kategorietemperatur  
Bemessungstemperatur  
Bezogener Spannungsabfall in %  
Effektivdivnung  
Voltage drop  
Spannungsabfall  
Voltage line to earth; voltage line to ground
 
Spannung Phase zu Erdpotential  
Nominal voltage  
Rated voltage  
Peak voltage  
Nenndivnung  
Bemessungsdivnung  
Spitzendivnung  
Test voltage  
Prüfdivnung  
Voltage over X capacitor  
Voltage over Y capacitor  
Inductive reactance  
Impedance  
Spannung über X-Kondensator  
Spannung über Y-Kondensator  
Induktiver Blindwiderstand  
Scheinwiderstand  
|Z|  
Impedance, absolute value  
Scheinwiderstand (Betragswert)  
Please read
Cautions and warnings
and  
Important notes
at the end of this document.  
Page 16 of 18  

Important notes  
The following applies to all products named in this publication:  
1.
Some parts of this publication contain
statements about the suitability of our products for  
certain areas of application
. These statements are based on our knowledge of typical re-  
quirements that are often placed on our products in the areas of application concerned. We  
nevertheless expressly point out
that such statements cannot be regarded as binding  
statements about the suitability of our products for a particular customer application
.  
As a rule, we are either unfamiliar with individual customer applications or less familiar with  
them than the customers themselves. For these reasons, it is always ultimately incumbent on  
the customer to check and decide whether a product with the properties described in the  
product specification is suitable for use in a particular customer application.  
2.
We also point out that
in individual cases, a malfunction of electronic components or  
failure before the end of their usual service life cannot be completely ruled out in the  
current state of the art, even if they are operated as specified
. In customer applications  
requiring a very high level of operational safety and especially in customer applications in  
which the malfunction or failure of an electronic component could endanger human life or  
health (e.g. in accident prevention or lifesaving systems), it must therefore be ensured by  
means of suitable design of the customer application or other action taken by the customer  
(e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by  
third parties in the event of malfunction or failure of an electronic component.  
3.
The warnings, cautions and product-specific notes must be observed.  
4.
In order to satisfy certain technical requirements,
some of the products described in this  
publication may contain substances subject to restrictions in certain jurisdictions (e.g.  
because they are classed as hazardous)
. Useful information on this will be found in our Ma-  
any more detailed questions, please contact our sales offices.  
5.
We constantly strive to improve our products. Consequently,
the products described in this  
publication may change from time to time
. The same is true of the corresponding product  
specifications. Please check therefore to what extent product descriptions and specifications  
contained in this publication are still applicable before or when you place an order. We also  
reserve the right to discontinue production and delivery of products
. Consequently, we  
cannot guarantee that all products named in this publication will always be available. The  
aforementioned does not apply in the case of individual agreements deviating from the fore-  
going for customer-specific products.  
6.
Unless otherwise agreed in individual contracts,
all orders are subject to our General  
Terms and Conditions of Supply
.  
Page 17 of 18  

Important notes  
7.
Our manufacturing sites serving the automotive business apply the IATF 16949 stan-  
dard.
The IATF certifications confirm our compliance with requirements regarding the quality  
management system in the automotive industry. Referring to customer requirements and cus-  
tomer specific requirements (“CSR”) TDK always has and will continue to have the policy of  
respecting individual agreements. Even if IATF 16949 may appear to support the acceptance  
of unilateral requirements, we hereby like to emphasize that
only requirements mutually  
agreed upon can and will be implemented in our Quality Management System.
For clari-  
fication purposes we like to point out that obligations from IATF 16949 shall only become  
legally binding if individually agreed upon.  
8.
The trade names EPCOS, CarXield, CeraCharge, CeraDiode, CeraLink, CeraPad, CeraPlas,  
CSMP, CTVS, DeltaCap, DigiSiMic, ExoCore, FilterCap, FormFit, LeaXield, MiniBlue,  
MiniCell, MKD, MKK, ModCap, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, PhiCap,  
PowerHap, PQSine,
 
PQvar, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD, SiMic, SIMID,  
SineFormer, SIOV, ThermoFuse, WindCap, XieldCap are
trademarks registered or pend-  
ing
in Europe and in other countries. Further information will be found on the Internet at  
Release 2020-06  
Page 18 of 18