TE-Connectivity-7-1393252-8

Part #TE-Connectivity-7-1393252-8
Download 
TE-Connectivity-7-1393252-8
W6/W9
series  
Magnetic Hydraulic  
Circuit Breakers  
T
y
pical Resistance and Impedance  
DC  
Features  
50/60 Hz.  
Impedance  
(Ohms)  
90  
400 Hz.  
Impedance  
(Ohms)  
180  
• Designed for the international market.
 
UL Recognized, CSA Certified,  
and VDE approved.  
• Ratings to 50 amps.  
Current  
(Amps)  
0.2  
Resistance  
(Ohms)  
90  
• Heavy duty #10-32 stud connections. (W9)  
• Optional 10 amp auxiliary switch.  
• Optional snap-in mounting. (W6)  
• Several delay curve options.  
1
.
0  
2.0  
5.0  
10.0  
20.0  
30.0  
40.0  
50.0  
1
.
2  
0.28  
0.04  
0.013  
0.004  
0.0027  
0.002  
0.0015  
1
.
2  
0.28  
0.04  
0.013  
0.005  
0.004  
0.002  
0.0015  
2.0  
0.50  
0.05  
0.025  
0.0065  
0.004  
0.003  
•
T
r
ip-free operation.  
0.0025  
T
o
lerance: 0
.
1
 
–
4
.99
 
15%; 5 – 9.99
 
20%; 10 – 15
 
25%; 16 – 30
 
50%.  
Mechanical/Environmental Data  
Operating
T
e
mperature:
 
-40°C to +85°C.  
Humidity:
Meets requirements of Mil-STD-202 method 103.  
Shock:
T
e
sted per Mil-STD-202, method 213, test condition C  
(100g @ 6 ms).  
Vibration:
T
e
sted per Mil-STD-202, method 20
1
, 1
0
-55 Hz., 0.06″ (
1
.
52mm)  
total excursion in 2 planes.  
Agency Approvals  
UL:
Recognized as Supplementary Protector under UL 107
7
.
 
F
ile  
E69543.  
CSA:
Certified as a Supplementary Protector. File LR15734.  
VDE:
Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment)  
License No. 73782.  
Fungus And Moisture Resistance
:
Special moisture resistant finish  
applied to all ferrous parts.  
Plastic parts are made of inherently  
fungus resistant material.  
Electrical Data  
Marking:
W6 units have ON and OFF molded on the rocker of rocker  
actuated units (rocker actuated VDE units have international  
“1” and “0”). W9 units have ON and OFF molded into the area  
at the base of the toggle. International “1” and “0” symbols are  
marked on the toggle for both W6 and W9.  
Mounting:
Panel mounted units are mounted with two #6-32 screws  
from the front of the panel.
 
Metric models for use with M3 x  
0.5 screws are available.
 
Units with snap-in mounting option  
snap through the front of the panel.
 
T
o
m
aintain published  
performance specifications, units should not be mounted  
more than 90° from their normal upright position.  
Weight:
Approximately 2.5 ounces per pole.  
Auxiliary Switch:
See Auxiliary Switch Ratings
T
a
ble 2 for details.  
Calibration:
Breakers will hold 100% of rated current.
 
Breakers may trip  
between 101% and 124% of rated load (149% for 400 Hz.  
units and 134% for AC/DC units).
 
Breakers must trip at  
125% of rated load and above (150% for 400 Hz. units and  
135% for AC/DC units).  
Dielectric Strength:
 
50/60 or 400 Hz., 1500V: DC,
1
1
0
0
V
.  
Insulation Resistance:
 
1
0
0 Megohms at 500VDC.  
Endurance:
10,000 on/off cycles – 6000 at rated load, 4000 at no load.  
Units tested at six cycles per minute, 1 second on and 9  
seconds off at 25°C ambient.  
Approvals and Ratings
T
a
ble 1  
W6 Series  
UL/CSA (All Circuit Functions)  
W6 Series  
VDE (Circuit Function X)  
Current  
Phase  
Interrupting  
Rating  
(Amps)  
Current  
Phase  
Interrupting  
Maximum  
V
o
ltage  
Frequency  
(Hz)  
Capacity  
(Amps)  
Maximum  
V
o
ltage  
Frequency  
(Hz)  
Rating  
Capacity  
(Amps)  
(Amps)  
65  
277  
DC  
50/60  
50/60  
50/60  
400  
–
0.2 – 50  
0.2 – 20  
21 – 50  
0.2 – 20  
0.2 – 20  
21 – 50  
0.2 – 20  
2,000  
5,000  
2,500  
5,000  
2,500  
1
,
250  
2,500  
65  
250  
DC  
–
1
0.2-50  
0.2-30  
31-50  
2,000  
5,000  
2,000  
5,000  
1
50/60  
50/60  
50/60  
277  
1
250  
1
277/480  
250  
250  
250  
3Ø-Wye  
415/240  
3Ø  
0.2-30  
1
1
400  
400  
3Ø-Wye  
W9 Series  
UL/CSA (All Circuit Functions)  
W9 Series  
VDE (Circuit Function X)  
Current  
Phase  
Interrupting  
Rating  
(Amps)  
Current  
Phase  
Interrupting  
Maximum  
V
o
ltage  
Frequency  
(Hz)  
Capacity  
(Amps)  
Maximum  
V
o
ltage  
Frequency  
(Hz)  
Rating  
Capacity  
(Amps)  
(Amps)  
65  
277  
277/480  
250  
250  
DC  
50/60  
50/60  
400  
–
0.2 – 50  
0.2 – 50  
0.2 – 20  
0.2 – 50  
0.2 – 50  
2,000  
5,000  
5,000  
2,500  
2,500  
65  
250  
DC  
–
1
0.2-50  
0.2-30  
31-50  
2,000  
5,000  
2,000  
5,000  
1
50/60  
50/60  
50/60  
3Ø-Wye  
1
3Ø-Wye  
250  
1
415/240  
3Ø  
0.2-30  
400  
Approvals and Ratings
T
a
ble 2  
UL/CSA  
VDE  
Switch  
Number  
V
o
ltage  
50/60 Hz.  
Current  
(Amps)  
T
e
rminals  
WxTxL  
Switch  
Number  
V
o
ltage  
50/60 Hz.  
Current  
(Amps)  
T
e
rminals  
WxTxL  
A
125  
10  
.093 x .020 x .250  
(2.36 x .51 x 6.40)  
V1  
V2  
V3  
250  
250  
250  
10  
5
0
.
1  
.110 x
.
020 x .280  
(2.79 x .51 x
7
.
1
1
)  

Time vs. Current
T
r
ip Curves For W6 Series and W9 Series  
AC 50/60 Hz.  
DC & 50/60 Hz.  
400 Hz.  
CURVE 0 NON-TIME DEL
A
Y  
CURVE 2 AC VO
L
TAGE 50/60 Hz.  
CURVE 3 AC VO
L
TAGE 50/60 Hz.  
10,000  
1
0
00  
1
0
0  
10  
10,000  
1
0
00  
1
0
0  
10  
10,000  
1
0
00  
1
0
0  
10  
TRI
P
T
IMES  
OVERLOAD @
 
50/60 Hz. & DC
 
@ 400 Hz.  
OVERLOAD TRI
P
T
IMES  
(SEC.)  
OVERLOAD TRIPTIMES  
(SEC.)  
125%  
200%  
400%  
600%  
800%  
1
0
00%  
10 – 150  
2.2 – 20  
.2 – 2  
125%  
150%  
200%  
400%  
600%  
800%  
1
0
0 ms max.  
55 ms max.  
30 ms max.  
15 ms max.  
12 ms max.  
12 ms max.  
Ma
y
T
r
ip  
125%  
200%  
400%  
600%  
800%  
1
0
00%  
1 – 15  
.15 – 1
.
5  
.03 – .25  
1
0
0 ms max.  
30 ms max.  
15 ms max.  
12 ms max.  
12 ms max.  
.03 – .75  
.007 –
.
15  
.005 – .04  
.007 –
.
15  
.003 – .08  
.003 – .04  
1
1
1
.1  
.1  
.1  
.01  
.01  
.01  
.001  
0
.001  
0
.001  
0
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
125 150  
125 150  
125 150  
LOAD CURRENT AS A PERCENT  
LOAD CURRENT AS A PERCENT  
LOAD CURRENT AS A PERCENT  
OF BREAKER RATING  
OF BREAKER RATING  
OF BREAKER RATING  
MOTOR START  
CURVE 13 HIGH INRUSH 50/60 Hz.  
CURVE 12 HIGH INRUSH 50/60 Hz.  
CURVE 10 HIGH INRUSH 50/60 Hz. AC  
10,000  
1
0
00  
1
0
0  
10  
10,000  
1
0
00  
1
0
0  
10  
10,000  
1
0
00  
1
0
0  
10  
OVERLOAD TRI
P
T
IMES  
OVERLOAD TRI
P
T
IMES  
(SEC.)  
OVERLOAD TRI
P
T
IMES  
(SEC.)  
(SEC.)  
125%  
200%  
400%  
600%  
800%  
1
0
00%  
40 – 500  
9 – 1
0
0  
2 – 20  
125%  
200%  
400%  
600%  
800%  
1
0
00%  
10 – 150  
3 – 25  
.5 – 2.5  
.15 – 1  
.015 – .7  
.009 – .35  
125%  
200%  
400%  
600%  
800%  
1
0
00%  
.8 – 30  
.15 – 2.5  
.03 – .3  
.02 –
.
15  
.009 –
.
12  
.009 – .09  
.8 – 10  
.1 –
4
.5  
.009 – 2  
1
1
1
.1  
.1  
.1  
.01  
.01  
.01  
.001  
0
.001  
0
.001  
0
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
125 150  
125 150  
125 150  
LOAD CURRENT AS A PERCENT  
LOAD CURRENT AS A PERCENT  
LOAD CURRENT AS A PERCENT  
OF BREAKER RATING  
OF BREAKER RATING  
OF BREAKER RATING  
DC  
10,000  
1
0
00  
1
0
0  
10  
CURVE 3 DC VO
L
TAGE  
CURVE 53 DC HIGH INRUSH  
CURVE 2 DC VO
L
TAGE  
10,000  
1
0
00  
1
0
0  
10  
10,000  
1
0
00  
1
0
0  
10  
OVERLOAD TRI
P
T
IMES  
OVERLOAD TRI
P
T
IMES  
(SEC.)  
OVERLOAD TRI
P
T
IMES  
(SEC.)  
(SEC.)  
125%  
200%  
400%  
600%  
800%  
1
0
00%  
80 – 700  
15 – 150  
2 – 20  
125%  
200%  
400%  
600%  
800%  
1
0
00%  
.6 – 7  
.16 – 1
.
5  
.03 – .25  
.01 – .13  
.004 – .05  
.003 – .015  
125%  
200%  
400%  
600%  
800%  
1
0
00%  
2 – 55  
.60 – 8  
.1 – 1
.
5  
.02 – .5  
.004 – .05  
.004 – .025  
.70 – 10  
.10 – 3  
.01 – .1  
1
1
1
.1  
.1  
.1  
.01  
.01  
.01  
.001  
0
.001  
0
.001  
0
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
125 150  
125 150  
125 150  
LOAD CURRENT AS A PERCENT  
LOAD CURRENT AS A PERCENT  
LOAD CURRENT AS A PERCENT  
OF BREAKER RATING  
OF BREAKER RATING  
OF BREAKER RATING  
AC/DC  
AC 400 Hz.  
CURVE 34 DC, 50/60 Hz. STANDARD DEL
A
Y  
CURVE 2 AC VO
L
TAGE 400 Hz.  
CURVE 3 AC VO
L
TAGE 400 Hz.  
10,000  
1
0
00  
1
0
0  
10  
10,000  
1
0
00  
1
0
0  
10  
10,000  
1
0
00  
1
0
0  
10  
OVERLOAD TRI
P
T
IMES  
(SEC.)  
OVERLOAD TRI
P
T
IMES  
OVERLOAD TRI
P
T
IMES  
(SEC.)  
(SEC.)  
135%  
200%  
400%  
600%  
800%  
1
0
00%  
1 – 90  
.60 – 20  
.095 – 2  
.02 – .95  
.002 – .45  
.002 – .09  
150%  
200%  
400%  
600%  
800%  
1
0
00%  
.55 – 5.5  
.18 – 2  
.02 – .2  
.006 – .075  
.004 – .05  
.004 – .035  
150%  
200%  
400%  
600%  
800%  
1
0
00%  
5 – 60  
2.2 – 20  
.3 – 3.2  
.01 – .17  
.006 – .06  
.005 – .045  
1
1
1
.1  
.1  
.1  
.01  
.01  
.01  
.001  
0
.001  
0
.001  
0
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
1
0
0 200 300 400 500 600 700 800 900
 
1
0
00
1
1
0
0
1
2
00  
125 150  
135  
125 150  
LOAD CURRENT AS A PERCENT  
OF BREAKER RATING  
125 150  
LOAD CURRENT AS A PERCENT  
LOAD CURRENT AS A PERCENT  
OF BREAKER RATING  
OF BREAKER RATING  
Note:  
For instantaneous curves for all voltages refer to Curve 0 Non-Time Delay under the AC 50/60 Hz. heading.  
Pulse
T
o
lerance Specifications  
Pulse tolerance is defined as a single pulse of a half sine  
wave (1/2 cycle or 8 milliseconds) that will not trip the  
breaker. An inertia wheel for increased pulse tolerance is  
available by specifying “P” after the time delay curve  
number in the ordering information. The table at right lists  
pulse tolerance values of standard and inertia delay models.  
Pulse
T
o
lerance
V
a
lue  
Inertia  
Time  
Delay  
Curve  
V
o
ltage  
Standard  
Delay  
2
3
10  
12  
13  
7
.
5  
6
18  
18  
18  
18  
18  
30  
30  
30  
AC  
50/60 Hz.  
AC  
400 Hz.  
2
3
6.5  
5.5  
18  
18  
To
d
etermine pulse tolerance multiply breaker rating by value in table. For  
example, a 2A breaker with time delay curve 3 has a standard pulse tolerance  
of 12A (2A x 6). The same breaker with an inertia delay has a pulse tolerance  
of 36A (2A x 18).  

Ordering Information  
W6 Series  
T
y
pical Part No.
 
B
 
2-  
20  
Q
67- X  
2
W
1
1. Circuit Breaker Mounting:  
W = #6-32 mounting threads.  
M = M3.0 x 0.5 mounting threads.  
X = Snap-in mounting. (Not available in rocker actuated models.)  
2. Number of Poles:  
67 = Single pole  
68 =
T
w
o pole  
69 = Three pole  
X = Series trip  
70 = Four pole  
3. Circuit Function: (Only X is VDE approved)  
A = Series trip with auxiliary switch (.093” QC)  
4. Actuator: (One actuator per pole)  
1 = Black toggle  
2 = White toggle  
3 = Black rocker  
4 = White rocker  
5 = Red rocker  
6 = Grey rocker  
9 = Red toggle  
5.
T
e
rmination:  
Q = .250” QC (DIN 46 244) 25A Max. VDE  
S = #8-32 screw  
T = #10-32 screw  
Note:
“T” termination must be used for all ratings of 31 amps or above.  
6. Maximum Line
V
o
ltage: (See
T
a
ble 1 for current ranges)  
UL/CSA
1 = 277VAC, 50/60 Hz.  
VDE  
1 = 250VAC, 415/240VAC  
TYPES  
2 = 277/480  
3 = 250VAC, 400 Hz.  
5 = 65VDC  
TYPES
5 = 65VDC  
7 = AC/DC 250VAC, 415/240VAC, 65VDC  
(Delay curve 34 must be specified.
)  
7 = AC/DC 277VAC or 65VDC  
(Delay curve 34 must be specified.)  
7.
T
ime Delay Curve:  
0 = Instantaneous  
2 = Standard delay  
3 = Short delay  
10 = AC high inrush (Motor start)  
12 = AC high inrush version of #2  
13 = AC high inrush version of #3  
34 = Combination AC/DC standard delay  
Notes:
Curves may be specified with increased pulse tolerance for 1/2 cycle by  
adding “P” after curve, See delay curve section for availability and details
.  
53 = DC high inrush  
8. Amp Rating:  
0.20  
0.25  
0.50  
0.75  
1
.
0  
1
.
5  
2.0  
2.5  
3.0  
3.5  
4.0  
5.0  
6.0  
7
.
0  
7
.
5  
8.0  
9.0  
10.0  
11
.
0  
12.0  
15.0  
20.0  
25.0  
30.0  
35.0  
40.0  
45.0  
50.0  
Consult factory for  
other values.  
9. VDE Approval: (See
T
a
ble 2 for auxiliary switch ratings)  
Blank = UL/CSA approved breaker  
V = VDE approved breaker without auxiliary switch  
V1 = VDE approved breaker with 10 amp VDE auxiliary switch  
V2 = VDE approved breaker with 5 amp VDE auxiliary switch  
V3 = VDE approved breaker with 0
.
1
a
mp VDE auxiliary switch  
Stock Items – We recommend that our authorized distributors stock the following items for immediate deliver
y
.  
W67-A2Q12-5  
W67-A2Q12-10  
W67-X2Q10-3  
W67-X2Q10-5  
W67-X2Q12-2  
W67-X2Q12-3  
W67-X2Q12-5  
W67-X2Q12-7  
W67-X2Q12-10  
W67-X2Q12-15  
W67-X2Q12-20  
W67-X2Q12-30  
W67-X2Q13-1  
W67-X2Q13-2  
W67-X2Q13-3  
W67-X2Q13-10  
W67-X2Q13-15  
W67-X2Q13-20  
W67-X2Q13-25  
W67-X2Q13-30  
W67-X2Q50-5  
W67-X2Q50-10  
W67-X2Q52-5  
W67-X2Q52-10  
W67-X2Q52-15  
W67-X2Q52-20  
W67-X2Q52-30  
W67-X2Q
1
1
0
-15  
W67-X2Q
1
1
0
-20  
W68-X2Q12-3  
W68-X2Q12-5  
W68-X2Q12-7  
W68-X2Q12-10  
W68-X2Q12-15  
W68-X2Q12-20  
W68-X2Q12-25  
W68-X2Q12-30  
W68-X2Q13-15  
W68-X2Q
1
1
0
-10  
W68-X2Q
1
1
0
-20  
W69-X2Q12-5  
W69-X2Q12-10  
W69-X2Q12-15  
W69-X2Q12-20  
W69-X2Q12-25  
W69-X2Q12-30  
W69-X2Q
1
1
0
-20  
W69-X2Q
1
1
0
-30  
Ordering Information  
W9 Series  
T
y
pical Part No.
 
B  
1
W
1
2- 20  
91-  
X
1. Circuit Breaker Mounting:  
W = #6-32 mounting threads.  
M = M3.0 x 0.5 mounting threads.  
93 = Three pole  
2. Number of Poles:  
91 = Single pole  
92 =
T
w
o pole  
94 = Four pole  
3. Circuit Function: (Only X is VDE approved)  
A = Series trip with auxiliary switch (.093” QC)  
X = Series trip  
4. Actuator: (One actuator per pole):  
1 = Black toggle  
2 = White toggle  
5. Maximum Line
V
o
ltage: (See
T
a
ble 1 for current ranges)  
UL/CSA
1 = 277VAC, 50/60 Hz.  
VDE  
1 = 250VAC, 415/240VAC  
TYPES  
2 = 277/480  
3 = 250VAC, 400 Hz.  
5 = 65VDC  
TYPES
5 = 65VDC  
7 = AC/DC 250VAC, 415/240VAC, 65VDC  
(Delay curve 34 must be specified.)  
7 = AC/DC 277VAC or 65VDC  
(Delay curve 34 must be specified.)  
6. Time Delay Curve:  
0 = Instantaneous  
2 = Standard delay  
3 = Short delay  
10 = AC high inrush (Motor start)  
12 = AC high inrush version of #2  
13 = AC high inrush version of #3  
34 = Combination AC/DC standard delay  
Notes:
Curves may be specified with increased pulse tolerance for 1/2 cycle  
by adding “P” after curve. See delay curve section for availability and details.  
53 = DC high inrush  
7.
A
mp Rating:  
0.20  
0.25  
0.50  
0.75  
1
.
0  
2.0  
2.5  
3.0  
3.5  
4.0  
5.0  
6.0  
7
.
0  
7
.
5  
8.0  
9.0  
10.0  
11
.
0  
12.0  
15.0  
20.0  
25.0  
30.0  
35.0  
40.0  
45.0  
50.0  
Consult factory for other values  
1
.
5  
8. VDE Approval: (See
T
a
ble 2 for auxiliary switch ratings)  
Blank = UL/CSA approved breaker  
V = VDE approved breaker without auxiliary switch  
V1 = VDE approved breaker with 10 amp VDE auxiliary switch  
V2 = VDE approved breaker with 5 amp VDE auxiliary switch  
V3 = VDE approved breaker with 0
.
1
a
mp VDE auxiliary switch  
Stock Items – We recommend that our authorized distributors stock the following items for immediate deliver
y
.  
W91-X
1
12-1  
W91-X
1
12-2  
W91-X
1
12-3  
W91-X
1
12-5  
W91-X
1
12-7  
W91-X
1
12-10  
W91-X
1
12-15  
W91-X
1
12-20  
W91-X
1
12-40  
W91-X
1
12-50  
W91-X
1
13-5  
W91-X
1
13-10  
W91-X
1
13-15  
W91-X150-5  
W91-X152-10  
W91-X152-15  
W91-X152-20  
W91-X152-30  
W91-X152-40  
W91-X152-50  
W91-X
1
11
0
-20  
W92-X
1
12-1  
W92-X
1
12-2  
W92-X
1
12-3  
W92-X
1
12-5  
W92-X
1
12-7  
W92-X
1
12-10  
W92-X
1
12-15  
W92-X
1
12-20  
W92-X
1
12-25  
W92-X
1
12-30  
W92-X
1
12-40  
W92-X
1
12-50  
W92-X
1
13-15  
W92-X
1
13-20  
W92-X
1
11
0
-20  
W92-X
1
11
0
-30  
W93-X
1
12-5  
W93-X
1
12-10  
W93-X
1
12-15  
W93-X
1
12-20  
W93-X
1
12-25  
W93-X
1
12-30  
W93-X
1
12-40  
W93-X
1
12-50  
W93-X
1
11
0
-20  
W93-X
1
11
0
-30  

Outline Dimensions –
T
o
ggle Actuator Models.  
W6 Series  
Panel Mounting Cutout  
1
.
640  
(4
1
.
66)  
.245  
(6.22)  
.235  
(5.97)  
.750  
(19.05)  
Ø .625 +.010  
-.000  
15.88 +0.25  
-0.00  
1 PER POLE  
LINE  
LOAD  
(
)
O
N
A
B
29
°
 
1
.
660  
(42
.
16)  
1
.
530  
(38.86)  
30
°  
1
.
048  
(26.62)  
OFF  
Ø
.
156  
(3.96)  
2.040  
(5
1
.
82)  
.67  
(
1
7
.
02)  
[2 PLACES PER POLE]  
W6 Series  
1 Pole  
2 Pole  
3 Pole  
4 Pole  
Ø .590  
(15.00)  
1
.
500  
(38
.
10)  
2.250  
(5
7
.
15)  
.750  
(19.05)  
3.000  
(76.20)  
1
.
660  
(42
.
16)  
2.000  
(50.80)  
1
.
05  
(26.67)  
1
.
22  
(3
1
.
00)  
6.3
2
T
H’D. .14 (3.56) D
P
.
T
Y
P
.  
M3 X 0.5 OPTIONAL  
Note:  
Multi-pole models furnished  
with separate handle tie hardware.  
VDE Models  
W/Screw
T
e
rminals  
UL/CSA Models  
W/Screw
T
e
rminals  
UL/CSA/VDE Models  
W/Aux. Switch  
.235  
(5.9)  
2.032  
(5
1
.
61)  
2.38
“
A”
S
TYLE  
(60.45)  
.416  
(10.57)  
LINE  
LINE  
LINE  
.827  
(20.85)  
C
1
.
058  
(26.87)  
1
.
530  
(38.86)  
NO  
NC  
LOAD  
LOAD  
LOAD  
Notes:  
1. T
e
rminal
 
protrusion dimensions are referenced from back of mounting panel.  
2. Main
 
terminals are male quick connect type .250 (6.35) wide x .031 (.79)  
thick x .377 (9.58) long.
 
Optional 8-32 x .250 (6.35) or 10-32 x .250 (6.35)  
screw type.  
3. Panel
 
mounting cutout detail mtg. detail tol.:
 
.005 (
.
13) unless noted.
 
Add  
additional cutouts to correspond to number of poles.
 
Outline drawing  
tolerance .015
 
(.38) unless noted.
 
Dimensions in brackets ( ) are in millimeters.  

Outline Dimensions – Rocker Actuator Models  
W6 Series  
1 Pole  
2, 3 & 4 Pole  
3.000  
.805  
(20.45)  
1
.
640  
(76.20)  
(4
1
.
66)  
.750  
(19.05)  
2.250  
(5
7
.
15)  
4
POLE  
.390  
(9.91)  
1
.
500  
.375  
(9.53)  
3
(38
.
10)  
.180  
(4.57)  
POLE  
2 POLE  
LOAD  
D
A
.388  
(9.86)  
1
.
530  
(38.86)  
2.000  
(50.80)  
1
.
30  
(33.0)  
ON  
ON  
OFF  
ON  
ON  
ON  
1
.
660  
(42
.
16)  
2.600  
(66.04)  
OFF  
OFF  
OFF  
OFF  
LINE  
.235  
(5.97)  
.375  
(9.53)  
2.430  
(6
1
.
72)  
TAPPED FOR #6-32  
M3 X 0.5 OPTIONAL  
.750  
(19.05)  
.750  
(19.05)  
.750  
(19.05)  
Panel Mounting Cutout  
VDE Rocker Marking  
.750  
(19.05)  
.750  
(19.05)  
.750  
(19.05)  
.205  
(5.21)  
.375  
(9.53)  
.750  
(19.05)  
.375  
(9.53)  
1
.
250  
Notes:  
(3
1
.
75)  
.388  
(9.86)  
1.
O
utline
 
drawing tolerance
 
.015 (.38) unless  
noted. Dimensions in brackets ( ) are in  
millimeters.  
1
.
660  
2.000  
(50.80)  
(42
.
16)  
I
2.600  
(66.04)  
2. Mounting
 
Detail
T
o
l.:
 
.005 (
.
13) unless noted  
O
.750  
1 POLE  
2 POLE  
Ø
.
156  
(19.05)  
1
.
500  
(38
.
10)  
2.250  
(5
7
.
15)  
3.000  
(76.20)  
(3.96)  
TY
P
. 2  
PER POLE  
3 POLE  
4 POLE  
TAPPED FOR #6-32  
M3 X 0.5 OPTIONAL  
Outline Dimensions – Snap-in Mounted Models  
W6 Series  
1 Pole  
2 Pole  
3 Pole  
1
.
640  
(4
1
.
66)  
.245  
(6.22)  
2.250  
(5
7
.
15)  
.750  
(19.05)  
1
.
500  
(38
.
10)  
.235  
(5.97)  
.128  
(3.25)  
O
N
ON  
ON  
ON  
ON  
ON  
ON  
1.110  
(28
.
19)  
29
°  
1
.
530  
(38.86)  
2.650  
(6
7
.
31)  
30
°  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
2.040  
(5
1
.
82)  
.67  
(
1
7
.
02)  
4 Pole  
Panel Mounting Cutout  
1 Pole  
2 Pole  
3 Pole  
3.000  
(76.20)  
1
.
525  
(38.7)  
2.280  
(5
7
.
9)  
.770  
(19.6)  
3.040  
(7
7
.
2)  
ON  
ON  
ON  
ON  
2
.
187  
(55.55)  
OFF  
OFF  
OFF  
OFF  
Notes:  
Mounting Detail
T
o
l.:
 
.005 (
.
13) unless noted  
Panel Thickness: .047 (
1
.
2) to
.
110
(
2.8)  

Outline Dimensions  
W9 Series  
Series
T
r
ip Model  
Series
T
r
ip Model  
.750  
.375  
(9.53)  
.750  
(19.05)  
.750  
(19.05)  
1
.
845  
(46.86)  
(19.05)  
.398  
(10.77)  
.281  
.750  
(19.05)  
.375  
(9.53)  
.313  
(
7
.
95)  
(
7
.
14)  
LINE  
ON  
ON ON  
ON ON ON ON ON ON ON ON  
OFF OFF
 
OFF OFF
 
OFF OFF
 
OFF OFF  
.218  
(5.54)  
29
°  
30
°  
1
.
438  
(36.53)  
1
.
940  
2.065  
(52.45)  
2.50  
(63.5)  
(49.28)  
OFF OFF  
OFF  
LOAD  
2 POLE  
1
.
500  
(38
.
10)  
1 POLE  
.14  
(3.56)  
#10-32  
STU
D
T
ERMINATION  
2
.
10  
2.250  
(5
7
.
15)  
3
P
OLE  
TAPPED #6-32 X
.
16 (4.06)  
DEEP  
M3 X 0.5 OPTIONAL  
(53.34)  
3.000  
4 POLE  
2.50  
(64.00)  
.74  
(18.8)  
(76.20)  
Series
T
r
ip
 
Model  
Panel Mounting Cutout Detail  
With Common Enclosed Auxiliary Switch  
.750  
(19.05)  
.750  
(19.05)  
Notes:  
2.46  
(62.48)  
1. T
e
rminal
 
protrusion  
dimensions are referenced  
from the back of the  
mounting panel.  
2. Mounting
 
detail tolerance  
.005 (13) unless noted.  
3. Outline
 
drawing tolerance  
.015 (.38) unless noted.  
Dimensions in brackets ( )  
are in millimeters.  
.750  
(19.05)  
.385  
‘A’ STYLE  
.732  
(18.59)  
.281  
(
7
.
14)  
(9.78)  
.907  
(23.04)  
LINE  
C
1
.
450  
(36.83)  
2.065  
(52.45)  
1
.
940  
(49.28)  
NO  
NC  
LOAD  
.76  
(19.3)  
1 POLE  
2X Ø
.
156  
(3.96)  
PER POLE  
1
.
52  
2 POLE  
3 POLE  
4 POLE  
2.50  
(64.00)  
(38.6)  
2.28  
(5
7
.
9)  
3.04  
(7
7
.
2)  
T
y
co Electronics  
700 Westpark Drive  
Peachtree City, GA 30269-1498  
Specifications and availability subject to change without notice.  
13C9699 Printed
 
in U.S.A.
 
IH/2-00