TE-Connectivity-CR0002

Part #TE-Connectivity-CR0002
Download 
TE-Connectivity-CR0002
Specialty Relays  
AGASTAT GP/ML/TR Series, 10 Amp Control Relay,  
Non-latching, Latching & Timing Versions  
This consists of a W-shaped
 
The absence of metal-to-  
GP/ML/TR Design Features  
mechanism, shown in  
metal friction, the symmetri-  
cal design of the contact  
arrangement and the lack  
of heavy impacts provides  
a mechanical life of  
Among the advances  
Figure 1.
 
When the center  
of the W is moved vertically  
the lower extremities move  
closer to each other as can  
be seen in the illustration.  
The center of the W mecha-  
nism is connected to the  
moving core of the electro-  
magnet and the two lower  
points are connected to the  
moving contacts.  
AGAS
T
AT
c
ontrol relays  
offer over existing designs is  
a unique contact operating  
mechanism. An
 
articulated  
arm assembly amplifies the  
movement of the solenoid  
core, allowing the use of a  
short stroke coil to produce  
an extremely wide contact  
gap. The
 
long support  
100,000,000 operations.  
For use in AC circuits, the  
relay is supplied with a  
built-in rectification circuit,  
thus retaining the high DC  
efficiency of the electro-  
magnet. The
 
current peak  
on energizing is also elimi-  
nated and consequently  
the relay can operate with  
a resistance in series (e.g.  
for high voltages or for  
arms used in conventional  
relays are eliminated.
 
Both  
current capacity and shock/  
vibration tolerance are  
greatly increased, as well  
as life expectanc
y
.  
SERIES GP  
SERIES TR  
Two of these mechanisms  
are placed side-by-side to  
actuate the four contacts  
sets of the relay.
 
These  
arms act as return springs  
for their corresponding  
contacts.  
Product Facts  
n
Occupies very small panel  
space  
drop-out by shorting the  
coil). The
 
use of the rectifi-  
cation circuit offers still  
other advantages.
 
The  
same model can operated  
at frequencies ranging from  
40 to 400 cycles.
 
Operation  
of the relay is possible even  
with a low AC voltage.  
n
May be mounted singly, in  
continuous rows or in  
groups  
Design/Construction  
AGAS
T
AT
c
ontrol relays are  
operated by a moving core  
electromagnet whose main  
gap is at the center of the  
coil.  
The mechanical amplification  
of the motion of the electro-  
magnet permits a greater  
distance between the con-  
tacts, while the high effi-  
ciency of the electromagnet  
provides a nominal contact  
force in excess of 100  
n
Available with screw  
terminal molded socket.  
n
4 SPDT contacts  
The coil provides a low  
mean turn length and also  
assists heat dissipation.  
Since the maximum travel of  
the electromagnet does not  
provide optimum contacts  
movement, an ingenious  
amplifying device has been  
designed.  
n
Magnetic blowout device  
option increases DC  
The plastic dust cover has  
current carrying ability  
approximately ten times  
for both N.O. and N.C.  
contacts. In both AC and  
DC operation, the addition  
of the device will normally  
double the contact life, due  
to reduced arcing.  
grams on the normally open
 
two windows to facilitate  
contacts.  
cooling and also to allow  
direct mounting of the relay.  
All the contacts are posi-  
tioned well away from the  
cover and are well ventilated  
and separated from each  
other by insulating walls.  
n
File E15631, File LR29186  
R
R
Users should thoroughly review the  
technical data before selecting a product  
part number. It is recommended that users  
also seek out the pertinent approvals  
files of the agencies/laboratories and  
review them to ensure the product meets  
the requirements for a given application.  
Figure 1 —  
Illustration of Amplification  
This diagram illustrates  
amplification obtained by  
the articulated  
operating mechanism.  
Note: Seismic & radiation tested EG
P
,
E
ML and ETR models are  
available. Consult factory for detailed information.  
12–28  
Catalog 5-1773450-5  
Revised 3-13  
Dimensions are shown for  
Dimensions are in millimeters  
unless otherwise specified.  
USA: +1 800 522 6752  
Asia Pacific: +86 0 400 820 6015  
UK: +44 800 267 666  
For additional support numbers  
reference purposes only.  
Specifications subject  
to change.  

Specialty Relays  
AGASTAT GP/ML/TR Series, 10 Amp Control Relay,  
Non-latching, Latching & Timing Versions

(Continued)  

GP/ML Contact Data @ 25°C  
Arrangements
— 4 Form C (4PDT)  
Material
— Silver plated  
Expected Life
—  
Mechanical — 100 million operations  
Electrical — See chart and graph  
Contact Ratings and Expected Life  
Power Factor
 
Number of  
or Electrical  
Voltage (Amps) Time
 
Constant Operations  
Current  
Remarks  
540 VAC  
380 VAC  
380 VAC  
3
COS Ø = 0.5  
Resistive  
15,000 2
 
contacts in series  
10,000 2
 
contacts in parallel  
200,000  
15  
10  
Resistive  
380 VAC
 
3 x 3.3  
COS Ø = 0.8  
Resistive  
200,000  
3hp motor  
220 VAC  
220 VAC  
220 VAC  
20  
15  
10  
20,000 2
 
contacts in parallel  
20,000 2
 
contacts in parallel  
400,000  
COS Ø = 0.5  
Resistive  
220 VAC
 
3 x 6  
COS Ø = 0.8  
200,000  
1,500,000  
3,000,000  
2,000,000  
15,000,000  
30,000,000  
3 hp motor  
220 VAC  
220 VAC  
220 VAC  
220 VAC  
220 VAC  
120 VDC  
48 VDC  
48 VDC  
5
5
Filament lamps  
Resistive  
COS Ø = 0.25  
Resistive  
Resistive  
Resistive  
Resistive  
5 ms  
2.5  
2
1.25  
1.5  
10  
1.5  
Load Life Curve  
20,000,000 with
 
blow-out device  
1,000,000  
18,000,000  
Initial Dielectric Strength
—  
Between non-connected terminals —  
2,000V rms, 60 Hz  
Between non-connected terminals &  
relay yoke — 2,000V rms, 60 Hz  
Initial Insulation Resistance
—  
Between non-connected terminals —  
109 ohms at 500VDC  
Between non-connected terminals &  
relay yoke — 109 ohms at 500VDC  
Coil Operating Voltage  
Environmental Data  
Operating Temperature Range: 0°C to  
+60°C.  
DC  
AC, 50/60Hz  
24 120
 
220  
12  
Nominal Coil Voltage  
Minimum Pick-up  
Voltage at 20°C  
12  
24  
18  
19  
48  
36  
125 250  
94 187  
Vibration: Single axis fragility curve data  
are available on request at frequencies  
from 5 Hz. to 33 Hz.  
Shock: The relay, when kept energized  
by means of one of its own contact sets,  
will withstand 40g shock load when  
operating on DC, and 150g shock load  
on AC.  
9
19  
92  
175  
Minimum Pick-up  
Voltage at 40°C  
9.5  
38  
53  
100 200  
143 275  
20  
27  
102 188  
137 245  
Maximum voltage  
for continuous use  
13.5 27  
For 380VAC – Use 6800 ohms 4 watt resistor in series with 220VAC relay.  
For 440VAC – Use 8200 ohms 6 watt resistor in series with 220VAC relay.  
Drop-out voltage is between 10% and 40% of the nominal voltages for both DC and  
AC (For example:
 
in a 120 VAC unit, drop-out will occur between 12 and 48 volts.)  
DC relays will function with unfiltered DC from a full-wave bridge rectifier.  
Coil Data  
Voltage
— 24, 120 & 220VAC, 60 Hz;  
Add series resistor for 380-440VDC;  
12, 24, 48, 125 & 250VDC  
Mechanical Data  
Mounting Terminals
—  
16 flat base pins. Screw terminal sockets  
are available.  
Duty Cycle
— Continuous  
Nominal Coil Power
—  
6VA for AC coils; 6W for DC coils.  
There is no surge current during  
operation.  
Wire Connection
— The 16 flat pins  
are arranged in four symmetrical rows of  
four pins; the pitch in both directions  
being .394”.
 
Connection may be made  
to the relay by soldering.
 
Sockets are  
available with screw terminals.  
The internal wiring of the relay is also  
symmetrical as shown in the adjacent  
figure, allowing the relay to be inserted  
into the socket in either of two positions.  
Terminals B2 and B3 are provided as extra  
connections for special applications.  
Operate Data @ 20°C  
Operate Time at Rated Voltage
—  
Between energizing and opening of  
normally closed contacts — less than  
18 milliseconds on AC and less than 15  
milliseconds on DC.  
Release Time
—  
Between energizing and closing of  
normally open contacts — less than  
35 milliseconds on AC and less than  
30 milliseconds on DC.  
Between de-energizing and opening of  
normally open contacts — less than  
70 milliseconds on AC and less than  
8 milliseconds on DC.  
Weight
—  
10.9 oz. (308g) approximately  
Between de-energizing and closing of  
normally closed contacts — less than  
85 milliseconds on AC and less than  
25 milliseconds on DC.  
12–29  
Catalog 5-1773450-5  
Revised 3-13  
Dimensions are shown for  
Dimensions are in millimeters  
unless otherwise specified.  
USA: +1 800 522 6752  
Asia Pacific: +86 0 400 820 6015  
UK: +44 800 267 666  
For additional support numbers  
reference purposes only.  
Specifications subject  
to change.  

Specialty Relays  
AGASTAT GP/ML/TR Series, 10 Amp Control Relay,  
Non-latching, Latching & Timing Versions

(Continued)  

Ordering Information  
Typical Part No.
‰
 
GP  
I
N
1. Basic Series:  
GP = Non-latching Control Relay  
ML = Magnetic Latching Control Relay  
2. Coil Voltage:  
A = 12VDC  
B = 24VDC  
C = 48VDC  
D = 125VDC  
F = 250VDC  
G = 24VAC, 60 Hz.  
I = 120VAC, 60 Hz.  
J = 220VAC, 60 Hz.  
3. Options:  
N = Magnetic Blow-out Device  
Q = Light to indicate coil energization (GP onl
y
.
1
20VAC, 125VDC, 220VAC and 250VDC voltages only.)  
R = Internal diode to suppress coil de-energization transient. (GP onl
y
.
W
hen used on DC unit, relay release time increases to same value as AC unit).  
Our authorized distributors are more likely to maintain the following items in stock for immediate delivery.  
GPD  
GPDN  
Outline Dimensions  
Wiring Diagrams (Bottom Views)  
12–30  
Catalog 5-1773450-5  
Revised 3-13  
Dimensions are shown for  
reference purposes only.  
Specifications subject  
to change.  
Dimensions are in millimeters  
unless otherwise specified.  
USA: +1 800 522 6752  
Asia Pacific: +86 0 400 820 6015  
UK: +44 800 267 666  
For additional support numbers  

Specialty Relays  
AGASTAT GP/ML/TR Series, 10 Amp Control Relay,  
Non-latching, Latching & Timing Versions

(Continued)  

TR Series  
Expected Life
—  
Mechanical — 100 million operations  
Electrical — See load/life graph  
Initial Dielectric Strength
—  
Between terminals and case and between  
mutually-isolated contacts — 2,000VAC  
Initial Insulation Resistance
—  
Between non-connected terminals —  
109 ohms at 500VDC  
Between non-connected terminals &  
relay yoke — 109 ohms at 500VDC  
TR Design/Construction  
Timing Specifications  
Operating Mode
—  
On-Delay (Delay on energization)  
Timing Adjustment
—  
Internal fixed or internal potentiometer  
Product Facts  
n
8 timing ranges  
n
4 SPDT contacts  
Couples an advanced  
electromechanical design  
with a field-proven solid-  
state timing network, an  
adaptation of the circuit  
used in the AGAS
T
AT  
Timing Ranges
—  
.15 to 3 sec.  
.55 to 15 sec.  
1 to 30 sec.  
n
Magnetic blowout device  
option increases DC  
premium grade SSC Timer.  
current carrying ability  
approximately ten times  
for both N.O. and N.C.  
contacts. In both AC and  
DC operation, the addition  
of the device will normally  
double the contact life, due  
to reduced arcing.  
2 to 60 sec.  
This unique circuit also  
eliminates the need for sup-  
plementary temperature-  
compensation components,  
affording unusual stability  
over a realistically broad  
operating temperature  
4 to 120 sec.  
10 to 300 sec.  
1 to 30 min.  
Coil Data  
Voltage
— 120VAC, 50-60 Hz.; 24 &  
125VDC  
Transient Protection
—  
1,500 volt transient of less than 100  
microseconds, or 1,000 volts or less  
2 to 60 min.  
Accuracy
—  
Repeat —
 
2% as fixed temperature and  
voltage  
Overall —
 
5% over combined rated  
extremes of temperature and voltage  
range. It
 
also provides  
transient protection and  
protection against prema-  
ture switching of the output  
contacts due to power  
Environmental Data  
Operating Temperature Range
—  
0°C to +50°C  
Reset Time
— 75ms.  
Contact Data @ 25°C  
Arrangements
— 4 Form C (4PDT)  
Nominal Rating
— 10A @ 120VAC  
Contact Pressure
—  
Between movable and normally closed  
contacts — 30 g, typical.  
Mechanical Data  
Mounting Terminals
—  
16 flat base pins. Screw terminal sockets  
are available.  
interruption during timing.  
Weight
— 11 oz. (311g) approximately.  
Between movable and normally open  
contacts — 100 g, typical.  
12  
Ordering Information  
Typical Part No.
‰  
TR  
1
4
B
1
A
N
1. Basic Series:  
TR = Timing control relay  
2. Operation:  
1 = On-delay  
3. Output:  
4 = 4PDT (4 form C)  
4. Operating Voltage:  
B = 24VDC  
D = 215VDC  
I = 120VAC, 50/60 Hz.  
5. Timing Adjustment:  
1 = Internal fixed.  
3 = Internal potentiometer.  
6. Timing Range:  
A = .15 to 3 sec.  
B = .55 to 15 sec.  
C = 1 to 30 sec.  
D = 2 to 60 sec.  
E = 4 to 120 sec.  
G = 10 to 300 sec.  
I = 2 to 60 min.  
N = 1 to 30 min.  
Load Life Curve  
7. Options:  
N = Magnetic blow-out device.  
Our authorized distributors are more likely to maintain the following items in stock  
for immediate delivery.  
None at present.  
For Outline Dimensions see  
page 12-30  
Wiring Diagram (Bottom View)  
12–31  
Catalog 5-1773450-5  
Revised 3-13  
Dimensions are shown for  
reference purposes only.  
Specifications subject  
to change.  
Dimensions are in millimeters  
unless otherwise specified.  
USA: +1 800 522 6752  
Asia Pacific: +86 0 400 820 6015  
UK: +44 800 267 666  
For additional support numbers  

Specialty Relays  
AGASTAT GP/ML/TR Series, 10 Amp Control Relay,  
Non-latching, Latching & Timing Versions

(Continued)  

Accessories for GP/ML/TR Series Control Relays  
Front Connected Sockets  
Cat. No. CR0001  
With captive clamp terminals  
Cat. No. CR0002  
With (#6) binding head screws  
Cat. No. CR0095  
With (#6) screw terminals  
Cat. No. CR0067  
With (#6) screw terminals  
Hold Down (Locking) Springs  
Cat. No. CR0069  
Cat. No. CR0070  
Cat. No. CR0111  
For socket:
 
CR0067  
For socket:
 
CR0095  
For sockets: CR0001& CR0002  
Heavy-duty Hold Down (Locking) Straps  
*Cat. No. CR0133  
*Cat. No. CR0155  
For socket: CR0001 & CR0002  
For socket: CR0095  
* Catalog number includes strap, strap plate and necessary brackets.  
Magnetic Blowout Device  
Extracting Handle  
Cat. No. CR0190  
Cat. No. CR0179  
Reduces arcing on the relay contacts  
when they make or break contact, either  
upon energizing or de-energizing,  
resulting in less contact degradation.  
Extends the life of the contact.  
Used to remove G
P
,
M
L and TR units  
from mounting bases.  
12–32  
Catalog 5-1773450-5  
Revised 3-13  
Dimensions are shown for  
reference purposes only.  
Specifications subject  
to change.  
Dimensions are in millimeters  
unless otherwise specified.  
USA: +1 800 522 6752  
Asia Pacific: +86 0 400 820 6015  
UK: +44 800 267 666  
For additional support numbers