Technical data  
1. Mechanical Design  
Self-extinguishing plastic housing, IP rating IP40  
4. General data  
Operating time  
AC:  
Mounting position:  
any  
10ms  
13ms  
2. Coil  
DC:  
Duration of operation:  
AC-Type:  
100%  
Release time  
AC:  
8ms  
DC:  
3ms  
Type  
Rated voltage AC  
Coil resistance
Ω (±10%)  
Mechanical life:  
Electrical life:  
20 x 10

6

switching cycles  
10 x 10

4

switching cycles at  
12A / 250V AC (AC1)  
Reduction factors for other loads  
see diagrams page 2  
5g (10 to 150Hz)  
RA 524L  
RA 615L  
RA 730L  
24V AC  
115V AC  
230V AC  
158  
3610  
16100  
L
LED  
Vibration:  
Shock resistance:  
10g / 5g (NO/NC)  
Rated frequency:  
50/60 Hz  
Rated consumptiom (50Hz):
 
1.6VA  
5. Insulation (according to EN 60664-1)  
Must release voltage:  
T
o
lerance:  
≥
0.2 x U

N  

0.8 to 1.1 x U

N  

Insulation rated voltage:  
Dielectric strength test voltage:  
Coil – contact:  
250V AC  
2500V AC  
1500V AC  
2500V AC  
DC-Type:  
Contact – contact:  
Pole – pole:  
Type  
Rated voltage DC  
Coil resistance
Ω (±10%)  
Insulation:  
RA 012L  
RA 024  
12V DC  
160  
Coil – contact:  
basic  
Pole – pole:  
basic  
RA 024L  
RA 024.02L  
24V DC  
640  
Clearance contact – contact:  
Rated surge voltage:  
Overvoltage category:  
Contact – coil distance:  
Clearance:  
micro-disconnection  
4000V (1,2 / 50μs
)
 
III  
L
LED  
RA xxx.02  
gold-plated contacts  
≥
2,5mm  
≥
4 mm  
3
Creepage:  
Insulation pollution degree:  
Rated consumption:  
Must release voltage:  
T
o
lerance:  
0.9 W  
≥
0.1 x U

N  

0.8 to 1.1 x U

N  

6. Ambient conditions  
Ambient temperature:  
AC:  
3. Contacts  
-40 to +55°C  
-40 to +70°C  
-40 to +85°C  
Rated switching voltage:  
Switching voltage:  
250V AC  
DC:  
max. 440V AC  
min. 5V AC  
12A / 250V AC  
AC15: 3A
 
/ 120V  
Storage temperature:  
Rated load:  
AC1:  
1,5A / 240V (B300)  
370W (single-phase motor)  
12A / 24V DC  
AC3:  
DC1:  
DC13: 0,22A
 
/ 120V  
0,1A / 250V (R300)  
Rated current:  
12A  
Min. switching current:  
Rated inrush current:  
Breaking capacity:
 
AC1:  
DC1:  
5mA  
24A  
max. 3000VA  
max. 288W  
Min. 0.3W  
Contact resistance:  
Switching frequency:  
≤100mΩ  
max. 20/min at rated load AC1  
max. 300/min, no load  
AgNi or AgNi/Au 5µm (.02 gold-plated  
contacts)  
Contact material:  

RA – Coupling relays  
Reduction factors  
Connections  
Reduction of electrical life depending on load  
AC1  
3
Dimensions  
Switching capacity (kVA)  
Reduction of switching capacity depending on switching voltage  
50  
DC1  
12  
10  
5
2
1
0,5  
0,1  
10  
20  
30 40
 
50  
100  
200  
300  
DC switching voltage  
Reduction of electrical life depending on switching voltage  
RELEASE 2013/11  