TELE-Controls-Inc-RA-615L-N
| Part # | TELE-Controls-Inc-RA-615L-N |
| Download | TELE-Controls-Inc-RA-615L-N |
RA – Coupling relays
Coupling relays – Miniature power relay
Miniature power relay
2 change over contacts
Hand operation
Position indicator via LED
Plug-in housing
Technical data
1. Mechanical Design
Self-extinguishing plastic housing, IP rating IP40
4. General data
Operating time
AC:
Mounting position:
any
10ms
13ms
2. Coil
DC:
Duration of operation:
AC-Type:
100%
Release time
AC:
8ms
DC:
3ms
Type
Rated voltage AC
Coil resistance
Ω (±10%)
Mechanical life:
Electrical life:
20 x 10
6
switching cycles
10 x 10
4
switching cycles at
12A / 250V AC (AC1)
Reduction factors for other loads
see diagrams page 2
5g (10 to 150Hz)
RA 524L
RA 615L
RA 730L
24V AC
115V AC
230V AC
158
3610
16100
L
LED
Vibration:
Shock resistance:
10g / 5g (NO/NC)
Rated frequency:
50/60 Hz
Rated consumptiom (50Hz):
1.6VA
5. Insulation (according to EN 60664-1)
Must release voltage:
T
o
lerance:
≥
0.2 x U
N
0.8 to 1.1 x U
N
Insulation rated voltage:
Dielectric strength test voltage:
Coil – contact:
250V AC
2500V AC
1500V AC
2500V AC
DC-Type:
Contact – contact:
Pole – pole:
Type
Rated voltage DC
Coil resistance
Ω (±10%)
Insulation:
RA 012L
RA 024
12V DC
160
Coil – contact:
basic
Pole – pole:
basic
RA 024L
RA 024.02L
24V DC
640
Clearance contact – contact:
Rated surge voltage:
Overvoltage category:
Contact – coil distance:
Clearance:
micro-disconnection
4000V (1,2 / 50μs
)
III
L
LED
RA xxx.02
gold-plated contacts
≥
2,5mm
≥
4 mm
3
Creepage:
Insulation pollution degree:
Rated consumption:
Must release voltage:
T
o
lerance:
0.9 W
≥
0.1 x U
N
0.8 to 1.1 x U
N
6. Ambient conditions
Ambient temperature:
AC:
3. Contacts
-40 to +55°C
-40 to +70°C
-40 to +85°C
Rated switching voltage:
Switching voltage:
250V AC
DC:
max. 440V AC
min. 5V AC
12A / 250V AC
AC15: 3A
/ 120V
Storage temperature:
Rated load:
AC1:
1,5A / 240V (B300)
370W (single-phase motor)
12A / 24V DC
AC3:
DC1:
DC13: 0,22A
/ 120V
0,1A / 250V (R300)
Rated current:
12A
Min. switching current:
Rated inrush current:
Breaking capacity:
AC1:
DC1:
5mA
24A
max. 3000VA
max. 288W
Min. 0.3W
Contact resistance:
Switching frequency:
≤100mΩ
max. 20/min at rated load AC1
max. 300/min, no load
AgNi or AgNi/Au 5µm (.02 gold-plated
contacts)
Contact material:
RA – Coupling relays
Reduction factors
Connections
Reduction of electrical life depending on load
AC1
3
Dimensions
Switching capacity (kVA)
Reduction of switching capacity depending on switching voltage
50
DC1
12
10
5
2
1
0,5
0,1
10
20
30 40
50
100
200
300
DC switching voltage
Reduction of electrical life depending on switching voltage
RELEASE 2013/11
Subject to alterations and errors